Laserfiche WebLink
TLC RFI Transmission Process Page 1 of 1 <br /> RFI Cover Sheet <br /> our Log # : 52951 <br /> ENGINEERING <br /> FOR ARCHITECTURE <br /> Project : INDIAN RIVER COUNTY ADMIN COMPLEX Project #: 503036 . 05 <br /> RFI Name: FIRE DAMPER REQUIREMENT RM-054 <br /> Client RFI #: 052 <br /> Requestor: TONY DONADIO Opened : 10/13/2006 <br /> Firm: DONADIO & ASSOCIATES , ARCHITECTS Closed : 10/13/2006 <br /> PM / PE : JAMES WAMSLEY Division : 51 <br /> Recipient: CHRISTOPHER HUDSON Status: CLOSED <br /> Please note : The following RFI response is not intended to authorize any deviation or modification to the design <br /> documents except as specifically clarified below for this specific application and circumstance. <br /> Furthermore, this response is not intended to authorize any increase in construction cost, schedule <br /> or time extension, or construction in conflict with any applicable codes or specified design <br /> standards. . It is the responsibility of the Contractor to notify the design team immediately of any <br /> perceived scope , schedule, or cost impacts or adjustments . <br /> Comments <br /> 10/13/2006 This is correct a fire damper is required in the 6" duct penetrating the wall of Locker room 054 <br /> which is a two hour rated wall assymbly. This damper was added on shop drawings approved by <br /> TLC on 10/5/2006. <br /> . . .christopher hudson <br /> http://ticemp.tic-eng.com/Custom_Function/RFI/Transmit RFI .ASP?r1`i=52951 &TransType=EXT 10/ 13/2006 <br />