Laserfiche WebLink
PRODUCT • 4 <br /> Product Specification <br /> i , Product Ref ; ConCore° Panel 24 with PosiLock TIUnderstructure <br /> PART 3 - EXECUTION (e) Access floor installer shall keep the subfloor broom <br /> clean as installation progresses . <br /> • 3. 1 Preparation <br /> (f) Partially complete floors shall be braced against <br /> (a) Examine stnXharal subfloor for unevenness , shifting to maintain the integrity of the installed system <br /> irrpgularilies and dnr7rpness that would affect the quality where required . <br /> and execution of the work . Do not proceed with <br /> installation until structural floor surfaces are level , clean , <br /> (g) Additional pedestals as needed shall support panels <br /> at id dry as cot lileled by otf iers . where floor is disrupted by columns , walls , and cutouts . <br /> (b) Concr ete sealers , if used , shall be identified and (h) Understructure shall be aligned such that all <br /> uncut. <br /> proven to be compatible with pedestal adhesive . If other panels are interchangeable and fit snugly but do not <br /> than manufacturer 's recommended adhesives or bind when placed in alternate positions . <br /> _.sealers are used , verify that adhesive achieves bond to (i) Finished floor shall be level , not varying more than <br /> slab before commencing work . 0 . 062 in 10 feet or 0 . 125" overall . <br /> (c) Verify dimensions on contract drawings , including G) Installed panels shall be spaced so that the distance <br /> level of interfaces including abutting floor, ledges and from one end to the other of any line of 12 panels is not <br /> doorsills . less than 24 feet and does riot exceed 24 ' Ura <br /> (d) Coordinate location of mechanical and electrical (k) Where plenum beneath raised floor is designed <br /> work in underfloor cavity to prevent interference with to deliver conditioned air: Close coordination with all <br /> • access floor system pedestals . trade that work within the plenum cavity beneath the <br /> ' -- raised floor is required . All walls passing into this cavity <br /> (e) Mark pedestal locations an subfloor by use of a grid shall be run completely down to the floor slab <br />and <br /> (with a module equal to (lie width of five floor panels in sealed at floor slab line to avoid plenum <br /> air short <br /> both directions) to enable mechanical and electrical work <br /> circuiting through wall chase . All holes in wall within <br /> to proceed . Pedestal locations shall be established from cavity shall be sealed . Perimeters of raised floor that <br /> contract drawings or approved shop drawings . abut columns , walls and other constructions shall be <br /> (f) Proceed with installation only after completion of sealed to minimize unintended air leakage from plenum . <br /> overhead .construction within affected spaces . <br /> 11 . • 3. 3 Adjusting , Cleaning , and Protection <br /> • 3. 2 Installation (a) After completing installation , vacuum clean access <br /> (a) Pedestal locations shall be established from flooring and cover with continuous sheets of reinforced <br /> approved shop drawings so that mechanical and paper or plastic . Maintain protective covering until time <br /> electrical work can be installed without interfering with of substantial completion . 4 : 07 <br /> pedestal . installation . <br /> (b)After completing installation of access floor, trades <br /> (b) Installation of access floor shall be coordinated with are responsible for cleanup of their dust and/or <br /> other trades to maintain -the integrity of the installed debris producing operations , including vacuuming of <br /> system . Traffic shall not be permitted on any floor area subfloor area . Installed service boxes and diffusers to <br /> for 24 hours to allow the pedestal adhesive to set . be protected from physical damage and temporarily <br /> (c) Floor system and accessories shall be installed covered to prevent dust or debris from <br /> entering <br /> under the supervision of the manufacturer's authorized subfloor area . <br /> representative and according to manufacturer's (c) Replace access flooring panels that are stained , <br /> • rc cor i irnendnlions . scratched , otherwise damaged , or not complying with <br /> (d) No dust or debris producing operations by other specified requirements . <br /> trades shall be allowed in areas where access floor is (d) Acceptance: Contractor shall accept floor in whole <br /> being installed to ensure proper bonding of pedestals or in part prior to allowing use by other trades . Tall to srtbfloor. <br /> ACCESS FLOORS <br /> /0220 - 7 <br />