Laserfiche WebLink
FOR DETAILS OF LINE BEND & PIPE MAY <br /> FILLING SEE W - 11 ( A ) BE USED FOR FULL <br /> FLOW FLUSHING <br /> EXISTING MAIN <br /> + <br /> L\ NEW WATER MAIN <br /> EXISTING OR NEW LIMITS OF FLUSHING <br /> GATE VALVE <br /> ELEVATION <br /> N OTES <br /> 1. A FULL LINE FLUSH IS THE ONLY FLUSHING METHOD APPROVED FOR MAINS, <br /> ALL FIRE HYDRANTS AND DETECTOR CHECK VALVES SHALL BE INSPECTED AND TESTED <br /> TO ENSURE THAT NO FOREIGN OBJECTS IMPEDE THE FLOW OF WATER. <br /> 20 A PRESSURE GAUGE SHALL BE INSTALLED UPSTREAM OF THE FLUSHING P ❑INT , <br /> THE PRESSURE UPSTREAM SHALL NOT FALL BELOW 35 P ,S . I , <br /> 3 . PROVIDE ALL NECESSARY THRUST BLOCKS AND / OR OTHER RESTRAINTS, <br /> 4 . INDIAN RIVER COUNTY UTILITY PERSONNEL , AFTER A MINIMUM OF A 48 HOUR <br /> NOTICE BY THE CONTRACTOR , SHALL BE PRESENT FOR ALL FLUSHING <br /> ACTIVITIES AND SHALL OPERATE ALL EXISTING VALVES. <br /> vDRAWING <br /> INDIAN RIVER COUNTY FLUSHING No, <br /> DEPARTMENT OF Q z <br /> UTILITIES SERVICES � CONNECTION W - 7 <br /> �LORII� griea�eoe 200 <br />