Laserfiche WebLink
AWWA Standard C605, "Underground Installation of Polyvinyl Chloride (PVC) Pressure Pipe and <br /> Fittings for Water". Engineer shall be present during all testing, and final inspections. No hydrostatic <br /> testing against existing system valves shall be allowed until the section to be tested has been <br /> bacteriologically cleared. <br /> 2 .02 The new water system shall remain disconnected (connecting valve to be locked in the closed position) <br /> from existing water lines except for the temporary jumper connection. All water used to fill and test the <br /> new water system shall be obtained through the temporary jumper connection. Flushing shall only be <br /> conducted in accordance with the plans. <br /> 2 .03 The general procedure for chlorination shall be first to flush all dirty or discolored water <br /> from <br /> the lines, and then introduce chlorine in approved dosages in accordance with Table 11 - 1 through a <br /> tap at one end, while water is being withdrawn at the other end of the line. The chlorine solution <br /> shall remain in the pipeline for no less than 24 hours. <br /> 2 .04 Following the chlorination period, all treated water shall be flushed from the lines at their extremities <br /> and replaced with water from the distribution system. Bacteriological sampling and analysis of the <br /> replacement water shall then be made in the presence of the Engineer in full accordance <br /> with the AWWA Standard C-651 . The Contractor will be required to re-chlorinate, if necessary. The <br /> line shall not be placed in service until the requirements of the State and County Public Health <br /> Department are met. <br /> 2 .05 The Contractor shall make all arrangements necessary with an independent commercial laboratory <br /> approved by the Department of Health and Rehabilitative Service (HRS) for the collection and <br /> examination of samples of water from disinfected water mains. These samples shall be examined for <br /> compliance with HRS requirements. Sampling shall be made daily and continuously until two <br /> successive examinations are found satisfactory. Should three examinations be found unsatisfactory, <br /> the line shall be flushed and disinfected again. Certified copies of all laboratory analyses shall be <br /> provided to the Owner. The cost of all sampling, flushing, and disinfecting shall be included in the <br /> contract price and no additional charge shall be made to the Owner for this work. County personnel <br /> shall operate all valves and be present to determine volume of water used for flushing. <br /> (continued on next page) <br /> e <br /> 02519 — Testing and Disinfecting Water System <br /> 02519 - 2 <br />