I:otiLH-31 Or,U once cotilinuCd
<br />-1::-
<br />Cut said heaters shall not be installed behind doors, under or near towel racks,
<br />or near shower curtains or window curtains. Each heater must be on a separate
<br />ci!cuit til�th a miniru;a wire size of No. 12 AUIG or larger.
<br />(s) One branch -circuit for signs shall be provided for each store
<br />frontage for each individual occupancy, said outlets to terminate outside, on
<br />or naar the front of the building. Sign outlets and windo:•i lighting shall be
<br />controlled by wall stitches, (It is suggested that these switches be installed
<br />near panel, so that time clock installation, if desired, will be conveniently
<br />located and less unsightly,)
<br />(t) Sufficient bathroom and toilet lighting must be installed and
<br />must be controlled by,wall switches only,
<br />(u) For protection against rust or corrosion, all steel or iron out-
<br />let boxes, junction boxes, cabinets, -gutters, and similar type equipment subject
<br />to rust or corrosion, shall be protected with a zinc or cadmium coating by
<br />either the galvanizing or sherardizing process.
<br />(v) hiring of slim.line or end. to end fixtures shall be as follows:
<br />Asbestos 1,000 volt rio• 14 wire or RH No. 12 wire will be accepted .for circuit
<br />wiring of fixtures that are installed end to end, to the extent of the supply
<br />of that circuit pissing through fixture that it supplies. The only permitted
<br />use of the fixture as a raceway would be for those fixtures approved by the
<br />Underwriters for that purpose; with special raceways, and RH No. 12 wiring would
<br />be accepted for additional circuits when installed according to this approval.
<br />Gas and oil burning equipment: Each unit shall be on a separate
<br />circuit and be provided with a pilot light and ditch located near the entrance.
<br />to the room where unit is installed. Minimum wire size No. 12 or larger,
<br />(w) Swimming pools: All conduits, junction boxes, reinforcing
<br />steel, filter pump equipment, lighting fixtures and similar metallic equipment
<br />must be bonded together and connected to a coir -mon ground, Metallic parts of
<br />ladders and diving boards must also be grounded. All underwater pool lights
<br />must be of.approved low voltage type.
<br />Section 28, FEEDERS. The carrying capacity bf each feeder or sub -
<br />feeder shall be based on the number of separate circuits which it supplies,
<br />computed as follows:
<br />(1} Overhead lighting circuits--assu-;ed as having 1,000 watts per
<br />circuit for each 15 -amp, circuit..
<br />(2) Convenience outlet circuits --assured as having 1,000 watts per
<br />circuit.
<br />(3) Non -itemized -and heavy duty circuit --specified load for vrhich
<br />designed.
<br />(4) Underground direct burial circuits shall be adequately sleeved
<br />under slabs, sidewralks, roads, flower beds, or crhen entering
<br />or leaving a building,
<br />To the total of these three, such demand factors as permitted by
<br />N E -C should be applied.
<br />Section 29. VOLTAGE DROP. The maximum allowable voltage drop shall
<br />be as follo:•rs:
<br />(1) Lighting--iiains and Feeders co-:bined, 1% drop fro;n point of at-
<br />ter.'.-•Cnt to Service drops to point of distribution (panel) for branch circuits.
<br />i�rarc�es, 2 fro.- distribution panel to recei`:?rs.
<br />(2) Po::er--;:ains and, fe'ders combin-2d, 3;, fro;q point or attachment
<br />to service drop, to distribution panel. Branches, 1j from distribution point
<br />LC recei`:ccrs
<br />(3) . Lighting and pc)::. -r co.ibin.:A -Th.e naximust allowable voltage drop
<br />cold pow;��r co.-b-ined shall iie 1%, fro;a point of $Ul"1 'i CC` ClltrdiiC. to
<br />•;;:,t-iFution Point• firandh,!� shall bcr in accordance with the i:i)t)V;2 ?t
<br />)1 n drop.
<br />MAY 2 21974 BOOK 20` PAA0