Laserfiche WebLink
EXISTING UTILITY <br />SERVICE FROM <br />LOCAL UTILITY <br />EXISTING METER AND DISCONNECT ON SITE <br />(RACK WONTED SEPARATELY 0R AT METE) <br />7 EXISTING 20CA.SERWCE'TO AT&T <br />1 /,,— <br />EMERGENCY GENERATOR <br />SET (EC), 20KW, <br />FURNISHED &T. <br />RE: 1/E-3 1 5 <br />EXISTING GENERATOR FLANGED INLET <br />EX151100 UNNERSAL POWER CABINET (UPC) sO <br />EXISTING LOAD CENTER PMELBOARD •CCP•, <br />30 POLE.LUG5 ONLY. BOLT ON BREAKERS <br />RE: 3/E-2 2 <br />J)NF 1101 000040 00707; <br />p CONTRACTOR SHALL FURNISH AND INSTALL <br />CONDUITS AND POWER CONDUCTORS AS <br />INDICATED FROM GENERATOR 10 POWER CABINET. <br />p CONTRACTOR SHALL PROWDE AND INSTALL FEEDS <br />FROM POWER CABINET TO GENERATOR FOR <br />BARMY CHARGER AND BLOCK HEATER AS' <br />INDICATED. <br />p AUTOMATIC TRANSFER SWITCH (ATS), FURNISHED <br />BY CUSTOMER AND INSTALLED BY CONTRACTOR. <br />ATS IS 120/240/, 2 POLE. 200A, NEMA 38 <br />WITH SINGLE PHASE SEN5100, AUTOMATIC ENGINE <br />STARTING. UL USTEO 1000. <br />O THE COMPACTOR SHALL REFER TO CABINET <br />SPECIFICATIONS FOR AW14 1911100 TO EXTERNAL <br />DEVICES (GENERATOR). INTERIOR ALARMS ARE <br />POE-W1RED. <br />0 00 NOT BOND GENERATOR NEUTRAL TO GROUND <br />OR GENERATOR FRAME. GENERATOR NEUTRAL IS <br />BONDED TO SERVICE ENTRANCE NEUTRAL. BOND <br />VA SO0DLY GROUNDEO ATS (OPEN .TRANSHRON, <br />FLOATING NEUTRAL AT GENERATOR <br />CABLE AND CONDUIT SCHEDULE <br />N0. <br />FROM <br />TO <br />WIRES <br />600100 <br />C0SI0 <br />26 <br />FUNCTION <br />1SERVICE <br />PROWDER <br />PROPOSED ATS <br />(3) 3/0 <br />(1) 14 <br />_2• <br />POWER FEED . <br />5 <br />PROPOSED ATS <br />GENERATOR <br />(2) 110 <br />(1) 110 <br />1• <br />START CIRCUIT <br />GENERATOR <br />PROPOSED ATS <br />(3).3/0 <br />(1) 14 <br />2• <br />POWER FEED. <br />Q <br />PROPOSED ATS- <br />EXISTING CIRCUIT PANEL <br />(3) 3/0 <br />(1) 14 <br />2• <br />POWER FEED <br />® <br />ExIST1N6 CIRCUIT PANEL <br />GENERATOR <br />(4) 112 <br />(2) 112 <br />1• <br />20 AMPCI00 IT FO RGENERATEOR RY LOCK 0 ER, <br />BATTE© <br />PROPOSED 015 <br />EXISTING AMM <br />4 -PAR 24 An <br />N/A <br />1• <br />ALARIA <br />111101 PUNCH FROM AM. DOWN S B7 AT&TDE 24- OF SLACK 1660. LABEL ALL WWES <br />7O <br />GENERATOR <br />EXISTING ALARM <br />12 -PAR 24 ANC <br />N/A <br />1' <br />FlANALM PUNCHS DOWN IS BT PAT&TDTECH LIBEL ALL 0.1 ES <br />GONE LINE DIAGRAM <br />SCALE: N.T.S. <br />600506406 NOTES- <br />pl BOND 70 EXISTING EQUIPMENT <br />GROUND RING (1YP) <br />O 12 TINNED 060 IN 1/2• FLEX BOND <br />TO GENERATOR FRAME W/2 HOLE <br />BOLTED LUG AT CORNER (IYP) <br />O 3/4. O 0' COPPER 6R00N0 <br />ROD. TO BE INSTALLED WHEN <br />DISTANCE 70 Ex15TIN0 GROUND <br />RING EXCEEDS 25'. <br />RE: 3/6-2 <br />®TYPICAL .GROUNDING PLAN <br />2 SCALE: N.T.S. <br />HEW AT&T 5004 <br />GENERATOR ON <br />CONCRETE PAD <br />• <br />0 <br />1. NEW CENSET PROVIDED BY AT&T AND INSTALLED <br />BY CONTRACTOR. IT S THE RESPONSIBILITY OF <br />THE CONTRACTOR TO FURNISH AND INSTALL ALL <br />4ATERMLS, COMPONENTS, ETC. WHICH ARE NOT <br />PROVIDED BY AT&T.-OENSET MANUFACTURER OR <br />EOUIPRENT MANUFACTURER AND 70 FURN1SH A <br />COMPLETE AND OPERATIONAL SYSTEM. <br />2. AR. CONTROL. <br />ND INDICATORCONDUCS RUTE NEW UNDER FROOM OENSET 10 <br />COSTING AT&T EOUIPMENT CARINET5. <br />3. 4AINTAN ALL CLEARANCES AS REOUIRED BY THE <br />NATIONAL ELECTRICAL CODE. <br />4. PROVIDE AND INSTALL -TWO GROUND RODS WITH <br />INSPECTION SLEEVES (ONE AT EACH END OF <br />GENSET FRAME .161140 AN APPROVED TWO HOLE <br />CONNECTOR. BOND GROUND R00 TO NEAREST <br />SITE BURIED GROUNDING SYSTEM RING. PRO0DE <br />INSPECTION SLEEVE AT CONNECTION POINT. SEE <br />INSPECTION SLEEVE DETAILS. <br />5. BOND METALLIC CONDUITS 10 0011160 GROUND <br />RING (SISTER) AS' THEY CROSS USING PIPE <br />CLAMP. DO NOT EXOTHERMICALLY WELD TO <br />CONDUIT. <br />B. BOND AL1 EXTERIOR CONDUITS, PIPES AND <br />CYLINDRICAL METALLIC OBNECTS:WITH A <br />PENNUNION GT SERIES CLAMP, BLACKBURN GUY <br />SERIES CLAMP 0R A BURNDY CAR 300000 <br />SERIES CLAMP ONLY, NO SUBS2TUTES <br />ACCEPTED. <br />7: BOND FENCE POST TO GROUND RING' (MERE <br />APPLICABLE) USING AN EXOTHERMIC 0E10. <br />GRADE <br />LGROUND RING /2 ANC <br />COPPER WIRE 5010. TINNED <br />(FROM CRERAIOR) <br />GROUND ROD COPPERWELD <br />3/4•..0'-0• LONG (40x) <br />V <br />®GROUND ROD DETAIL (IF REQUIRED) <br />3 SCALE: N.T.S. <br />B+T GRP <br />at&t <br />row <br />wenn. o <br />GENERAL DYNAMICS <br />M <br />O <br />EXISTING WATF.R TOWER <br />PROJECT NO, <br />911113001 <br />CHECKED ID) <br />ISSUED 0011, <br />REY <br />art <br />ow. <br />9/8/14 <br />P RDN.I.R1 5C4CR <br />• <br />14141 <br />• 10001.•00 PCV. <br />'/15/1. <br />PR0W,11•A. REV[. <br />5/14/14 <br />CD01RK,0N <br />10/H/1. <br />R.. <br />CD,s14LC104 <br />BM ENGINEERING. INC. <br />27400 <br />ERPT,es'2/20/1 <br />+:11.1"..70S1747.1, -.R. Mf OetWUn. <br />SHEET NUANHro <br />E-2 <br />REVISION, <br />1 <br />