Laserfiche WebLink
QUESTION NO. 49 <br />Please confirm the Owner is providing the Threshold Inspection Services. <br />ANSWER NO. 49 <br />The General Contractor is responsible for providing the Threshold Inspection Services. <br />QUESTION NO. 50 <br />The Spec's call out for an Accordion Door and the plans show a Folding Partition with Pocket Doors. Please clarify. <br />ANSWER NO. 50 <br />The specifications call for both. 083513 Accordion Folding Fire Doors and 0835 Folding Doors. The fire doors are <br />noted as fire rated. <br />QUESTION NO. 51 <br />Please define if the linear lights are lay -in, surface, or pendant fixtures. If they are lay -in lights it is likely they will <br />work with the Silhouette grid system. Please advise. <br />ANSWER NO. 51 <br />These are lay -in. <br />QUESTION NO. 52 <br />Typically, there is a Steel I -Beam to support the door's weight. Plans do not show any steel above doors. Please <br />advise. <br />ANSWER NO. 52 <br />For NanaWall support, see detail 7/S1.07.03 showing new W8x18 support beam. For operable partition support, <br />see detail 3/S1.07.03 showing angle frame and steel channel support. <br />QUESTION NO. 53 <br />What type of Finish Material should we figure to cover the door with? Standard is Vinyl/Rib Tex. Please advise. <br />ANSWER NO. 53 <br />Utilize Nanawall as basis of design; powder coat aluminum, with opaque glass. <br />Page 13 of 20 <br />F:\Public Wodca\ENGINEERING DIVISION PROJECTS\I13S-S County Park Intergeneratiional Roc Facility Wdmim\ADDENDUM \Addendum No. 4 11-12-2014.doc <br />