My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
04/01/2014 (4)
CBCC
>
Meetings
>
2010's
>
2014
>
04/01/2014 (4)
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/24/2021 1:17:25 PM
Creation date
3/23/2016 9:18:29 AM
Metadata
Fields
Template:
Meetings
Meeting Type
BCC Regular Meeting
Document Type
Agenda Packet
Meeting Date
04/01/2014
Meeting Body
Board of County Commissioners
Supplemental fields
FilePath
H:\Indian River\Network Files\SL00000K\S0005ZY.tif
SmeadsoftID
14725
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
572
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
180' DOWNTURN BEND, 2" HDPE W/2" PLUG <br /> (SEE NOTE 6) <br /> METER BOX LID <br /> (OPEN POSITION) <br /> G <br /> GRADE ROADWAY RADE (SWALE) <br /> VALVE <br /> (MIN) <br /> BOX <br /> 2" LOCKING CURB STOP <br /> (BY CONTRACTOR) <br /> COMPRESSION APPROVED <br /> FITTINGS ° ° METER BOX <br /> • ° ° ° ° 24"x18" (MIN) <br /> •°• . .° ° <br /> fR.S.G.V. ° ° � 1 CUBIC FOOT <br /> ° •° ° ° ° °�3/4" GRAVEL OR <br /> (Iiiw ° ° ° ° ° CRUSHED ROCK <br /> • ° • ° ° °MARKER BALL <br /> ° <br /> 2" HDPE <br /> RESTRAINED PLUG (M.J.) HORIZONTAL DISTANCE EQUAL <br /> TO DEPTH OF COVER <br /> ELEVATION <br /> -RT- <br /> NOTES <br /> 1. BLOW-OFF TO BE LOCATED AT ALL PROPERTY LINES AND DEAD END LINES, AS REQUIRED BY <br /> IRCDUS ENGINEERING. <br /> 2. ALL MATERIALS ARE TO BE PER IRCDUS APPROVED MANUFACTURERS' PRODUCT LIST. <br /> 3. METHODS OF RESTRAINT AS APPROVED BY IRCDUS. <br /> 4. TRACE WIRE TO BE INSTALLED AS PER DETAIL M-13. <br /> 5. LOCATE MARKER BALLS ARE TO BE LOCATED ADJACENT TO ALL VALVE BOXES AND PLACED IN ALL <br /> METER BOXES WITHIN 24" FROM SURFACE. <br /> 6• THE DOWNTURN SECTION SHALL BE CONSTRUCTED BY IRCDUS WHEN A MAIN REQUIRES A BLOW OFF. <br /> THE DOWNTURN SECTION SHALL BE REMOVED AFTERWARD. ALL OTHER CONSTRUCTION TO <br /> BE BY THE CONTRACTOR. <br /> 7. ALL BLOW OFFS SHALL BE LOCATED WITHIN 4' OF A VALVE. <br /> WING <br /> INDIAN RIVER COUNTY �� VER MANUAL DR NOO. <br /> DEPARTMENT OF yz <br /> UTILITIES SERVICES 2 BLOW- OFF W- 3 <br /> �LORI�� MAM=4 <br />
The URL can be used to link to this page
Your browser does not support the video tag.