Laserfiche WebLink
36' X 36' X 8' THICK FIBERCRETE PAD AT EACH <br /> VALVE BOX IN PAVED AREAS (TYPE I) <br /> 24' X 24' X 8' THICK FIBERCRETE PAD AT EACH <br /> VALVE BOX IN UNPAVED AREAS (TYPE II) <br /> (SEE M-5) <br /> CURB BOX 2'0 TO HOUSE TRACE WIRE <br /> WITH DUCTILE IR❑N LID IS TO BE <br /> PROVIDED IN UNPAVED AREAS (TYPE II) <br /> aoo <br /> d� <br /> VALVE BOX LID (SEE NOTE 3) <br /> �n <br /> 40 BRASS INDICATOR (EXAMPLE) SHALL BE FLUSH WITH <br /> PAD/PAVEMENT AND SHALL BE WET SET IN CONCRETE OR <br /> DRIVEN/ANCH❑RED IN ASPHALT <br /> PLAN VIEW <br /> -T- <br /> NOTES <br /> 1. VALVE BOX LID SHALL BE PAINTED, BLUE — WATER <br /> GREEN — FORCE MAINS <br /> PURPLE — REUSE WATER <br /> BRINE — BROWN <br /> 2. IN UNPAVED AREAS (SEE M-5, TYPE II) A BRASS VALVE INDICATOR IS TO BE PROVIDED <br /> WITH ENGRAVED DIAGRAM OF VALVE LOCATION AND DESCRIPTION. (SEE EXAMPLE ABOVE) <br /> INDICATOR SHALL BE FLUSH WITH PAD/PAVEMENT. <br /> 3. VALVE BOX LID LOCATED IN PAVEMNT SHALL BE A DUCTILE IR❑N STAY—PUT COVER, MINIMUM 24 LBS. <br /> WITH A MINIMUM 6' LONG THR❑UT AND SHALL BE MARKED WITH RAISED LETTERS, 'WATER', 'SEWER', <br /> 'BRINE', OR 'REUSE WATER' AS APPLICABLE. <br /> 4. VALVE BOX SHALL COMPLY WITH FD❑T STANDARDS AS APPLICABLE. <br /> 5. NO VALVE RINGS ARE TO BE USED. <br /> 6. IN TYPE I, PAVED AREAS, THE VALVE BOX PAD TOP ELEVATION SHALL BE EVEN WITH THE ROCK <br /> GRADE TO ALLOW BOTH LAYERS OF ASPHALT TO COVER THE VALVE BOX PAD WITH THE FINAL <br /> ASPHALT LAYER FLUSH WITH THE TOP OF THE VALVE BOX. <br /> gSVER DRAWING <br /> INDIAN RIVER COUNTY �'p� NO. <br /> DEPARTMENT OF VALVE B O X P A D C <br /> UTILITIES SERVICES �� � M - 6 <br /> LORI�� KVM ems <br /> 113. ,14,T. <br />