Laserfiche WebLink
SECTION 1 <br /> WATER MAINS <br /> DUCTILE IRON PIPES AND FITTINGS <br /> 1.01 SCOPE <br /> This section covers cast ductile iron pipe and cast ductile iron fittings for <br /> water mains. <br /> 1.02 GENERAL <br /> A. Ductile iron pipe (D.I.P.) shall be allowed for use as water pipe <br /> where compatible with the specific conditions of the project. The <br /> use of material other than ductile iron may be required by Indian <br /> River County Department of Utility Services (IRCDUS) during <br /> construction permit review or by IRCDUS field personnel during <br /> construction if it is determined that ductile iron pipe is unsuitable <br /> for the particular application. <br /> B. All ductile iron pipe shall be manufactured in accordance with <br /> AWWA Specification C150 (A21.50-96), or latest revision and <br /> shall be pressure Class 300 or 350 minimum as depicted on Table <br /> 1.1 on page 1-2. All ductile iron pipe crossing under roadways <br /> and other trafficked areas shall be pressure class 350 minimum. <br /> C. Unless specifically indicated otherwise, restrained joint <br /> underground piping shall be manufactured restrained bell and <br /> spigot and above ground piping shall be flanged. <br /> D. Cutting of ductile iron pipe shall be by sawing only. <br /> 1.03 PIPE <br /> Ductile iron pipe shall be bell and spigot cast in accordance with AWWA <br /> Specification C150 (ANSI A21.50-96), or latest revision. Cast ductile iron <br /> shall have a minimum tensile strength of 60,000 psi, with a minimum yield <br /> strength of 42,000 psi. Pipe wall thickness shall be computed in <br /> accordance with AWWA Specification C150 (ANSI A21.51-96), or latest <br /> revision, using the physical characteristics cited above, with a minimum <br /> working pressure of 200 psi and a Laying Condition "Type 2." Unless <br /> otherwise indicated or specified herein, the pipe shall have the minimum <br /> wall thickness according to class designation for diameters shown. All <br /> pipe shall be given a minimum factory hydrostatic test of 500 pounds per <br /> square inch. <br /> 1 - 1 <br />