Laserfiche WebLink
August 24, 1962 <br />TO: General Contractors <br />FRCK; Nelson A. Faerber, A.I.A. <br />RR: Indian River County Sheriff Dept., Vero Beach, Fla. <br />SUBJ: Addendum #1 to Plans A Specifications <br />Item #1: Amend Sheet #S-1 and new sheet #S-2 will be <br />forwarded under separate cover. <br />Item #2: Due to the fact that electrical service at site <br />is a 180 volt to ground and high leg system, <br />electrical service to building as indicated on <br />drawings shall be altered as follows: <br />A) Connect old building service to new <br />service installing 400 amp entrance to <br />replace existing 100 amp. <br />B) 42 circuit panel indicated on drawings <br />shall be changed from 3 phase to single <br />phase panel. Three phase panel indicated <br />on drawings as air conditioning shall be <br />enlarged to accommodate elevator power plant. <br />Main switch gear to be located in storage ; <br />room area 103. <br />Item #3: Water service as indicated on drawings shall <br />be 411 meter with 2" service to building. <br />Item #4: Bid date shall be changed to Friday, Sept•. 21, <br />9:00 a.m. <br />. uwowa.a Ia+N k wUtD VERO BEACH, nORIDA <br />