Laserfiche WebLink
40 <br />• <br />40 <br />• The building is in good condition with no apparent signs of deterioration. <br />• The building's exterior walls are constructed of fully reinforced masonry. <br />• No evidence of degradation is present on roof. <br />• An Emergency Standby Power Generator exists on site. <br />Marginal characteristics of this facility includes <br />• No verification of wind parameters used in design but no apparent flaws were noted. <br />• The building has a flat, lightweight roof system. <br />• The building is within the Vulnerability Zone of two Section 302 facilities but with low release <br />potential. <br />• The structure provides no interior safe space. <br />Non-compliant characteristic of this facility include: <br />• Several hazards within lay -down range of building. <br />• The building has unprotected windows and doors that lead into shelter areas. <br />• The building's roof exceeds a 40 foot span. <br />Retrofit Recommendation: <br />• Have a structural engineer evaluate roof system to determine modifications required to resist <br />uplift and bending forces. Roof span exceeds 40 feet. <br />• Install shutters or other protective systems on unprotected systems windows to exterior doors to <br />meet the SBC Standard SSTs] 12-44 of Dade County version of the South Florida Building <br />Code (Section 2314.1, 2314.5 and 1-2314.4). <br />Minor (Please note that while these minor retrofit recommendations will enhance the integrity of <br />shelter space evaluated they will not increase potential usable shelter square footage.) <br />Remove potential lay -down hazards. <br />• Remove potential debris hazards. <br />