GENERAL NOTES: <br />1. ALL WORK PRESENTED IN THESE DRAWINGS MUST BE COMPLETED BY <br />THE CONTRACTOR UNLESS OTHERWISE SPECIFIED. <br />2. THE CONTRACTOR MUST HAVE A MINIMUM OF 5 YEARS OF <br />EXPERIENCE IN TOWER ERECTION AND RETROFIT SIMILAR TO THAT <br />DESCRIBED HEREIN. <br />3. ALL CONSTRUCTION IS TO BE COMPLETE IN ACCORDANCE WITH THE <br />ANSUASSE A10.48 AND ANSVIlA322 STANDARDS, THE CONTRACTOR <br />MUST HAVE CONSIDERABLE WORKING KNOWLEDGE IN THESE <br />STANDARDS TO ACCEPT THIS WORK. BY ACCEPTING THIS PROJECT. <br />THE CONTRACTOR IS ATTESTING THAT HE HAS SUFFICIENT <br />EXPERIENCE, ABILITY. AND KNOWLEDGE OF THE WORK TO BE <br />PERFORMED AND IS PROPERLY LICENSED AND REGISTERED TO <br />COMPLETE THIS WORK. <br />4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL <br />DIMENSIONS, ELEVATIONS. AND EXISTING CONDITIONS PRIOR TO <br />BEGINNING ANY MATERIAL ORDERS, FABRICATION OR CONSTRUCTION <br />WORK ON THIS PROJECT. ANY DISCREPANCIES SHALL BE IMMEDIATELY <br />BROUGHT TO THE ATTENTION OF THE EOR. THE DISCREPANCIES MUST <br />BE RESOLVED BEFORE THE CONTRACTOR MAY PROCEED WITH THE <br />PROJECT. <br />5. ANY WORK PERFORMED WITHOUT A PREFABRICATION MAPPING I$ <br />DONE AT THE RISK OF THE CONTRACTOR AND/OR FABRICATOR. <br />6. ALL MANUFACTURERS' INSTRUCTIONS FOR INSTALLATION MUST BE <br />FOLLOWED EXACTLY AS SPECIFIED. WHEN CONFLICTING WITH THESE <br />DRAWINGS, THE MANUFACTURER SPECIFICATIONS SHALL GOVERN. <br />7. ALL MATERIALS AND EQUIPMENT USED IN THE INSTALLATION OF THESE <br />DRAWINGS SHALL BE IN NEW OR GOOD WORKING QUALITY, FREE <br />FROM DEFECTS AND FAULTS AND IN CONFORMANCE WITH THE <br />CONTRACT DOCUMENTS. ALL SUBSTITUTIONS MUST BE GIVEN <br />WRITTEN APPROVAL FROM THE EOR PRIOR TO INSTALLATION. ALL <br />MATERIALS SHALL BE WARRANTED FOR ONE YEAR FROM <br />ACCEPTANCE DATE. <br />8. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL <br />INTENDED CONSTRUCTION ACTIVITY INCLUDING MATERIALS. ACCESS <br />AND WORK SCHEDULE. THE CONTRACTOR IS RESPONSIBLE FOR <br />OBTAINING ALL PERMITS AND WILL BE RESPONSIBLE FOR ABIDING BY <br />ALL REQUIREMENTS AND CONDITIONS OF THE PERMITS. WHEN <br />APPLICABLE, THE CONTRACTOR MUST NOTIFY THE APPLICABLE <br />JURISDICTION PRIOR TO BEGINNING OF ANY CONSTRUCTION. <br />S. THE CONTRACTOR IS RESPONSIBLE FOR ALL CONSTRUCTION MEANS <br />AND METHODS. INCLUDING BUT NOT LIMITED TO, ERECTION PLANS, <br />RIGGING PLANS, CLIMBING PLANS, AND RESCUE PLANS. <br />CONSTRUCTION OF THE PROPOSED WORK SHALL MEET ANSUASSE <br />A10.48. OSHA, AND GENERAL INDUSTRY STANDARDS. ALL RIGGING <br />PLANS SHALL ADHERE TO ANSUNA-322 INCLUDING THE REQUIRED <br />INVOLVEMENT OF A QUALIFIED ENGINEER FOR CLASS IV <br />CONSTRUCTION. <br />10. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE <br />INSTALLATION PROCEDURE AND SEQUENCE TO INSURE THE SAFETY <br />OF THE STRUCTURE AND ITS COMPONENTS DURING ERECTION <br />AND/OR FIELD ALTERATIONS. THIS INCLUDES, RUT IS NOT LIMITED TO, <br />THE ADDITION OF TEMPORARY BRACING. GUYS OR TIE -DOWNS THAT <br />MAY BE NECESSARY, SUCH MATERIAL SHALL BE REMOVED AFTER THE <br />COMPLETION OF THE PROJECT. <br />11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INITIATING, <br />MAINTAINING. AND SUPERVISING ALL SAFETY PRECAUTIONS AND <br />PROGRAMS IN CONNECTION WITH THIS PROJECT. THE CONTRACTOR IS <br />RESPONSIBLE FOR ENSURING THAT THIS PROJECT AND RELATED <br />WORK COMPLIES WITH ALL APPLICABLE LOCAL, STATE, AND FEDERAL <br />SAFETY CODES AND REGULATIONS GOVERNING THIS WORK. <br />12. THE CLIMBING FACILITIES. SAFETY CLIMB AND ALL PARTS THEREOF <br />SHALL NOT BE IMPEDED. MODIFIED OR ALTERED WITHOUT THE <br />EXPRESS WRITTEN APPROVAL OF THE EOR. <br />13, INCORRECTLY FABRICATED, DAMAGED, MIS -FITTING, OR <br />NON -CONFORMING MATERIALS AND CONDITIONS SHALL SE REPORTED <br />TO THE EOR PRIOR TO ANY REMEDIAL OR CORRECTING ACTION. ALL <br />ACTIONS SHALL REQUIRE EOR APPROVAL. <br />STEEL: <br />1. THE FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL <br />CONFORM TO THE LATEST AISC CODE AND ASTM SPECIFICATIONS. <br />2. HOLES SHALL NOT BE TORCH CUT THROUGH STRUCTURAL STEEL FOR <br />FABRICATION. ALL STEEL FABRICATION MUST FOLLOW AISC <br />SPECIFICATIONS. <br />3. HOT -DIP GALVANIZE ALL ITEMS AFTER FABRICATION IN COMPLIANCE <br />WITH ASTM A-123 UNLESS OTHERWISE SPECIFIED. ALL NEW STEEL IS <br />TO BE PAINTED TO MATCH THE EXISTING STEEL. <br />4. NEW STEEL MEMBERS MUST HAVE SINGLE DRILLED HOLES. SLOTTED <br />AND DOUBLY DRILLED HOLES ARE NOT ACCEPTABLE MEANS OF <br />FABRICATION UNLESS OTHERWISE SPECIFIED. <br />S. ALL CONNECTIONS NOT DETAILED IN THESE DRAWINGS MUST BE <br />DETAILED BY THE STEEL FABRICATOR IN ACCORDANCE WITH THE <br />LATEST AISC SPECIFICATIONS. <br />6. ALL BOLTED CONNECTIONS MUST BE INSTALLED TO A <br />SNUG -TIGHTENED CONDITION PER AISC -SPECIFICATION FOR <br />STRUCTURAL JOINTS USING ASTM 325 OR A490 BOLTS' SECTION 8.1 <br />UNLESS OTHERWISE SPECIFIED. <br />7. CONTRACTOR MAY BE REQUIRED TO STACK WASHERS FOR BOLTS <br />WHERE THREADS ARE EXCLUDED FROM SHEAR PLANE TO OBTAIN <br />SNUG TIGHT INSTALLATION. A NUT LOCKING DEVICE MUST BE <br />INSTALLED ON ALL PROPOSED AND/OR REPLACED BOLTS. GALVANIZED <br />ASTM 325 OR M90 BOLTS SHALL NOT BE REUSED. <br />COLD GALVANIZATION• <br />1. ALL DAMAGED SURFACES SHALL BE REPAIRED HATH A <br />COLD -GALVANIZING COATING CONFORMING TO ASTM 780. THIS <br />COATING SHALL BE APPLIED BY BRUSH. THE GALVANIZING COMPOUND <br />SHALL CONTAIN A MINIMUM OF 95%s PURE ZINC. THE FINISHED <br />COATING SHALL BE A MINIMUM THICKNESS OF 4 MILS. <br />2. CONTRACTOR TO USE ZINGA OR ZRC COLD GALVANIZATION <br />COMPOUNDS OR APPROVED EQUIVALENTS. <br />3. CLEAN AREAS TO BE PREPARED AND REMOVE SLAG FROM WELDS FOR <br />TREATMENT ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. <br />4. IF THE TOWER IS PAINTED. ALL TREATED AREAS ARE TO BE BRUSH <br />PAINTED TO MATCH THE TOWER AFTER COLD GALVANIZING <br />COMPOUND IS ALLOWED TO CURE. <br />U-NOLTE• <br />1. ALL U -BOLTS ARE TO BE ASTM A36IA307, SAE 429 OR. 2 UNLESS <br />OTHERWISE SPECIFIED. <br />2. U -BOLTS SHALL MEET REQUIREMENTS OF ASME 018.31.5-2011 BENT <br />BOLTS. <br />3. U�BOLT ASSEMBLY SHALL COME COMPLETE WITH NUTS (ASTM A563). <br />WASHERS (ASTM F436). AND LOCK WASHERS. <br />4. FULL U -BOLT ASSEMBLY TO BE HOT -DIP GALVANIZED PER ASTM <br />A153/A153M OR A123. AS APPLICABLE. <br />MODIFICATION MATERIALS <br />SCOPE SHAPE GRADE YIELD STRENGTH (Fy) ULTIMATE STRENGTH (FU) <br />ALL PIPE A53 GR. B 35 KSI 60 KSI <br />ALL THREADED RODS SAE 429 GR. 2 57 KSI 74 KSI <br />I NO. I DATE I DESCRIPTION I BY I <br />`tttttllllll//�// <br />Mp <br />No. 0200 <br />��Q •' STATE OF <br />S10NA� t�,`` <br />RAPHAEL I. MOHAMED. PE. PEnO <br />SENIOR DIRECTOR OF ENGINEERING <br />FL PE LICENSE NO. 82846', FL COA NO. 32141 <br />I HEREBY CERTIFY THAT THIS ENGINEERING <br />DOCUMENT WAS PREPARED BY ME OR UNDER MV <br />DIRECT PERSONAL SUPERVISION AND THAT I AM A <br />DULY LICENSED PROFESSIONAL ENGINEER UNDER <br />THE LAWS OF THE STATE OF FLORIDA. <br />a <br />omasiec <br />NNworkSdullorls <br />iis� �wrssulre loi <br />RJPWETv er Hor�w <br />REP90WLiKw o9 CAu9Nc ro BE <br />aF �uI�Ec.hElKOR�c 6o�u - 5510�I <br />SITE NAME. WEST VERO <br />SITE NUMBER: FLFPU1005 <br />FA NUMBER: 10032101 <br />MNS ENG. NUMBER. 43368-MMDI <br />SITE ADDRESS'. <br />5850 COLLEGE LANE. VERO BEACH <br />INDIAN RIVER COUNTY, FL 32966 <br />DRAWN BY VB <br />CHECKED BY: NDN <br />APPROVEDBY.RM <br />SCALE'. N.T.S <br />GENERALNOTES <br />REV <br />N-2 o <br />