Laserfiche WebLink
For maximum credit in the Schedule, all hydrants should be inspected twice a year. The <br /> inspection should include operation of the fire hydrant, a test for leaks (using domestic <br /> pressure), and a flushing of the hydrant. Records should be kept of inspections. <br /> Water System:Vero Beach <br /> Item 630.A"Inspection(HI):" Time Interval <br /> Most recent inspection was Jan 01, 2009 <br /> 1" prior inspection was Jun 01, 2008 0.5 year <br /> 2n4 prior inspection was Feb 01, 2007 1.25 years <br /> Review of Inspection(HI): Earned Credit Credit Available <br /> 85 100 <br /> Note:The inspection dates shown are for the water system which includes the largest <br /> concentration of hydrants in the graded area; however,the earned credit reflects the <br /> frequency of inspection for all applicable water systems. <br /> For maximum credit in the Schedule, all hydrants should be conspicuous, well located for use <br /> by a pumper and in good condition. There were 20 hydrants examined in this FSRS item. <br /> Item 630.B"Condition(HF):" Maximum Factor <br /> Standard: 1.0 <br /> There were 20 hydrants considered in standard condition. <br /> Usable: 0.5 <br /> There were 0 hydrants considered in usable condition. <br /> Not Usable: 0.0 <br /> There were 0 hydrants considered not usable. <br /> Review of Condition(HF): <br /> Earned Credit Credit Available <br /> 1.00 1.0 <br /> The points calculated for the inspection and condition of hydrants for Vero Beach resulted in <br /> the following: <br /> CIC = 2.55 <br /> ®ISO Properties,Inc,2007 Page 33 <br /> 109 <br />