Laserfiche WebLink
The final step in determining the credit for Water Supply is to add up the following three <br /> components: <br /> Earned Credit <br /> Item Credit Available <br /> 616. Credit for Supply System (CSS) 25.43 35 <br /> 621. Credit for Hydrants(CH) 2.00 2 <br /> 631. Credit for Inspection and Condition(CIC) 2.40 3 <br /> Total Credit 29.83 40 <br /> If the score Indian River CO FD achieved for the water supply system was translated into a <br /> 100 point scale instead of the 40 points actually used, the relative Fire Suppression Rating <br /> Schedule classification for this section of the review would be a(relative)Class 3. <br /> 1111111111 <br /> Divergence considers a difference between the protection provided by the Fire Department <br /> and the Water Supply. This difference would prevent the better feature from being utilized to <br /> its fullest extent. Therefore, an adjustment is made to reflect any difference between these <br /> two features. Because of the difference in total weights assigned to the two features, the total <br /> for the Fire Department, which has the higher total weight, is adjusted to make the <br /> comparison reflect the relative adequacies of the two features. <br /> The expression (CWS)-0.804 in the following formula is the Divergence calculation: <br /> PPC = I (CFA + CFD + CWS) - 0.5 {I (CWS) -0.8 (CFD) (} ] <br /> 10 <br /> PPC = [ (9.23 + 28.36 + 29.83) - 0.5 (J (29.83) -0.8 (28.36) 1) <br /> 10 <br /> olSO Properties.Inc.,2007 Page 34 <br />