Laserfiche WebLink
Item #10: Draftstopping at Administration Building: Is located on Sheet LS- 1 per wall rating legend as a <br /> "Long dash, dot, long dash". Draftstopping material is '/x" drywall applied to 3 5/8", 25 gauge <br /> steel studs at 24" o/c extended from top of wall partitions to underside of deck. Wall shall be <br /> taped and mudded. <br /> Item #11 : Door Schedule Sheet A-4 : Doors #6 & #7 require 45 minute rating on doors and frames to <br /> comply with Life Safety requirements . Specifications section 08710, headings #6 and #5 are <br /> correct. <br /> Item #12 : Air Compressor: (Note for Clarification) : 220V, 5 horse power, 175psi , vertical tank, unit is to <br /> be located in the mechanic bay per Sheet A-2. Sheets E-4 & E-7 denote the power circuit and <br /> panel MB- 12 : 14. Sheet P-3 denotes airline piping routing and condensate thru-wall drain <br /> location. Sheet P-4 denotes air-line piping routing and the isometric drawing of a typical air <br /> drop . <br /> Item #13 : Sheet A- 14 (Note for Clarification): Elevations A/A- 14 and B/A- 14 are "Women" not men and <br /> elevation C/A- 14 is men, not women. <br /> Item #14: Bath Accessories (Note for Clarification) : All fixed mirrors shall be 18" x 30" per specification <br /> section 10800, (2 .08)(A) in lieu of sizes depicted on drawings . Add one additional mirror over <br /> the "Men' s" sink in Administration Building. Toilet room elevation B/A- 1 on sheet A- 1 is <br /> incorrect at the dimension of the toilet paper dispenser. The 36" dimension is to the far edge of <br /> the dispenser, NOT to the centerline. Sheet ACC is correct, and this is a maximum dimension. <br /> Provide a single heavy duty clothes hook in the men and women shower rooms on the frame <br /> wall that separates the two rooms. Hook as specified with backing in specification section <br /> 10800, 2 .09, and mounted at 48" max A.F.F . for accessibility compliance. Provide a shelf with <br /> mop and broom holder in Mechanical Room #2 above the mop sink S-3 . Unit per specification <br /> section 10800, 2 . 10. No diaper changing stations are required for this project. <br /> Item #15 : Women ' s Shower Room Shower: Shall be the same wall and pan detail as 2/A- 14. Cultured <br /> marble wall panels to 8 ' -0" height. <br /> Item #16: Threshold Building: None of the three buildings in this complex requires Threshold Inspection <br /> Services. Criteria for this requirement are a) greater than 3 stories in height, b) greater than 50 ' <br /> in height, c) assembly occupancy classification over 5 ,000 square feet and 500 people. <br /> Item #17: Metal Roofing Clarification: The metal roofing on all three (3) buildings shall be Englert (or <br /> approved equal) Series S2500 Roofing, with 2" mechanically seamed, 180 degree seam, 24 <br /> gauge roofing with optional ribs, and 16" centers on seams. Englert Series 52500 meets UL and <br /> ASTM standards for structural roofing when applied directly over purlins. Refer to <br /> Specifications Section 07610 for acceptable manufacturers. Roofing assembly shall meet all <br /> requirements of the FBC 2004 for hurricane wind resistance in a coastal zone at 135 mph. <br /> (Note: This project is permitted under FBC 2004 with 2005 amendments, and interpolated wind <br /> speed of 135 mph) . Refer to sheet S- 1 for complete information. All clips, closures, and <br /> fasteners shall be as recommended by the manufacturer of the roofing assembly. Local Englert <br /> rep is Tom Blowers at 813-446-5303 . <br /> - 3 — <br /> F:IEngineeringlCapital Projects10701 IRC PARKS COMPLEXIAddendumsJACParks Maintenance Complex Addendum #2. doe <br />