My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
2009-192
CBCC
>
Official Documents
>
2000's
>
2009
>
2009-192
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/10/2016 11:41:36 AM
Creation date
9/30/2015 11:37:50 PM
Metadata
Fields
Template:
Official Documents
Official Document Type
Contract
Approved Date
07/14/2009
Control Number
2009-192
Agenda Item Number
8.I.
Entity Name
DeAngelis Diamond Construction
Subject
Contract IRC Parks Maintenance Complex
Area
5500 77th St.
Project Number
0701
Bid Number
2009043
Supplemental fields
SmeadsoftID
6815
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
478
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
FORT PIERCE ENGINEERING, INC. IRC Maintenance <br /> individual alarm inputs or normal system responses (outputs) for alarms, without changing the <br /> system's executive programming or affecting operation of the rest of the system. How to do this <br /> must be included in the training required to be given to the owner's designated personnel (see <br /> 8 .6), and must also be part of the written documentation provided by the fire alarm equipment <br /> supplier. <br /> 1 .5 A Fire Alarm Control Unit (FACU) is required and shall be located in the reception area of the <br /> main building. Consult with the local fire official prior to precisely locating the FACU. <br /> 1 .6 The FACU and all other control equipment locations, including any transponders, sub-panels, and <br /> booster power supplies, must be protected by a spot type smoke detector located within 15 feet of <br /> the equipment (measured horizontally). <br /> 1 . 7 A supervised "AHU Shutdown Defeat" switch must be provided in/adjacent to the FACU or as a <br /> key-operated function in the Remote Annunciator (if provided). The switch must cause a system <br /> "trouble" indication when it's placed in the off-normal (" Shutdown Defeated") position. <br /> 1 . 8 Reserved. <br /> 1 .9 Reserved. <br /> 1 . 10 The fire alarm system must include an LED-type "zone" annunciator at (or in) the FACU, or in <br /> another location if acceptable to the AHJ. As a minimum, this annunciator is to indicate the <br /> specific type of alarm or supervisory signal (smoke detector, waterflow, sprinkler valve closed, <br /> etc.), for groups of devices. The facility shall, at a minimum, be divided into the following zones: <br /> 1 ) Office Building West; 2) Office Building East; 3 ) Office Building Ducts ; 4)Maintenance <br /> Building; 4) Storage Bays <br /> 1 . 11 Alarm notification appliances (audible and visible) are to comply with NFPA 72 and the Florida <br /> Building Code for intensity and placement. The audible evacuation signal shall be the ANSI <br /> S3 .41 three-pulse temporal pattern. All strobe lights installed in a single space must be <br /> synchronized. Contact the AHJ for additional information or to seek approval of any alternative <br /> design. <br /> 1 . 12 Alarm notification appliance (NAC) circuits shall be NFPA 72 Style Y (Class B). The load <br /> connected to each circuit must not exceed 80% of rated module output and the coverage of each <br /> circuit in the main building shall not exceed half of the main building. The NAC voltage drop <br /> during alarm must not exceed 14% of the voltage measured across the batteries at that time. To <br /> achieve this, the design must consider wire size, length of circuit, device load, inherent voltage <br /> loss within the FACU's power supply, etc. The contractor shall use power outage testing to verify <br /> that the NAC circuit was designed and installed properly. <br /> 1 . 13 The following protection against voltage transients and surges must be provided by the fire alarm <br /> equipment supplier, and installed by the electrical contractor: <br /> On AC Input: A feed-through (not shunt-type) branch circuit transient suppressor such as the EFI <br /> E100HW120, Leviton 51020-OWM, Emerson/Northern Technologies TCS-HWR, Transtector <br /> ACPIOOBW series, or any equivalent UL 1449 - 2nd Edition Listed device submitted to and <br /> 16965 FIRE DETECTION & ALARM SYSTEM Page 3 OF 10 <br />
The URL can be used to link to this page
Your browser does not support the video tag.