Laserfiche WebLink
FORT PIERCE ENGINEERING, INC. IRC Maintenance <br /> individual alarm inputs or normal system responses (outputs) for alarms, without changing the <br /> system's executive programming or affecting operation of the rest of the system. How to do this <br /> must be included in the training required to be given to the owner's designated personnel (see <br /> 8 .6), and must also be part of the written documentation provided by the fire alarm equipment <br /> supplier. <br /> 1 .5 A Fire Alarm Control Unit (FACU) is required and shall be located in the reception area of the <br /> main building. Consult with the local fire official prior to precisely locating the FACU. <br /> 1 .6 The FACU and all other control equipment locations, including any transponders, sub-panels, and <br /> booster power supplies, must be protected by a spot type smoke detector located within 15 feet of <br /> the equipment (measured horizontally). <br /> 1 . 7 A supervised "AHU Shutdown Defeat" switch must be provided in/adjacent to the FACU or as a <br /> key-operated function in the Remote Annunciator (if provided). The switch must cause a system <br /> "trouble" indication when it's placed in the off-normal (" Shutdown Defeated") position. <br /> 1 . 8 Reserved. <br /> 1 .9 Reserved. <br /> 1 . 10 The fire alarm system must include an LED-type "zone" annunciator at (or in) the FACU, or in <br /> another location if acceptable to the AHJ. As a minimum, this annunciator is to indicate the <br /> specific type of alarm or supervisory signal (smoke detector, waterflow, sprinkler valve closed, <br /> etc.), for groups of devices. The facility shall, at a minimum, be divided into the following zones: <br /> 1 ) Office Building West; 2) Office Building East; 3 ) Office Building Ducts ; 4)Maintenance <br /> Building; 4) Storage Bays <br /> 1 . 11 Alarm notification appliances (audible and visible) are to comply with NFPA 72 and the Florida <br /> Building Code for intensity and placement. The audible evacuation signal shall be the ANSI <br /> S3 .41 three-pulse temporal pattern. All strobe lights installed in a single space must be <br /> synchronized. Contact the AHJ for additional information or to seek approval of any alternative <br /> design. <br /> 1 . 12 Alarm notification appliance (NAC) circuits shall be NFPA 72 Style Y (Class B). The load <br /> connected to each circuit must not exceed 80% of rated module output and the coverage of each <br /> circuit in the main building shall not exceed half of the main building. The NAC voltage drop <br /> during alarm must not exceed 14% of the voltage measured across the batteries at that time. To <br /> achieve this, the design must consider wire size, length of circuit, device load, inherent voltage <br /> loss within the FACU's power supply, etc. The contractor shall use power outage testing to verify <br /> that the NAC circuit was designed and installed properly. <br /> 1 . 13 The following protection against voltage transients and surges must be provided by the fire alarm <br /> equipment supplier, and installed by the electrical contractor: <br /> On AC Input: A feed-through (not shunt-type) branch circuit transient suppressor such as the EFI <br /> E100HW120, Leviton 51020-OWM, Emerson/Northern Technologies TCS-HWR, Transtector <br /> ACPIOOBW series, or any equivalent UL 1449 - 2nd Edition Listed device submitted to and <br /> 16965 FIRE DETECTION & ALARM SYSTEM Page 3 OF 10 <br />