My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
2009-192
CBCC
>
Official Documents
>
2000's
>
2009
>
2009-192
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/10/2016 11:41:36 AM
Creation date
9/30/2015 11:37:50 PM
Metadata
Fields
Template:
Official Documents
Official Document Type
Contract
Approved Date
07/14/2009
Control Number
2009-192
Agenda Item Number
8.I.
Entity Name
DeAngelis Diamond Construction
Subject
Contract IRC Parks Maintenance Complex
Area
5500 77th St.
Project Number
0701
Bid Number
2009043
Supplemental fields
SmeadsoftID
6815
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
478
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
FORT PIERCE ENGINEERING, INC. IRC Maintenance <br /> approved by the electrical design engineer. Install suppressor in a listed enclosure near the <br /> electrical panelboard, and trim excess lead lengths. Wind small coil in the branch circuit <br /> conductorjust downstream of the suppressor connection. Coil to be 5 to 10 turns, about 1 " <br /> diameter, and securely tie-wrapped. This series impedance will improve the effectiveness of the <br /> suppressor in clipping fast rise time voltage transients. <br /> On DC Circuits Extending Outside Building: Adjacent to the FACU, and also near point of entry <br /> to outlying building, provide "pi"-type filter on each leg, consisting of a primary arrestor, series <br /> impedance, and a fast acting secondary arrestor that clamps at 30v-40v. Some acceptable <br /> models : Innovative Technology D2S33-2ML, Simplex 2081 -9027/-9028, Transtector TSP8601 , <br /> Ditek DTKxLVL series, Citel America B280-24V, Leviton 3824-OWM, Northern Technologies <br /> DLP-42. Submit data on others to the engineer for approval . UL 497B listing is normally a <br /> prerequisite for their consideration. Devices using only MOV active elements are not acceptable. <br /> 1 . 14 Systems are to be provided with a separate and independent source of secondary power. <br /> The system shall have a minimum of 24 hours secondary power capacity, plus 5 minutes of full <br /> alarm load. <br /> Include a copy of system battery sizing calculations with the shop drawing submittal to the <br /> engineer. Use manufacturer's battery discharge curve to determine expected battery <br /> voltage after 24 hours of providing standby power. Then use calculated Notification <br /> Appliance Circuit current draw in the alarm mode to determine expected voltage drop at <br /> EOL, based on conductor resistance per manufacturer's data sheet or NEC 2005, Table 8. <br /> Remember to double the ohms per foot since two conductors are required to power the <br /> circuit. Also, add any inherent voltage drop caused by the system ' s power supply. <br /> The voltage drop at EOL must not exceed 14 % of the expected battery voltage, after the <br /> required standby time plus alarm time. (Typically, for a 24 volt system, this limits the <br /> voltage drop from the battery to the EOL to 3 volts). Determine "worst case" voltage at far <br /> end of each NAC, by subtracting its calculated V-drop from the expected battery voltage. <br /> The result must be no less than the minimum listed operating voltage for the alarm <br /> notification appliances used. <br /> All of these calculations must be placed on a dedicated sheet of as-built drawings for future <br /> reference by fire alarm service technicians NAC voltage drop is to be verified during <br /> system tests. <br /> 1 . 15 Fire/smoke/CO detectors used shall be of the following types: 1 ) photoelectric smoke detectors <br /> for office building ceilings; 2) photoelectric duct smoke detectors for HVAC ducts; 3) 135°C <br /> heat detectors and CO warning system for maintenance building and storage bays. <br /> 1 . 16 Manual pull stations shall be provided at each point of egress in the office building and in <br /> accordance with the prescriptive requirements of NFPA 72 in the maintenance building and <br /> storage bay building. <br /> 2.0 Reserved. <br /> 3.0 Monitoring of Signals by Supervising Station : <br /> 16965 FIRE DETECTION & ALARM SYSTEM Page 4 OF 10 <br />
The URL can be used to link to this page
Your browser does not support the video tag.