Laserfiche WebLink
FORT PIERCE ENGINEERING, INC. IRC Maintenance <br /> approved by the electrical design engineer. Install suppressor in a listed enclosure near the <br /> electrical panelboard, and trim excess lead lengths. Wind small coil in the branch circuit <br /> conductorjust downstream of the suppressor connection. Coil to be 5 to 10 turns, about 1 " <br /> diameter, and securely tie-wrapped. This series impedance will improve the effectiveness of the <br /> suppressor in clipping fast rise time voltage transients. <br /> On DC Circuits Extending Outside Building: Adjacent to the FACU, and also near point of entry <br /> to outlying building, provide "pi"-type filter on each leg, consisting of a primary arrestor, series <br /> impedance, and a fast acting secondary arrestor that clamps at 30v-40v. Some acceptable <br /> models : Innovative Technology D2S33-2ML, Simplex 2081 -9027/-9028, Transtector TSP8601 , <br /> Ditek DTKxLVL series, Citel America B280-24V, Leviton 3824-OWM, Northern Technologies <br /> DLP-42. Submit data on others to the engineer for approval . UL 497B listing is normally a <br /> prerequisite for their consideration. Devices using only MOV active elements are not acceptable. <br /> 1 . 14 Systems are to be provided with a separate and independent source of secondary power. <br /> The system shall have a minimum of 24 hours secondary power capacity, plus 5 minutes of full <br /> alarm load. <br /> Include a copy of system battery sizing calculations with the shop drawing submittal to the <br /> engineer. Use manufacturer's battery discharge curve to determine expected battery <br /> voltage after 24 hours of providing standby power. Then use calculated Notification <br /> Appliance Circuit current draw in the alarm mode to determine expected voltage drop at <br /> EOL, based on conductor resistance per manufacturer's data sheet or NEC 2005, Table 8. <br /> Remember to double the ohms per foot since two conductors are required to power the <br /> circuit. Also, add any inherent voltage drop caused by the system ' s power supply. <br /> The voltage drop at EOL must not exceed 14 % of the expected battery voltage, after the <br /> required standby time plus alarm time. (Typically, for a 24 volt system, this limits the <br /> voltage drop from the battery to the EOL to 3 volts). Determine "worst case" voltage at far <br /> end of each NAC, by subtracting its calculated V-drop from the expected battery voltage. <br /> The result must be no less than the minimum listed operating voltage for the alarm <br /> notification appliances used. <br /> All of these calculations must be placed on a dedicated sheet of as-built drawings for future <br /> reference by fire alarm service technicians NAC voltage drop is to be verified during <br /> system tests. <br /> 1 . 15 Fire/smoke/CO detectors used shall be of the following types: 1 ) photoelectric smoke detectors <br /> for office building ceilings; 2) photoelectric duct smoke detectors for HVAC ducts; 3) 135°C <br /> heat detectors and CO warning system for maintenance building and storage bays. <br /> 1 . 16 Manual pull stations shall be provided at each point of egress in the office building and in <br /> accordance with the prescriptive requirements of NFPA 72 in the maintenance building and <br /> storage bay building. <br /> 2.0 Reserved. <br /> 3.0 Monitoring of Signals by Supervising Station : <br /> 16965 FIRE DETECTION & ALARM SYSTEM Page 4 OF 10 <br />