My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
2009-192
CBCC
>
Official Documents
>
2000's
>
2009
>
2009-192
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/10/2016 11:41:36 AM
Creation date
9/30/2015 11:37:50 PM
Metadata
Fields
Template:
Official Documents
Official Document Type
Contract
Approved Date
07/14/2009
Control Number
2009-192
Agenda Item Number
8.I.
Entity Name
DeAngelis Diamond Construction
Subject
Contract IRC Parks Maintenance Complex
Area
5500 77th St.
Project Number
0701
Bid Number
2009043
Supplemental fields
SmeadsoftID
6815
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
478
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
FORT PIERCE ENGINEERING, INC. IRC Maintenance <br /> (duct-seal), to prevent condensation from infiltrating humid air. <br /> 6 .5 There shall be no splices in the system other than at device terminal blocks, or on terminal blocks <br /> in cabinets. "Wire nuts" and crimp splices will not be permitted. Permanent wire markers shall <br /> be used to identify all connections at the FACU and other control equipment, at power supplies, <br /> and in terminal cabinets. <br /> 6.6 If building layout requires the terminal cabinet to be above a drop ceiling, its location must be <br /> clearly and permanently identified with a placard readable from floor. Terminal block screws <br /> shall have pressure wire connectors of the self-lifting or box lug type. <br /> 6. 7 Initiating device circuits shall be wired with type FPL/FPLR/FPLP fire alarm cable, AWG 18 <br /> minimum, low capacitance, twisted shielded copper pair. Cable shield drain wires are to be <br /> connected at each device to maintain continuity, taped to insulate from ground, and terminated at <br /> the FACU . Acceptable cables include Atlas 228- 18- 1 - 1STP, BSCC S1802s19 (same as EEC <br /> 78061,C), West Penn D975, D991 (AWG 16), D995 (AWG 14), or equal wire having capacitance <br /> of 30pf/ft. maximum between conductors. Belden 5320FJ acceptable if only FPL rating needed. <br /> The cable jacket color shall be red, with red (+) and black (-) conductor insulation. In <br /> underground conduit, use Type TC or PLTC cable (PE insulated) to avoid problems from <br /> moisture. Minimum conduit size of any type is 1/4 inch. <br /> 6.8 Reserved. <br /> 6. 9 Except as required by 2. 8 and 6.7, all other circuits in the system shall be wired with AWG 121 <br /> stranded copper, THHN/THWN conductors, installed in minimum 3/4 inch conduit. Color code <br /> as shown below throughout the system, without color change in any wire run: <br /> • Alarm notification Appliance Circuits (homs/strobes). . . . . .Blue (+)Black (-) <br /> • Separate 24vdc Operating Power (for equipment) . . . . . . . . . . . . Yellow (+)Brown (-) <br /> • Circuits from ZAM's to Monitored Devices (AWG 14/ 16). . .Violet(+)/Grey (-) <br /> 6. 10 Notification Appliance Circuit booster ("ADA") power supplies must be individually monitored <br /> by the FACU and protected by a smoke detector per NFPA 72 . They shall not be located above a <br /> ceiling, or in non-conditioned space. <br /> 6. 11 All junction boxes shall be painted red prior to pulling the wire. Those installed in finished areas <br /> are permitted to be painted outside to match the finish color. <br /> 6. 12 The branch circuit breaker supplying the system must be physically protected by panelboard lock <br /> or handle lock and each must be identified with a 1 /4" permanent red dot applied to handle or <br /> exposed body area. The breaker supplying the system shall also be clearly and conspicuously <br /> identified on the electric branch-circuit panel schedule and electrical as-built drawings . <br /> 6. 13 Provide an engraved label at each fire alarm system control unit, system sub-panel or data <br /> gathering panel, supplementary notification appliance (SNAC) panel, digital alarm <br /> communicator, etc., identifying its 120vac power source, as follows: Panelboard location, <br /> panelboard identification, and branch circuit number. <br /> 6 . 14 The fire alarm system shall monitor 120vac power to shunt trip breakers used in conjunction with <br /> 16965 FIRE DETECTION & ALARM SYSTEM Page 7 OF 10 <br />
The URL can be used to link to this page
Your browser does not support the video tag.