Laserfiche WebLink
FORT PIERCE ENGINEERING, INC. IRC Maintenance <br /> (duct-seal), to prevent condensation from infiltrating humid air. <br /> 6 .5 There shall be no splices in the system other than at device terminal blocks, or on terminal blocks <br /> in cabinets. "Wire nuts" and crimp splices will not be permitted. Permanent wire markers shall <br /> be used to identify all connections at the FACU and other control equipment, at power supplies, <br /> and in terminal cabinets. <br /> 6.6 If building layout requires the terminal cabinet to be above a drop ceiling, its location must be <br /> clearly and permanently identified with a placard readable from floor. Terminal block screws <br /> shall have pressure wire connectors of the self-lifting or box lug type. <br /> 6. 7 Initiating device circuits shall be wired with type FPL/FPLR/FPLP fire alarm cable, AWG 18 <br /> minimum, low capacitance, twisted shielded copper pair. Cable shield drain wires are to be <br /> connected at each device to maintain continuity, taped to insulate from ground, and terminated at <br /> the FACU . Acceptable cables include Atlas 228- 18- 1 - 1STP, BSCC S1802s19 (same as EEC <br /> 78061,C), West Penn D975, D991 (AWG 16), D995 (AWG 14), or equal wire having capacitance <br /> of 30pf/ft. maximum between conductors. Belden 5320FJ acceptable if only FPL rating needed. <br /> The cable jacket color shall be red, with red (+) and black (-) conductor insulation. In <br /> underground conduit, use Type TC or PLTC cable (PE insulated) to avoid problems from <br /> moisture. Minimum conduit size of any type is 1/4 inch. <br /> 6.8 Reserved. <br /> 6. 9 Except as required by 2. 8 and 6.7, all other circuits in the system shall be wired with AWG 121 <br /> stranded copper, THHN/THWN conductors, installed in minimum 3/4 inch conduit. Color code <br /> as shown below throughout the system, without color change in any wire run: <br /> • Alarm notification Appliance Circuits (homs/strobes). . . . . .Blue (+)Black (-) <br /> • Separate 24vdc Operating Power (for equipment) . . . . . . . . . . . . Yellow (+)Brown (-) <br /> • Circuits from ZAM's to Monitored Devices (AWG 14/ 16). . .Violet(+)/Grey (-) <br /> 6. 10 Notification Appliance Circuit booster ("ADA") power supplies must be individually monitored <br /> by the FACU and protected by a smoke detector per NFPA 72 . They shall not be located above a <br /> ceiling, or in non-conditioned space. <br /> 6. 11 All junction boxes shall be painted red prior to pulling the wire. Those installed in finished areas <br /> are permitted to be painted outside to match the finish color. <br /> 6. 12 The branch circuit breaker supplying the system must be physically protected by panelboard lock <br /> or handle lock and each must be identified with a 1 /4" permanent red dot applied to handle or <br /> exposed body area. The breaker supplying the system shall also be clearly and conspicuously <br /> identified on the electric branch-circuit panel schedule and electrical as-built drawings . <br /> 6. 13 Provide an engraved label at each fire alarm system control unit, system sub-panel or data <br /> gathering panel, supplementary notification appliance (SNAC) panel, digital alarm <br /> communicator, etc., identifying its 120vac power source, as follows: Panelboard location, <br /> panelboard identification, and branch circuit number. <br /> 6 . 14 The fire alarm system shall monitor 120vac power to shunt trip breakers used in conjunction with <br /> 16965 FIRE DETECTION & ALARM SYSTEM Page 7 OF 10 <br />