Loading...
HomeMy WebLinkAbout2014-200CINDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.1 EXAMINATION A. Do not proceed with installation until all wet work such as concrete, terrazzo, plastering and painting has been completed and thoroughly dried out. 3.2 PREPARATION A. Measure each ceiling area and establish layout of acoustical units to balance border widths at opposite edges of each ceiling. Avoid use of less than half width units at borders, and comply with reflected ceiling plans. Coordinate panel layout with mechanical and electrical fixtures. 3.3 INSTALLATION A. Install suspension system and panels in compliance with ASTM C636, with the authorities hav- ing jurisdiction, and in accordance with the manufacturer's installation instructions: 1. MetalWorks Tegular Installation Instructions, LA 295519 2. MetalWorks Cutting Instructions, LA 295518 B. Suspend main beam from overhead construction with hanger wires spaced 4 feet on center along the length of the main runner. Install hanger wires plumb and straight. Hanger wires shall not be installed in convenience holes. C. Install wall moldings at intersection of suspended ceiling and vertical surfaces. Miter corners where wall moldings intersect or install corner caps. D. Follow the instructions found in "MetalWorks Tegular Installation Instructions", LA -295519 for border treatment of the MetalWorks Tegular panels. The face of the suspension system rests directly on the molding or trim flange. 3.4 ADJUSTING AND CLEANING A. Replace damaged and broken panels. B. Clean exposed surfaces of ceilings panels, including trim, edge moldings, and suspension members. Comply with manufacturer's instructions for cleaning and touch up of minor finish damage. Remove and replace work that cannot be successfully cleaned and repaired to perma- nently eliminate evidence of damage END OF SECTION 09545 ACOUSTICAL METAL PAN CEILINGS 09545-6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 096223 - BAMBOO FLOORING PART 1 — GENERAL 1.01 SUMMARY A. Standard no -added formaldehyde bamboo strip flooring installed by the nail or staple method. B. Related Sections 1. Section 06 16 23 — Subflooring 2. Section 06 16 29 — Acoustical Underlayment 3. Section 06 46 19 — Wood Base and Shoe Moldings 1.02 REFERENCED STANDARDS A. ASTM — American Society for Testing and Materials 1. ASTM E648: Standard Test Method for Critical Radiant Flux of Floor -Covering Systems Using a Radiant Heat Energy Source 2. ASTM D1037: Standard Test Methods for Evaluating Properties of Wood -Base Fiber and Particle Panel Materials 3. ASTM D3501: Standard Test Methods for Wood -Based Structural Panels in Compression 4. ASTM D3359: Standard Test Method for Measuring Adhesion by Tape Test 5. ASTM D4060: Standard Test Method for Abrasion Resistance of Organic Coatings by the Taber Abraser 6. ASTM D4442: Standard Test Methods for Direct Moisture Content Measurement of Wood and Wood -Base Materials B. NWFA — National Wood Flooring Association: Technical Reference Manual 1.03 SYSTEM PERFORMANCE A. Compatibility with Radiant Floor Heating Systems: Compatible. 1.04 SUBMITTALS A. Reference Section 01 33 00; Submit the following items: 1. Product Data BAMBOO FLOORING 096223-1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Each product specified 2. Quality Assurance/Control Submittals: a. NWFA Technical Reference Manual. b. Proof of bamboo flooring manufacturer's qualifications. c. Test Reports: Reports for specified Physical Property Performance Requirements. 3. Shop Drawings: Show installation details including location, layout, fastening method, and transition of each type of flooring and accessory. 4. Samples: a. 6 inch (150 mm) long strip of flooring material b. Fasteners c. One of each specified accessory, minimum 4 inches (100 mm) 1.05 QUALITY ASSURANCE A. Qualifications 1. Manufacturer: a. Minimum 10 years experience in manufacturing and distributing bamboo flooring products. b. Member: National Wood Flooring Association, American Bamboo Society, U.S. Green Building Council. 2. Installer: Minimum 5 years experience in hardwood flooring installation. B. Reference Section 01 31 19.33; Pre -Installation Meeting: 1. Convene meeting at project site within one week of scheduled start of installation with representatives of the following in attendance: Owner, Architect, General Contractor, Sub -Contractor. 2. Review substrate conditions, requirements of related work, requirements for operation of HVAC system, installation instructions, storage and handling procedures, and protection measures. 3. Keep minutes of meeting including responsibilities of various parties and deviations from specifications and installation instructions. 4. Distribute minutes to attendees within 48 hours. 1.06 DELIVERY, STORAGE, AND HANDLING A. Deliver flooring materials in original unopened cartons. B. Reference Section 01 66 00: Product Handling and Storage Requirements. BAMBOO FLOORING 096723-2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Deliver flooring after completion of all wet work and after all moisture has dissipated from this work. Wet work includes, but is not limited to, concrete, plaster, tile, drywall, grouting, and painting. 2. Store flooring in a warm, dry, well -ventilated, and weather -tight location. 3. Open the boxes, acclimate, and confirm moisture content compatibility. Flooring should acclimate for a minimum of 72 hours. 4. Do not store directly on concrete or near outside walls. 1.07 PROJECT CONDITIONS A. The temperature and relative humidity (RH) of the installation area should be stabilized with nounal year-round conditions a minimum of one week before installation. For optimum performance manufacturer's recommended temperature range of 50-80°F and an RH of 30-50% should be maintained year-round. 1.08 SCHEDULING These items must be completed before delivery and installation of flooring. A. Building must be water -tight with all windows and doors installed. B. Completion of all wet work and after all moisture has dissipated from this work. Wet work includes but is not limited to: concrete, plaster, tile, drywall, grouting, and painting. C. Environmental and humidity control system is operating for 14 days in installation and storage areas at the temperature and humidity of the occupied building. 1.09 WARRANTY A. Warranty for Smith & Fong Flooring referenced at www.plyboo.com 1.10 MAINTENANCE AND PROTECTION A. Maintain and protect installed work at all times per the manufacturer's instructions. B. Do not protect the flooring with plastic sheeting or moisture retardant membranes. C. Use hard surface protection such as hardboard over kraft paper. Tape kraft paper and hardboard to prevent grit infiltration. PART 2— PRODUCTS 2.01 MANUFACTURER A. Smith & Fong Company, San Francisco, CA 94103 BAMBOO FLOORING 096213-3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Tel: (866) 835-9859 2. E-mail: sales@plyboo.com 3. Website: www.plvboo.com 2.02 MATERIALS A. Bamboo Strip Flooring 1. Species: Moso (Phyllostachys Pubescens) 2. Manufactured without added urea -formaldehyde 3. FSC certified 4. FloorScore certified 5. Edge Configuration: Tongue and groove, 4 sides 6. Type: No alternates accepted. a. Prefinished: 3-5/8 inches wide by 5/8 inches thick by 72 inches in length. 7. Physical/Mechanical Properties a. ASTM E648: Critical Radiant Flux (1) Flat Grain prefinished: Class 1 (2) Edge Grain prefmished: Class 1 b. ASTMD1037: (1) Dimensional Stability, 50% to 20% RH Linear Expansion: Edge Grain: Parallel —0.02%, Perpendicular -0.07% Thickness Swell: Edge Grain: -0.34% (2) Hardness (Janka Ba11 Test) Edge Grain Amber: 1,300 lbf (avg) d. ASTM D3501: Compressive Strength (1) Compressive Strength / Max Load Edge Grain: 6,160 lbs / 12,201 lbf (avg) e. ASTM D3359: Adhesion by Tape Test (1) Edge Grain: Class 4B f. ASTM D4060: Taber Abrasion (1) Avg. Wear -through / Wear Rate Edge Grain Amber: 20,000 cycles / 6,897 cycles per 0.001 inch g. ASTM D4442: Moisture Content (1) Flat and Edge Grain: 6%— 9% (average range) h. ASTM D5116-06: Organic Emissions [CA Section 01350; Indoor Air Quality] (1) Office scenario / Classroom scenario: Flat and Edge Grain: Pass / Pass B. Fasteners: 1. Comply with both the Manufacturer Installation Instructions and the NWFA's Technical Reference Manual. 2.03 ACCESSORIES Flat and edge grain accessories referenced at http://plyboo.com/images/plyboo/downloads/sf_plybooaccessories.pdf. A. Base Shoe: Prefinished, 1" thick by 3/4" wide by 72" long BAMBOO FLOORING 096223-4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Amber Edge. B. Baseboard: Prefinished, 5/8" thick by 3" wide by 72" long 1. Amber Edge. C. Reducer: Prefinished, 5/8" thick by 2" wide by 72" long 1. Amber Edge. D. Standard Threshold: Prefinished, 9/16" thick by 3-5/8" wide by 72" long 1. Amber Edge. PART 3 — EXECUTION 3.01 EXAMINATION A. Examine substrates for compliance with requirements for installation tolerances, and other conditions affecting performance of flooring. B. Verify substrate is dry, clean and free of loose material, grease, and other contaminates. D. Do not install bamboo flooring if wood substrate exceeds 12% moisture. E. Do no install bamboo flooring if moisture variation between substrate and bamboo exceeds 3%. F. Verify HVAC System is operating and maintaining temperature and humidity conditions in compliance with Manufacturer's Installation Instructions. G. Coordinate with responsible entity to correct unsatisfactory conditions. H. Commencement of work by installer is acceptance of substrate conditions. 3.02 PREPARATION A. Humidity: maintain indoor air humidity levels between 30% and 50% for two weeks before installation and continually thereafter. B. Temperature: maintain temperature of materials and installation area between 62 degrees and 68 degrees during installation. C. Acclimatization: Open flooring boxes and remove packing minimum 3 days prior to start of installation. D. Grind and fill subfloor using methods and materials appropriate to the subfloor construction to eliminate high spots and depressions exceeding 3/16 inch (5 mm) inch in 10 feet (3048 mm). BAMBOO FLOORING 0962123-5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.03 INSTALLATION OF SMITH & FONG PLYBOO FLOORING A. Flooring: Comply with manufacturer's installation instructions. Available for download at: http://plyboo.com/images/plyboo/downloads/plyboo_flooring install_instructionsmdf 3.04 CLEANING: Reference Section 01 74 00: Cleaning and Waste Management A. Repair or replace damaged installed products. B. Clean installed products in accordance with manufacturer's instructions prior to Owner's acceptance. 3.05 PROTECTION B. Protect installed product from damage during construction by covering with heavy kraft -paper or other suitable covering. Maintain covering throughout remainder of construction period. END OF SECTION 096223 BAMBOO FLOORING 096Y23-6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 096466 - WOOD ATHLETIC FLOORING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes wood athletic flooring. B. Related Sections: 1. Section 096400 "Wood Flooring" for traditional solid -wood and engineered -wood, strip, plank, and parquet flooring. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for wood athletic flooring. B. Shop Drawings: For each type of floor assembly and accessory. Include plans, elevations, sections, details, and attachments to other work. Include the following: 1. Expansion provisions and trim details. 2. Layout, colors, widths, and dimensions of game lines and markers. 3. Locations of floor inserts for athletic equipment installed through flooring assembly. C. Samples for Initial Selection: Manufacturer's color charts showing colors and glosses available for the following: 1. Floor finish. 2. Game -line and marker paint. D. Samples for Verification: For each type of wood athletic flooring and accessory required; approximately [12 inches (300 mrn) long] and of same thickness and material indicated for the Work. 1. Include sample sets showing the full range of normal color and texture variations expected in wood flooring. 2. Include Sample sets showing finishes and game -line and marker paint colors applied to wood flooring. WOOD ATHLETIC FLOORING 096466 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.4 INFORMATIONAL SUBMITTALS A. Qualification Data: For qualified manufacturer. B. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for wood athletic flooring system. 1.5 CLOSEOUT SUBMITTALS A. Maintenance Data: For wood athletic flooring and finish systems to include in maintenance manuals. 1.6 QUALITY ASSURANCE A. Manufacturer Qualifications: A qualified manufacturer that is certified for chain -of -custody certification by an FSC -accredited certification body. B. Installer Qualifications: A firm or individual that has been approved by MFMA as an accredited Installer according to the MFMA Accreditation Program. C. Installer Qualifications: An experienced Installer who has completed wood athletic flooring installations similar in material, design, and extent to that indicated for this Project and whose work has resulted in installations with a record of successful in-service performance. 1. Installer responsibilities include installation and field finishing of wood athletic flooring components and accessories, and application of game lines and markers. D. Maple Flooring: Comply with MFMA grading rules for species, grade, and cut. 1. Certification: Provide flooring that carries MFMA mark on each bundle or piece. E. Mockups: Build mockups to verify selections made under Sample submittals and to demonstrate aesthetic effects and set quality standards for fabrication and installation. 1. To set quality standards for installation, install mockup of floor area as shown on Drawings. 2. Prepare finished mockup of floor area as shown on Drawings to set quality standards for sanding and application of field finishes and game lines and markers. 3. Approval of mockups does not constitute approval of deviations from the Contract Documents contained in mockups unless Architect specifically approves such deviations in writing. 4. Approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion. 1.7 DELIVERY, STORAGE, AND HANDLING A. Deliver assembly materials in unopened cartons or bundles. WOOD ATHLETIC FLOORING 096466 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Protect wood from exposure to moisture. Do not deliver wood components until after concrete, masonry, plaster, ceramic tile, and similar wet work is complete and dry. C. Store wood components in a dry, warm, well -ventilated, weathertight location and in a horizontal position. 1.8 FIELD CONDITIONS A. Conditioning period begins not less than seven days before wood athletic flooring installation, is continuous through installation, and continues not less than seven days after installation. 1. Environmental Conditioning: Maintain an ambient temperature between 65 and 75 deg F (18 and 24 deg C) and relative humidity planned for building occupants, but not less than 35 percent or more than 50 percent, in spaces to receive wood athletic flooring during the conditioning period. 2. Wood Conditioning: Move wood components into spaces where they will be installed, no later than beginning of the conditioning period. a. Do not install wood athletic flooring until wood components adjust to relative humidity of, and are at same temperature as, spaces where they are to be installed. b. Open sealed packages to allow wood components to acclimatize immediately on moving wood components into spaces in which they will be installed. B. After conditioning period, maintain relative humidity and ambient temperature planned for building occupants. C. Install wood athletic flooring after other finishing operations, including painting, have been completed. 1.9 COORDINATION A. Coordinate layout and installation of wood athletic flooring systems with floor inserts for gymnasium equipment. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. 2. 3. 4. 5. Mondo. 6. Robbins S Sport Court International. WOOD ATHLETIC FLOORING 096466 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 7. WD Floorin.-, LLC. 2.2 DESCRIPTION A. System Type: Floating. B. Overall System Height: 2-1/8 inches (54 mm. 2.3 PERFORMANCE REQUIREMENTS A. Provide wood athletic flooring systems tested by a qualified testing agency according to DIN V 18032-2 and shown to meet the following requirements: 1. Shock Absorption: Minimum 53 percent. 2. Vertical Deflection: Minimum 0.09 inch (2.3 innr) 3. Area of Deflection: Maximum 15 percent. 4. Ball Bounce: Minimum 90 percent. 5. Surface Friction: Not less than 0.5 or more than 0.7. 6. Rolling Loads: No damage when subjected to 337 lbf 0..500 N) applied through a single wheel. B. FloorScore Compliance: Wood athletic flooring shall comply with requirements of FloorScore Standard. C. Low -Emitting Materials: Wood athletic flooring systems shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small -Scale Environmental Chambers." 2.4 FLOORING MATERIALS A. Certified Wood: Provide wood flooring produced from wood obtained from forests certified by an FSC -accredited certification body to comply with FSC STD -01-001, "FSC Principles and Criteria for Forest Stewardship." B. Random -Length Strip Flooring: Northern hard maple (Acer saccharum), kiln dried, random length, tongue and groove, and end matched. 1. Grade: MFMA-RL Second and Better. 2.5 SUBFLOOR MATERIALS A. Wood Sleepers: Standard grade; 48 inches (1200 trim) long; kiln -dried Eastern hemlock, fir, pine, or spruce. 1. Size: Nominal] [2 by 4 inches (50 by 100 mm)]. WOOD ATHLETIC FLOORING 096466 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Sleeper Anchors: Manufacturer's standard drive pins recommended by anchor manufacturer to achieve minimum 900-lbf (4000-N) pullout strength in 3000 -psi (20.7- MPa) concrete. 3. Sleeper Shims: In size and type recommended in writing by flooring manufacturer for application indicated. 4. Asphalt Primer: ASTM D 41. 5. Asphalt Mastic: ASTM D 312, Type I, cold -applied dead -level asphalt or Type III, hot - applied steep asphalt, as recommended in writing by manufacturer. 2.6 FINISHES A. Floor -Finish System: System of compatible components recommended in writing by flooring manufacturer, and MFMA approved. 1. Floor -Sealer Formulation: Pliable, penetrating type. MFMA Group 1, Sealers. 2. Finish -Coat Formulation: Formulated for gloss finish indicated and multicoat application. 3. Game -Line and Marker Paint: Industrial enamel compatible with fmish coats and recommended in writing by manufacturers of finish coats, and paint for this use. 2.7 ACCESSORIES A. Resilient Wall Base: Molded, vented, rubber or vinyl cove base; 4 by 3 by 48 inches (l UO by 75 by 1200 mm); with premolded outside corners. 1. Color: Black. B. Fasteners: Type and size recommended by manufacturer, but not less than those recommended by MFMA for application indicated. C. Trowelable Leveling and Patching Compound: Latex -modified, hydraulic -cement -based formulation approved by wood athletic flooring manufacturer. PART 3 - EXECUTION 3.1 PREPARATION A. Grind high spots and fill low spots on concrete substrates to produce a maximum 1/8 -inch (3 - mm) deviation in any direction when checked with a 10 -foot (3-m) straight edge. 1. Use trowelable leveling and patching compounds, according to manufacturer's written instructions, to fill cracks, holes, and depressions in substrates. B. Remove coatings including curing compounds and other substances on substrates that are incompatible with installation adhesives and that contain soap, wax, oil, or silicone; use mechanical methods recommended by manufacturer. Do not use solvents. WOOD ATHLETIC FLOORING 096466 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Broom and vacuum clean substrates to be covered immediately before product installation. After cleaning, examine substrates for moisture, alkaline salts, carbonation, or dust. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. General: Comply with wood athletic flooring manufacturer's written instructions, but not less than written recommendations of MFMA applicable to flooring type indicated. B. Pattern: Lay flooring parallel with long dimension of space to be floored unless otherwise indicated. C. Expansion Spaces: Provide as indicated, but not less than that required by manufacturer's written instructions and MFMA's written recommendations at walls and other obstructions, and at interruptions and terminations of flooring. 1. Cover expansion spaces with base molding, trim, and saddles, as indicated on Drawings. D. Vapor Retarder: Cover entire slab area beneath wood flooring. Install with joints lapped a minimum of 6 inches (150 nun) and sealed. E. Underlayment: Install perpendicular to direction of flooring, staggering end joints in adjacent rows. F. Sleepers: 1. Prime entire slab beneath wood floor area with asphalt primer at coverage rate recommended by manufacturer. 2. Install sleepers perpendicular to direction of flooring, staggering end joints a minimum of [24 inches (610 mm)] <Insert dimension>. 3. Space at spacing recommended by manufacturer for system components indicated 4. Shim and level sleepers and install anchors at spacing recommended by manufacturer, but not less than 30 inches (760 mm) o.c. 5. Anchor predrilled sleepers through resilient pads. G. Installation Tolerances: 1/8 inch in 10 feet (3 mm in 3 in) of variance from level. 3.3 SANDING AND FINISHING A. Allow installed flooring to acclimate to ambient conditions before sanding B. Follow applicable recommendations in MFMA's "Industry Recommendations for Sanding, Sealing, Court Lining, Finishing, and Resurfacing of Maple Gym Floors." C. Machine sand with coarse, medium, and fine grades of sandpaper to achieve a level, smooth, uniform surface without ridges or cups. Remove sanding dust by tack or vacuum. D. Finish: Apply seal and fmish coats of finish system according to finish manufacturer's written instructions. Provide no fewer than four coats total and no fewer than two finish coats. WOOD ATHLETIC FLOORING 096466 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Water -Based Finishes: Use finishing methods recommended by finish manufacturer to reduce grain raise and sidebonding effect. 2. Game -Line and Marker Paint: Apply game -line and marker paint between final seal coat and first finish coat according to paint manufacturer's written instructions. a. Mask flooring at game lines and markers, and apply paint to produce lines and markers with sharp edges. b. Where game lines cross, break minor game line at intersection; do not overlap lines. c. Apply fmish coats after game -line and marker paint is fully cured. 3.4 PROTECTION A. Protect wood athletic flooring during remainder of construction period to allow finish to cure and to ensure that flooring and finish are without damage or deterioration at time of Substantial Completion. 1. Do not cover flooring after finishing until finish reaches full cure and not before seven days after applying last finish coat. 2. Do not move heavy and sharp objects directly over flooring. Protect fully cured floor finishes and surfaces with plywood or hardboard panels to prevent damage from storing or moving objects over flooring. END OF SECTION 096466 WOOD ATHLETIC FLOORING 096466 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 09 65 00 - RESILIENT WALL BASE PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Resilient Wall Base 1.02 REFERENCED DOCUMENTS A. ASTM International: 1. F 1861 Standard Specification for Resilient Wall base 2. E 84 Standard Test Method for Surface Burning Characteristics of Building Materials 3. F 386 Standard Test Method for Thickness of Resilient Flooring Materials Having Flat Surfaces 4. E 648 Standard Test Method for Critical Radiant Flux of Flooring systems Using a Radi- ant EnergySource. 5. E 662 Test Method for Specific Density of Smoke Generated by Solid Materials. 6. F 925 Standard Test Method for Resistance to Chemicals of Resilient Flooring. 7. F 137 Standard Test Method for Flexibility of Resilient Flooring Materials with Cylin- drical Mandrel Apparatus 8. F 1515 Standard Test Method for Measuring Light Stability of Resilient Vinyl Flooring by Color Change B. Other Referenced Documents 1. National Fire Protection Association (NFPA): NFPA 255, Test Method for Crit cal Radi- ant Flux of Floor Covering Systems Using a Radiant Energy Source 2. National Fire Protection Association (NEPA) 258 Test Method for Specific Density of Smoke Generated by Solid Materials. 3. California Safe Drinking Water and Toxic Enforcement Act of 1986 (Proposition 65). 4. The Collaborative for High Performance Schools (CHPS) 1.03 SUBMITTALS A. Product Data: Submit product data, including manufacturer's specification summary sheet for specified products B. Shop Drawings: Submit shop drawings showing layout, fmish colors, patterns and textures. C. Samples: Submit selection and verification samples for finishes, colors, and textures. RESILIENT WALL BASE 096500-1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Quality Assurance Submittals: Submit the following: I. Test Reports: Certified test reports showing compliance with specified performance char- acteristics and physical properties. 2. Manufacturer's Instructions: Manufacturer's installation and maintenance instructions. E. Submit the following: 1. Maintenance Data: Maintenance data for installed products in accordance with Division 1 sections. Include methods for maintaining installed products, and precautions against cleaning materials and methods detrimental to finishes and performance. 2. Warranty: Warranty documents specified herein. 1.04 QUALITY ASSURANCE A. Installer Qualifications: Installer experienced in performing work of this section who has spe- cialized in installing work similar to that required for this project. B. Regulatory Requirements 1. Fire Performance characteristics: Provide resilient sheet vinyl floor covering with the fol- lowing fire performance characteristics as determined by testing products in accordance with ASTM method (and) NFPA method) indicated below by a certified testing laborato- ry or another testing and inspecting agency acceptable to authorities having jurisdiction. a. ASTM E 648 (NFPA 253), Critical Radiant Flux of Floor Covering Systems: Class 1, > 1.0 W/cm2 b. ASTM E 662 (NEPA 258), Specific Optical Density of Smoke Generated by Solid Materials: Passes, <450 c. ASTM E 84 (NFPA 255), Surface Building Characteristics of Building Materials: Class C C. Single -Source Responsibility: Obtain resilient wall base and manufacturer's recommended ad- hesive from a single supplier. D. Pre -Installation Meetings: Conduct pre -installation meeting to verify project requirements, sub- strate Conditions & manufacturer's recommended substrates and required preparation manufacturer' installation instructions and manufacturer's warranty requirements. Comply with requirements in Division 1. 1.05 DELIVERY, STORAGE, AND HANDLING A. General: Comply with requirements in Division 1. B. Ordering: Comply with manufacturer's ordering instructions and lead-time requirements to avoid construction delays. C. Delivery: Deliver materials in manufacturer's original, unopened, undamaged containers with identification labels intact. RESILIENT WALL BASE 096500-2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Storage and Protection: Store materials protected from exposure to harmful weather conditions and acclimated to site conditions at temperature and humidity conditions recommended by manufacturer. 1.06 PROJECT CONDITIONS A. Environmental Requirements/Conditions: hi accordance with manufacturer's recommendations, areas to receive resilient wall base shall be clean, fully enclosed, weather tight with the perma- nent HVAC set at a uniform temperature of 65-85 degrees F for 48 hours prior to during, and thereafter installation of resilient wall base. Resilient wall base and adhesive shall be condi- tioned in the same manner. Resilient wall base must be unboxed acclimated in area of use at least 48 hours prior to installation. Minimum temperature shall be a 65 degrees F after installa- tion. B. Existing Conditions: Ensure all existing walls are suitable for resilient base installation. Bring all unacceptable areas to owner's attention prior to commencement of work. 1.07 SEQUENCING AND SCHEDULING A. Finishing Operations: Install resilient wall base after finishing operations, including floor cov- ering painting and ceiling operations etc., have been completed. 1.08 WARRANTY A. Manufacturer's Materials Warranty: Submit, for Owner's acceptance, manufacturer's standard warranty document. Manufacturer's warranty is in addition to, and not a limitation of, other rights Owner may have under Contract Documents. 1. Warranty Period: 1 year limited warranty commencing on Date of Substantial Comple- tion. Notice of any defect must be made in writing to manufacturer within thirty (30) days after buyer learns of the defect. 2. Limited Wear Warranty: 3 year limited wear warranty. 1.09 MAINTENANCE A. Extra Materials: Deliver to Owner extra materials from same production run as products in- stalled. Package products with protective covering and identify with descriptive labels. Comply with Division One Closeout Submittals (Maintenance Materials) Section. 1. Quantity: Furnish quantity of Resilient Wall Base equal to 5% of amount installed. 2. Delivery, Storage and Protection: Comply with Owner's requirements for delivery, stor- age and protection of extra materials. B. Maintenance of finished floor covering to be conducted per Manufacturer's Maintenance Guide. RESILIENT WALL BASE 096500-3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 2 PRODUCTS 2.01 RESILIENT WALL BASE A. Manufacturer: Roppe Corporation 1. Contact: P.O. Box 1158 Fostoria, Ohio USA 44830-1158. Phone: (419) 435-8546 Fax: (419) 435-1056 B. Test results: 1. Thickness tolerance: Complies with ASTM F-386 2. Flexibility: Complies with ASTM F-137 3. Resistance to Heat Aging: Complies with ASTM F-1515 4. Resistance to Detergents: Complies with ASTM F-925 5. Resistance to Alkalis: No fading or softening 6. Dimensional Stability: Complies with ASTM F 1861 7. Squareness: 90 degrees +/- 0.5 degrees 8. Does do not contain any of the hazardous chemicals listed in California Proposition 65 9. Collaborative for High Performance Schools (CHPS) 01350 Low -Emitting Material Cri- teria: Pass C. Proprietary Product: 1. Roppe Pinnacle Rubber Base a. Complies with ASTM F-1861 Type TS (Thermoset Vulcanized Rubber), Group 1 (Solid) b. Contains 10% natural rubber c. Thickness: 1/8" ( 3.175 mm) nominal d. Color: As specified on Finish Material List e. Profile: Standard Toe (Cove Base) 1) Nominal Height: 4" 2) Lengths: 120' coils 3) Corners: Factory pre -formed outside corners (6") 2.02 PRODUCT SUBSTITUTIONS A. Substitutions: No substitutions permitted. PART 3 EXECUTION 3.01 MANUFACTURER'S INSTRUCTIONS A. Compliance: Comply with manufacturer's instructions for installation. RESILIENT WALL BASE 096500-4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Adhesive: (select one) Roppe 205 Wall Base Adhesive or 210 White Acrylic Wall Base Adhe- sive C. Caulking: Roppe Colored Caulk 3.02 EXAMINATION Site Verification of Conditions: Verify substrate conditions are acceptable for installing product in accordance with manufacturer's instructions. B. Material Inspection: In accordance with manufacturer's installing requirements, visually inspect materials prior to installing. Material with visual defects shall not be installed. 3.03 PREPARATION A. Adjacent Surfaces Protection: Protect adjacent work areas and finish surfaces from damage during product installation. B. Surface Preparation, General: Prepare substrate in accordance with manufacturer's instructions. C. Substrate: Prepare manufacturer's recommended substrates to be smooth, rigid, flat, lev el, permanently dry, clean and free of foreign materials such as paint, dust, grease, oils, solvent, old adhesive residue, vinyl wall coverings, non -porous surfaces and all other contaminants that may interfere with adhesive bond. 3.04 INSTALLING A. Manufacturer's instructions for specifications on installing resilient wall base. B. Resilient wall base colors, heights and profiles: As selected by Architect. C. Roppe Adhesive D. Roppe Colored Caulk 3.05 FIELD QUALITY REQUIREMENT A. Manufacturer's Field Services: Upon Owner's request and with minimum 72 hours notice, pro- vide manufacturer's field service consisting of product use recommendations and periodic site visits to confirm installing of product is in accordance with manufacturer's instructions. 1. Site Visits On site visit shall occur on the first day of resilient wall base installation. RESILIENT WALL BASE 096500-5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.06 CLEANING A. Cleaning: Repair or replace damaged installed products. Clean installed products in accordance with manufacturer's instructions prior to owner's acceptance. Remove construction debris from project site and legally dispose of debris. END OF SECTION 096500 RESILIENT WALL BASE 096500-6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 096519 - RESILIENT TILE FLOORING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Resilient vinyl tile flooring. B. Related Sections: Sections related to this section include: 1. Procurementf and Contracting Requirements: Division 00 General Conditions. 2. General Requirements: Division 01 Specification Sections. 3. Concrete: Division 03 Concrete Sections. 1.02 REFERENCES A. American Concrete Institute (ACI): 1. ACI 302.1 Guide for Concrete Floor and Slab Construction. 2. ACI SP -15 Field Reference Manual - Standard Specifications for Structural Concrete. ASTM International: 1. ASTM D2047 Standard Test Method for Static Coefficient of Friction of Polish -Coated Floor Surfaces as Measured by the James Machine. 2. ASTM E648 Standard Test Method for Critical Radiant Flux of Floor -Covering Systems Using a Radiant Heat Energy Source. 3. ASTM E662 Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials. 4. ASTM E1643 Standard Practice for Installation of Water Vapor Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs. 5. ASTM E1745 Standard Specification for Water Vapor Retarders Used in Contact with Soil or Granular Fill Under Concrete Slabs. 6. ASTM F137 Standard Test Method for Flexibility of Resilient Flooring Materials with Cylindrical Mandrel Apparatus. 7. ASTM F386 Standard Test Method for Thickness of Resilient Flooring Materials Having Flat Surfaces. 8. ASTM F536 Test Method for Size of Resilient Floor Coverings. (This test method was withdrawn by ASTM in 2004). 9. ASTM F540 Test Method for Squareness of Resilient Floor Tile by Dial Gage Method. (This test method was withdrawn by ASTM in 2004). 10. ASTM F710 Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring. 11. ASTM F925 Standard Test Method for Resistance to Chemicals of Resilient Flooring. RESILIENT TILE FLOORING 096519-1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 12. ASTM F970 Standard Test Method for Static Load Limit. 13. ASTM F1482 Standard Guide to Wood Underlayment Products Available for Use Under Resilient Flooring. 14. ASTM F1514 Standard Test Method for Measuring Heat Stability of Resilient Vinyl Flooring by Color Change. 15. ASTM F1515 Standard Test Method for Measuring Light Stability of Resilient Vinyl Flooring by Color Change. 16. ASTM F 1700 Standard Specification for Solid Vinyl Floor Tile. 17. ASTM F1869 Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride. 18. ASTM F1914 Standard Test Method for Short -Term Indentation and Residual Indentation of Resilient Floor Covering. 19. ASTM F2170 Standard Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes. C. Americans with Disabilities Act (ADA) of 1990. D. Federal Specifications (FS): 1. Federal Standard Number 501a (Notice 1) Federal Test Method Standard for Floor Covering, Resilient, Non -Textile, Sampling and Testing Method 6211 Dimensional Stability. E. International Organization for Standardization (ISO): 1. ISO 9001 Quality Systems - Model Quality Assurance in Production, Installation, and Servicing. 2. ISO 14001 Environmental Management Systems - Specification with Guidance for Use. F. National Fire Protection Association (NFPA): 1. NFPA 253 Standard Method of Test for Critical Radiant Flux for Floor Covering Systems Using a Radiant Heat Energy Source. 2. NFPA 258 Recommended Practice for Determining Smoke Generation of Solid Materials. 1.03 SYSTEM DESCRIPTION A. Performance Requirements: 1. The manufacturer of the flooring product must be accredited to both ISO 9001 (Quality Management System) and ISO 14001 (Environmental Management System). 2. Provide resilient tile flooring which has been manufactured and can be installed to maintain performance criteria stated by manufacturer without defects, damage or failure. 1.04 SUBMITTALS RESILIENT TILE FLOORING 096519-2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS A. General: Submit listed submittals in accordance with Conditions of the Contract and Division 01 Submittal Procedure Section(s). B. Product Data: Submit product data, including manufacturer's technical specifications, for each type of specified products. C. Shop Drawings: Submit shop drawings showing layout, pattern and colors. D. Samples: Submit selection and verification samples for finish and colors. E. Quality Assurance/Control Submittals: Submit the following: 1. Test Reports: Upon request, submit test reports of physical performance and characteristics from recognized test laboratories. 2. Technical Specifications: Submit manufacturer's technical specification document that certifies products meet or exceed specified requirements. 3. Manufacturer's Instructions: Submit manufacturer's installation instructions for resilient flooring. F. Closeout Submittals: Submit the following: 1. Maintenance Data: Maintenance data for installed products in accordance with Division 01 Closeout Submittals, Maintenance Data and Operation Data Section. Include methods for maintaining installed products and precautions against cleaning materials and methods detrimental to finishes and performance. 2. Warranty: Submit warranty documents specified herein. 1.05 QUALITY ASSURANCE A. Manufacturer: The manufacturer of the flooring product must be accredited to both ISO 9001 (Quality Management System) and ISO 14001 (Environmental Management System). B. Flooring Contractor Qualifications: 1. The awarded contractor shall be an established firm with experience in the installation of the specified product and have access to all manufacturers' required technical, maintenance, specifications and related documents. 2. The flooring contractor shall have completed at least 3 projects of similar scope, material and complexity, and must provide project reference details including contact names and telephone numbers. C. Installer Qualifications: An experienced installer, as determined by contractor, who has specialized in the installation of work similar to that required for this project is to perform the work of this section. 1. Installation procedures should be in strict accordance with Amtico International published technical documentation and shall not begin until the work of all other trades has been completed. RESILIENT TILE FLOORING 096519-3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Test Floors: Install test floor at project site using acceptable products and manufacturer approved installation methods. Obtain Owner's and Architect's acceptance of maintainability and workmanship standard. Comply with Division 01 Quality Control (Test Floor Requirements) Section. 1. Test Floor Size: 8'x8' 2. Maintenance: Maintain test floor during construction for workmanship comparison; remove and legally dispose of test floor when no longer required. 3. Incorporation: Test floor may be incorporated into final construction upon Owner's approval. E. Preinstallation Meetings: Conduct preinstallation meeting to verify project requirements, substrate conditions, manufacturer's installation instructions and manufacturer's warranty requirements. Comply with Division 01 Project Management and Coordination (Project Meetings) Section. 1.06 DELIVERY, STORAGE & HANDLING A. General: Comply with Division 01 Product Requirements Section. B. Ordering: Comply with manufacturer's ordering instructions and lead time requirements to avoid construction delays. C. Delivery: Deliver materials in manufacturer's original, unopened, undamaged containers with identification labels intact. D. Storage and Protection: Store materials flat, protected from exposure to harmful weather conditions, between 50 degrees F - 81 degrees F (10 - 27 degrees C) and 50% (± 10%) relative humidity. 1.07 PROJECT CONDITIONS A. Substrate Conditions: Use the current test methods described below to determine the dryness as required to ensure initial and long-term success: 1. Comply with ASTM F1869 testing procedures. 2. Comply with ASTM F2170 testing procedures. 3. The General Contractor shall be responsible for conducting in situ relative humidity testing (ASTM F2170) or calcium chloride testing (ASTM F1869). Perform minimum of 3 tests for the first 1000 square feet, and at least one test for each additional 1000 square feet, to ensure concrete internal relative humidity does not exceed 80% or moisture vapor emissions do not exceed 5.0 lb per 1000 square feet within a 24 hour period. 4. Contingency for High Moisture Readings: If at the time of testing the moisture readings are in excess of 80% internal relative humidity or 5.0 lb moisture vapor emissions, the Architect will initiate testing using petrographic analysis to determine the Water/Cement Ratio and if sufficient hydration has taken place. If the Specifications were not followed in their entirety, water/cement ratio (as specified), and/or the concrete surface has been RESILIENT TILE FLOORING 096519-4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS inadequately hydrated, the Contractor responsible for the placement of the cement shall be responsible for the costs associated with the petrographic analysis and subsequent remediation requirements. B. The Flooring Contractor shall verify in writing to the Owner, a minimum of thirty (30) days prior to scheduled resilient flooring installation, the following substrate conditions: 1. Moisture: Maximum of 80% internal relative humidity tested in accordance with the current ASTM F2170 or maximum of 5.0 lb Moisture Vapor Emission Rate tested in accordance with the current ASTM F1869. 2. Alkalinity (ASTM F710): Between 7.0 - 10.0 pH. 3. Suitability of Substrate Surface: Ensure that substrate surface is sound, smooth and flat to 1/8 inch in 10 feet (3.2 nun in 3.1 m). 4. For substrate conditions that require additional preparation, Flooring Contractor shall furnish Owner and General Contractor with written documentation detailing noncompliance, proposed remediation, timing and cost. C. Environmental Requirements/Conditions: In accordance with manufacturer's recommendations. Areas to receive flooring shall be clean, fully enclosed, weathertight with stable environmental conditions between 64 degrees F - 81 degrees F (18 - 27 degrees C) and 50% (* 10%) relative humidity. The flooring material shall be conditioned in the same manner. D. Temperature Requirements: Maintain air temperature and relative humidity levels in spaces where products will be installed for time period before, during and after installation as recommended by manufacturer. 1. Temperature Conditions: Maintain 64 degrees F - 81 degrees F (18 - 27 degrees C) for 48 hours before, during and continuously after installation. 2. Relative Humidity Conditions: Maintain 50% (± 10%) relative humidity for 48 hours before, during and continuously after installation. E. Close spaces to traffic during resilient flooring installation and for time period after installation recommended in writing by the manufacturer. 1. No foot traffic for 24 hours after installation. 2. No point loads for 48 hours after installation. 3. Wait 5 days after installation before any wet maintenance is performed. F. Install resilient flooring material and accessories after all other finishing operations, including painting, have been completed. 1.08 WARRANTY A. Project Warranty: Refer to Conditions of the Contract for project warranty provisions. B. Manufacturer's Warranty: Submit manufacturer's Commercial Limited Wear Warranty for Owner's acceptance. Manufacturer's warranty is in addition to, and not a limitation of, other rights Owner may have under the Contract Documents. RESILIENT TILE FLOORING 096519-5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Warranty Period: Twenty years commencing on Date of Substantial Completion. 2. Warranty Acceptance: Owner is sole authority who will determine acceptability of manufacturer's warranty documents. 1.09 MAINTENANCE A. Extra Materials: Deliver extra materials from same production run as products installed to Owner. Package products with protective covering and identify with descriptive labels. Comply with Division 01 Closeout Submittals (Maintenance Materials) Section. 1. Quantity: Furnish quantity of full-size units equal to 5% of amount installed. 2. Delivery, Storage and Protection: Comply with Owner's requirements for delivery, storage and protection of extra materials. PART 2 PRODUCTS Specifier Note: Retain Article for proprietary method specification. Add product attributes, performance characteristics, material standards and descriptions as applicable. Use of such phrases as "or equal" or "or approved equal" or similar phrases may cause ambiguity in specifications. Such phrases require verification (procedural, legal and regulatory) and assignment of responsibility for determining "or equal" products. 2.01 RESILIENT TILE FLOORING A. Luxury Vinyl Tile - Manufacturer: Patcraft Design Catalyst 1. Contact: (800)241-4014, P.O. Box 2128, Dalton, GA 30722, www.patcraft.com 2. Product(s): As specified in Finish Material List. 3. Wearlayer: 20 mil 4. Wearlayer Thickness: .120 (3 mm) 5. Reference Specification ASTMF 1700: a. Class III printed film vinyl tile b. Type A (smooth) 6. Finish: ExoGuard Quartz Enhanced Urethane 7. Installation: Glue down 8. Recommended Adhesive: Shaw 4100 or 5150 9. Antimicrobial: FlorSept 10. Tile Size: 18" x 18" B. Acceptable Alternate Manufacturers: 1. Amtico 2. Centiva RESILIENT TILE FLOORING 096519-6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Vinyl Composition Tile Flooring — Armstrong 1. Contact: Armstrong, P.O. Box 3001, Lancaster, PA 17604, 1-800-233-3823, www.amrstrong.com 2. Products: As specified on drawings. D. Azrock VCT, SOLIDS & FEATURE STRIPS specify — Resilient Vinyl Composition Tile Flooring with the following physical characteristics: 1. Complies with requirements for ASTM F 1066, Class 1 (Solid Color) Standard Specification for Vinyl Composition Floor Tile 2. Wear layer/Overall thickness: 1/8" (3.2 mm) 3. Tile sizes: 12" x 12" (30.5 cm x 30.5 cm) 4. Slip Resistance: ADA Compliant 5. ASTM F 970, Standard Test Method for Static Load Limit — 150 PSI 6. ASTM E 648, Standard Test method for Critical Radiant Flux of 0.45 watts/cm2 or greater, Class I 7. Warranty: 5 year Manufacturer's Warranty 2.02 PRODUCT SUBSTITUTION A. Substitutions: No substitutions permitted. 2.03 RELATED MATERIALS A. Leveling and Patching Compounds: Refer to Division 03 Concrete Section. B. Concrete Curing, Sealing, Hardening and Parting Compounds: Refer to Division 03 Concrete Section. C. Expansion Joint Covers: Refer to Division 07 Joint Protection Sections. D. Vapor Retarders: Refer to Division 07 Vapor Retarder Section. 2.04 SOURCE QUALITY CONTROL A. Source Quality Control: Obtain resilient tile flooring proprietary products, including vinyl tile, from a single manufacturer. PART 3 EXECUTION 3.01 MANUFACTURER'S INSTRUCTIONS A. Compliance: Comply with manufacturer's product data for substrate condition, preparation and installation, including product technical bulletins, product catalog installation instructions and RESILIENT TILE FLOORING 096519-7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS product packaging instructions for installation. Flooring contractor must examine areas and conditions under which resilient flooring and accessories are to be installed and must notify General Contractor in writing of conditions detrimental to proper and timely completion of work. Do not proceed with work until unsatisfactory conditions have been corrected in manner acceptable to Owner and Architect. 3.02 EXAMINATION A. Substrates: Examine and verify that all substrates, which have been previously installed under other sections, are acceptable for product installation in accordance with manufacturer's instructions. B. Coordinate with Division 01 General Requirements for testing and allowances, Division 3 Concrete Section and Division 7 Vapor Retarder Section. To ensure a good quality appearance and good adhesion, the subfloor must be hard, smooth, clean, dry and free from defects. Slab on -grade and below -grade subfloors must incorporate an approved vapor retarder (ASTM E1745) properly installed (ASTM E1643) to ensure they are sufficiently dry and to reduce ground moisture vapor transmission from entering the slab after construction. This can be checked by using a suitable moisture test method. More detailed information is available on the preparation of specific subfloor types. C. Concrete Substrate Testing: Prior to flooring installation, test concrete substrates for internal relative humidity (maximum 80% per ASTM F2170) or water vapor emission (maximum 5.O lb per ASTM F1869) and alkalinity (7.0 - 10.0 pH per ASTM F710) harmful to resilient flooring installation performance. Consult resilient flooring manufacturer for requirements pertaining to proprietary resilient flooring products. Include testing costs in contract sum. Refer to Division 01 Quality Requirements. 3.03 PREPARATION A. Surface Preparation: 1. Concrete subfloors shall be constructed in accordance with ACI 302.1 and ACI SP -15, utilizing a water -to -cement ratio of 0.45 or less containing no admixtures or surface treatments that are adverse to the installation of resilient flooring. 2. Concrete subfloors must be finished and cured without additives or surface treatments that will adversely affect the flooring materials according to ACI and ASTM F710 with a minimum compressive strength of 3500 psi (24,115 kPa). 3. Wood subfloors and underlayment panels must be acclimated to within 3% and have an equilibrium moisture content of 14% or less. 4. Floors must be clean, dry and smooth. 5. Incompatible Compounds: Remove compounds and other substances harmful or incompatible with installation adhesives and flooring products. This includes any surface materials, such as paint, wax, grease, oil, adhesive residues, etc. Chemical adhesive removers must be completely removed. Floors must be free of any sealers, curing, hardening or parting compounds that would adversely affect the adhesive used with the flooring. Refer to ACI and ASTM F710. RESILIENT TILE FLOORING 096519-8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 6 A vapor retarder shall be installed prior to pouring of on grade or below grade slabs. Moisture vapor transmission shall not exceed 80% internal Relative Humidity per ASTM F2170 In -Situ Relative Humidity Test and/or 5.0 lb/1000 ftP2P/24 hours per ASTM F1869 Calcium Chloride Test. 7. Wood floors must be double construction with a minimum thickness of 1 inch (25.4 mm). The top layer of wood shall be APA Underlayment Grade Plywood or other wood underlayment panel approved and warranted beneath resilient flooring. Refer to ASTM F1482. 8. Maintain room temperature, adhesive and flooring material at 64 degrees F - 81 degrees F (18 - 27 degrees C) and 50% (*10%) relative humidity for 48 hours before, during and continuously after installation. 9. Broom clean or vacuum surfaces to be covered and inspect substrate. Start of flooring installation indicates acceptance of subfloor conditions and full responsibility for completed work. 10. Adjacent Surfaces Protection: Protect adjacent work areas and finish surfaces from damage during product installation. 11. Substrate Cleaning and Preparation: Comply with manufacturer's requirements for substrate cleaning and preparation for resilient flooring products. 12. Leveling and Patching: Use only Portland cement based leveling and patching compounds, in accordance with compound manufacturer's requirements, to fill depressions, holes and cracks and to smooth substrate surface to 1/8 inch (3.2 mm) in a 10 foot (3.1 m) radius to receive resilient flooring. 3.04 INSTALLATION A. Resilient Tile Installation: Install tiles from established center marks so that tiles at opposite room edge are of equal tile width. Follow installation procedures in accordance with Amtico International published Technical documentation, and do not begin until the work of all other trades has been completed. 1. Patterns: Install tiles with grain running in one direction. 2. Rolling: Roll floor using 100 Ib roller in both directions within 1 hour. B. Adhesive: Apply adhesive to substrate in accordance with manufacturer's instructions, including trowel notching, adhesive mixing and adhesive open and working times. 3.05 FIELD QUALITY CONTROL A. Manufacturer's Field Services: Upon Owner's request, provide manufacturer's field service consisting of product use recommendations and periodic site visit for inspection of product installation in accordance with manufacturer's instructions. 1. Site Visits: At commencement of installation and at flooring installation completion. 3.06 CLEANING & PROTECTION RESILIENT TILE FLOORING 096519-9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS A. Initial Cleaning: Remove temporary coverings and protection of adjacent work areas. When installation has been finished for 24 hours, inspect workmanship and repair or replace damaged installed products. Clean installed products in accordance with manufacturer's instructions prior to Owner's acceptance. Remove construction debris from project site and legally dispose of debris. 1. Pick up litter and sweep floor to remove debris using a non -treated dust mop or vacuum cleaner with hard surface attachment. 2. Initial Wet Cleaning: Wait at least 48 hours after installation is complete before performing the initial wet cleaning process. This will allow the adhesive to cure. 3. Clean new floor thoroughly using a proprietary cleaner/maintainer solution of neutral pH detergent diluted in accordance with manufacturer's instructions. Machine scrub the wet floor using a 3M Red scrubbing pad or equivalent. When finished, remove remaining cleaning solution using a mop or wet vacuum. Rinse floor with clean water and allow to dry thoroughly. 4. In conditions of heavy soiling, pre -wash the floor using a proprietary cleaner solution of neutral pH detergent mixed in accordance with manufacturer's instructions. Allow the solution to stand for 5 - 10 minutes before machine scrubbing or in accordance with the manufacturer's instructions. 5. For floors requiring the application of a floor fmish, initial cleaning should be carried out using a suitable floor stripper. 6. When floor finishes are used, Amtico International recommends at least 2 coats of a satin or low gloss floor finish be applied in accordance with the manufacturer's instructions. Products used should be suitable for the intended usage. 7. Routine Maintenance: Frequency of mop or machine cleaning should be determined based upon daily usage and soiling conditions. Perform routine maintenance in accordance with the Amtico International Maintenance Procedures. 8. Protection: Protect installed product's fmish surfaces from damage during construction. After the floor has been installed, it should be maintained in a manner that provides a clean and slip resistant surface for occupant safety. 3.07 SCHEDULES A. Schedules: Refer to Finish Floor Plan for location of resilient tile flooring. END OF SECTION 096519 RESILIENT TILE FLOORING 096519-10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 09 67 23 - RESINOUS FLOORING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Industrial resinous flooring systems. 2. High-performance resinous flooring systems. B. Related Sections: 1. Section 07 92 00 "Joint Sealants" for sealants installed at joints in resinous flooring systems. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. Include manufacturer's technical data, application instructions, and recommendations for each resinous flooring component required. B. Samples for Initial Selection: For each type of exposed finish required. C. Samples for Verification: For each resinous flooring system required, 6 inches (150 mm) square, applied to a rigid backing by Installer for this Project. 1.4 INFORMATIONAL SUBMITTALS A. Installer Certificates: Signed by manufacturer certifying that installers comply with specified requirements. B. Material Certificates: For each resinous flooring component, from manufacturer. C. Material Test Reports: For each resinous flooring system. 1.5 CLOSEOUT SUBMITTALS A. Maintenance Data: For resinous flooring to include in maintenance manuals. RESINOUS FLOORING 09 67 23 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.6 QUALITY ASSURANCE A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation of flooring systems required for this Project. 1. Engage an installer who is certified in writing by resinous flooring manufacturer as qualified to apply resinous flooring systems indicated. B. Source Limitations: Obtain primary resinous flooring materials, including primers, resins, hardening agents, grouting coats, and topcoats, from single source from single manufacturer. Provide secondary materials, including patching and fill material, joint sealant, and repair materials, of type and from source recommended by manufacturer of primary materials. 1.7 DELIVERY, STORAGE, AND HANDLING A. Deliver materials in original packages and containers, with seals unbroken, bearing manufacturer's labels indicating brand name and directions for storage and mixing with other components. 1.8 PROJECT CONDITIONS A. Environmental Limitations: Comply with resinous flooring manufacturer's written instructions for substrate temperature, ambient temperature, moisture, ventilation, and other conditions affecting resinous flooring application. B. Lighting: Provide permanent lighting or, if permanent lighting is not in place, simulate permanent lighting conditions during resinous flooring application. C. Close spaces to traffic during resinous flooring application and for not less than 24 hours after application unless manufacturer recommends a longer period. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Basis -of -Design Product: Subject to compliance with requirements, provide Key Resin Company — Key Urecon SL or comparable product by one of the following: 1. BASF Construction Chemicals, Inc.; BASF Building Systems. 2. ChemMasters. 3. Delta Polymers, Inc. 4. Dur -A -Flex, Inc. 5. Epoxy Systems, Inc. 6. Tnemec Company, Inc. 7. Tufco International Inc. 8. Valspar Flooring. RESINOUS FLOORING 09 67 23 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.2 MATERIALS A. VOC Content of Liquid -Applied Flooring Components: Mot more than 100 g/L when calculated according to 40 CFR 59, Subpart D (EPA Method 24): B. Low -Emitting Materials: Flooring system shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small -Scale Environmental Chambers." 2.3 INDUSTRIAL RESINOUS FLOORING A. Resinous Flooring: Abrasion-, impact- and chemical -resistant, industrial -aggregate -filled, resin - based, monolithic floor surfacing designed to produce a seamless floor[ and integral cove base]. B. System Characteristics: 1. Color and Patten: As selected by Architect from manufacturer's full range. 2. Wearing Surface: Manufacturer's standard wearing surface. 3. Overall System Thickness: 1/4 inch (6.4 mm. C. System Physical Properties: Provide resinous flooring system with the following minimum physical property requirements when tested according to test methods indicated: 1. Compressive Strength: 7500 psi per ASTM C 579, 7 days. 2. Tensile Strength: 1100 psi per ASTM C 307. 3. Flexural Modulus of Elasticity: 2600 psi per ASTM C 580. 4. Passes Thermal Shock Resistance (ASTM C-884). 5. Coefficient of Thermal Expansion: 2 x 10-5 per °F per ASTM C 531. 6. Passes Chemical Resistance (ASTM D-1308). 7. Impact Resistance: Withstands 16 ft./lbs. with no chipping, cracking, or delamination and not more than 1/16 -inch (1.6 -mm) permanent indentation per MIL -D-3134. 8. Resistance to Elevated Temperature: No slip or flow of more than 1/16 inch (1.6 mm) per MIL -D-3134. 9. Flammability: Self -extinguishing per ASTM D 635. 10. Hardness: 80 - 85, Shore D per ASTM D 2240. 11. Bond Strength: 300 psi minimum tensile strength, 100 percent concrete failure per ACI 503R. 12. Will not support Fungus & Bacteria Growth per MIL -F-52505. 2.4 ACCESSORIES A. Primer: Type recommended by manufacturer for substrate and body coats indicated. B. Patching and Fill Material: Resinous product of or approved by resinous flooring manufacturer and recommended by manufacturer for application indicated. RESINOUS FLOORING 09 67 23 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION 3.1 PREPARATION A. General: Prepare and clean substrates according to resinous flooring manufacturer's written instructions for substrate indicated. Provide clean, dry substrate for resinous flooring application. B. Concrete Substrates: Provide sound concrete surfaces free of laitance, glaze, efflorescence, curing compounds, form -release agents, dust, dirt, grease, oil, and other contaminants incompatible with resinous flooring. 1. Repair damaged and deteriorated concrete according to resinous flooring manufacturer's written instructions. 2. Verify that concrete substrates are dry and moisture -vapor emissions are within acceptable levels according to manufacturer's written instructions. a. Perform anhydrous calcium chloride test, ASTM F 1869. Proceed with application of resinous flooring only after substrates have maximum moisture -vapor -emission rate of 3 Ib of water/1000 sq. ft. (1.36 kg of water/92.9 sq. m) of slab area in 24 hours or as per manufacturer's requirements. b. Perform plastic sheet test, ASTM D 4263. Proceed with application only after testing indicates absence of moisture in substrates. c. Perform relative humidity test using in situ probes, ASTM F 2170. Proceed with installation only after substrates have a maximum 75 percent relative humidity level measurement or as per manufacturer's requirements. 3. Alkalinity and Adhesion Testing: Verify that concrete substrates have pH within acceptable range. Perform tests recommended by manufacturer. Proceed with application only after substrates pass testing. C. Resinous Materials: Mix components and prepare materials according to resinous flooring manufacturer's written instructions. D. Use patching and fill material to fill holes and depressions in substrates according to manufacturer's written instructions. E. Treat control joints and other nonmoving substrate cracks to prevent cracks from reflecting through resinous flooring according to manufacturer's written instructions. 3.2 APPLICATION A. General: Apply components of resinous flooring system according to manufacturer's written instructions to produce a uniform, monolithic wearing surface of thickness indicated. 1. Coordinate application of components to provide optimum adhesion of resinous flooring system to substrate, and optimum intercoat adhesion. 2. Cure resinous flooring components according to manufacturer's written instructions. Prevent contamination during application and curing processes. RESINOUS FLOORING 09 67 23 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3. At substrate expansion and isolation joints, comply with resinous flooring manufacturer's written instructions. B. Apply primer over prepared substrate at manufacturer's recommended spreading rate. C. Apply waterproofing membrane, where indicated, in manufacturer's recommended thickness. 1. Apply waterproofing membrane to integral cove base substrates. D. Apply reinforcing membrane to substrate cracks. E. Integral Cove Base: Apply cove base mix to wall surfaces before applying flooring. Apply according to manufacturer's written instructions and details including those for taping, mixing, priming, troweling, sanding, and topcoating of cove base. Round internal and external corners. 1. Integral Cove Base: 4 inches (100 mm) high. F. Apply self -leveling slurry body coats in thickness indicated for flooring system. 1. Broadcast aggregates at rate recommended by manufacturer and, after resin is cured, remove excess aggregates to provide surface texture indicated. G. Apply troweled or screeded body coats in thickness indicated for flooring system. Hand or power trowel and grout to fill voids. When cured, remove trowel marks and roughness using method recommended by manufacturer. H. Apply grout coat, of type recommended by resinous flooring manufacturer, to fill voids in surface of final body coat and to produce wearing surface indicated. I. Apply topcoats in number indicated for flooring system and at spreading rates recommended in writing by manufacturer. 3.3 FIELD QUALITY CONTROL A. Core Sampling: At the direction of Owner and at locations designated by Owner, take one core sample per 1000 sq. ft. (92.9 sq. m) of resinous flooring, or portion of, to verify thickness. For each sample that fails to comply with requirements, take two additional samples. Repair damage caused by coring and correct deficiencies. B. Protect resinous flooring from damage and wear during the remainder of construction period. Use protective methods and materials, including temporary covering, recommended in writing by resinous flooring manufacturer. RESINOUS FLOORING 09 67 23 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS END OF SECTION 09 67 23 RESINOUS FLOORING 09 67 23 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 09 6813 -TILE CARPETING PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Tile carpeting. 1.3 PREINSTALLATION MEETINGS A. Preinstallation Conference: Conduct conference at Project site. 1. Review methods and procedures related to carpet tile installation including, but not limited to, the following: a. Review delivery, storage, and handling procedures. b. Review ambient conditions and ventilation procedures. c. Review subfloor preparation procedures. 1.4 SUBMITTALS A. Product Data: Submit product data for each carpet material and installation accessory required. Submit written data on physical characteristics, durability, resistance to fading, and flame resistance characteristics. B. Shop Drawings: 1. Columns, doorways, enclosing walls or partitions, built-in cabinets, and locations where cutouts are required in carpet tiles. 2. Type of subfloor. 3. Type of installation. 4. Pattern of installation. 5. Pattern type, location, and direction. 6. Pile direction. C. Samples: For each of the following products and for each color and texture required. Label each Sample with manufacturer's name, material description, color, pattern, and designation indicated on Drawings and in schedules. 1. Carpet Tile: Full-size Sample. 2. Exposed Edge, Transition, and Other Accessory Stripping: 12 -inch -long Samples. TILE CARPETING 096183-1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Product Schedule: For carpet tile. Use same designations indicated on Drawings. E. Qualification Data: For Installer. F. Product Test Reports: For carpet tile, for tests performed by a qualified testing agency. G. Sample Warranty: For warranty indicated. H. Maintenance Data; For carpet tiles to include in maintenance manuals. Include the following: L Methods for maintaining carpet tile, including cleaning and stain -removal products and procedures and manufacturer's recommended maintenance schedule. 2. Precautions for cleaning materials and methods that could be detrimental to carpet tile. 1.5 MAINTENANCE MATERIAL SUBMITTALS A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. L Carpet Tile: Full-size units equal to 5 percent of amount installed for each type indicated, but not less than 10 sq. yd. 1.6 QUALITY ASSURANCE A. Installer Qualifications: An experienced installer who is certified by the International Certified Floorcovering Installers Association Advanced Commercial certification level. B. Fire -Test -Response Ratings: Provide carpet tile identical to those of assemblies tested for fire response according to NFPA 253 by a qualified testing agency. 1.7 DELIVERY, STORAGE, AND HANDLING A. Comply with CRI 104. 1.8 FIELD CONDITIONS A. Comply with CRI 104 for temperature, humidity, and ventilation limitations. B. Environmental Limitations: Do not deliver or install carpet tiles until spaces are enclosed and weathertight, wet work in spaces is complete and dry, and ambient temperature and humidity conditions are maintained at occupancy levels during the remainder of the construction period. C. Do not install carpet tiles over concrete slabs until slabs have cured and are sufficiently dry to bond with adhesive and concrete slabs have pH range recommended by carpet tile manufacturer. 1.9 WARRANTY A. Manufacturer's Warranty for Carpet Tiles: Manufacturer agrees to repair or replace components of carpet tile installation that fail in materials or workmanship within specified warranty period. TILE CARPETING 096183-2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Warranty does not include deterioration or failure of carpet tile due to unusual traffic, failure of substrate, vandalism, or abuse. 2. Failures include, but are not limited to, more than 10 percent edge raveling, snags, runs, dimensional stability, excess static discharge, loss of tuft bind strength, loss of face fiber, abrasive wear and delamination. 3. Warranty Period: Lifetime from date of Substantial Completion. PART 2 -PRODUCTS 2.l TILE CARPETING A. Products and Manufacturers: Refer to Material List Sheet A1.02.20, Basis of Desi en: Sub'ect to compliance with reuirements, provide Products and Manufacturers as listed in the Material List. or comparable products from an approved manufacturer. 2.2 PERFORMANCE REQUIREMENTS A. CPT -1, CPT -2, CPT -3, CPT -4: 1. Fiber Content: Eco Solution q Nylon, 62% solution dyed / 38% yam dyed. 2. Pile Characteristic: Multi -Level Pattern Loop pile. 3. Density: 6990 oz./cu. yd. 4. Pile Thickness: 0.103. 5. Stitches: 9.0 6. Gage: 1/12 7. Tufted Yarn Weight: 20 oz./sq. yd.. 8. Backing System: Synthetic EcoWorx Tile 9. Size: 24.9" h x 28.8" dia x 14.4" side 10. Applied Soil -Resistance Treatment: SSP Shaw Soil Protection 11. Antimicrobial Treatment: Manufacturer's standard material 12. Performance Characteristics: As follows: a. Appearance Retention Rating: Heavy traffic, 3.0 minimum according to ASTM D 7330. b. Critical Radiant Flux Classification: Not less than 0.45 W/sq. cm. c. Dry Breaking Strength: Not less than 100 Ibf according to ASTM D 2646. d. Delamination: Not less than 4 lbf/in. according to ASTM D 3936. e. Dimensional Tolerance: Within 1/32 inch of specified size dimensions, as determined by physical measurement. f. Dimensional Stability: 0.2 percent or less according to ISO 2551 (Aachen Test). g. Resistance to Insects: Comply with AATCC 24. h. Colorfastness to Crocking: Not less than 4, wet and dry, according to AA'TCC 165. i. Colorfastness to Light: Not less than 4 after 60 AFU (AATCC fading units) according to AATCC 16, Option E. j. Antimicrobial Activity: Not less than 2 -mm halo of inhibition for gram -positive bacteria, not less than 1 -mm halo of inhibition for gram-negative bacteria, and no fungal growth, according to AATCC 174. k. Electrostatic Propensity: Less than 3.5kV according to AATCC 134. TILE CARPETING 096183-3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. CPT -5, CPT -6: 1. Fiber Content: Eco Solution q Nylon, 100% solution dyed: 2. Pile Characteristic: Random tip shear. 3. Density: 6887 oz./cu. yd. 4. Pile Thickness: 0.115. 5. Stitches: 9.5 s.p.i. 6. Gage: 1/12 7. Surface Pile Weight: 22 oz/ 8. Primary Backing / Backcoating: Synthetic Ecoworx 9. Size: 24.9" h x 28.8" dia. x 14.4" side 10. Applied Soil -Resistance Treatment: SSP Shaw Soil Protection 11. Antimicrobial Treatment: Manufacturer's standard material 12. Performance Characteristics: As follows: a. Appearance Retention Rating: Heavy traffic, 3.5 minimum according to ASTM D 7330. b. Critical Radiant Flux Classification: Class I -Not less than 0.45 W/sq. cm. c. Tuft Bind: Not less than 6.25 lbf according to ASTM D 1335. d. Delamination: Not less than 3.5 Ibf/in. according to ASTM D 3936. e. Dimensional Tolerance: Within 1/32 inch of specified size dimensions, as determined by physical measurement. f. Dimensional Stability: 0.2 percent or less according to ISO 2551 (Aachen Test). g. Resistance to Insects: Comply with AATCC 24. h. Colorfastness to Crocking: Not less than 4, wet and dry, according to AATCC 165. i. Colorfastness to Light: Not less than 4 after 60 AFU (AATCC fading units) according to AATCC 16, Option E. j. 10. Antimicrobial Activity: Not less than 2 -mm halo of inhibition for gram -positive bacteria, not less than 1 -mm halo of inhibition for gram-negative bacteria, and no fungal growth, according to AATCC 174. k. Electrostatic Propensity: Less than 3.5kV according to AATCC 134. 1. NSF 140 Certification: PLATINUM certified. B. CPT -7, CPT -8: 1. Fiber Content: Eco Solution q 2. Pile Characteristic: Multi-level pattern loop, 100% solution dyed. 3. Density: 4993 oz./cu. yd. 4. Pile Thickness: .0280. 5. Stitches: 10.0 s.p.i. 6. Gage: 1/12 7. Surface Pile Weight: 19 oz 8. Primary Backing / Backcoating: Synthetic Ecoworx 9. Size: 24" x 24" 10. Applied Soil -Resistance Treatment: SSP Shaw Soil Protection 2.3 INSTALLATION ACCESSORIES A. Trowelable Leveling and Patching Compounds: Latex -modified, hydraulic-cementbased formulation provided or recommended by carpet tile manufacturer. TILE CARPETING 096183-4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Adhesives: Water-resistant, mildew -resistant, nonstaining, pressure -sensitive type to suit products and subfloor conditions indicated, that complies with flammability requirements for installed carpet tile and is recommended by carpet tile manufacturer for releasable installation. 1. Adhesives shall have a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). C. Metal Edge/Transition Strips: Extruded aluminum with mill finish of profile and width shown, of height required to protect exposed edge of carpet, and of maximum lengths to minimize running joints. PART 3 -EXECUTION 3.1 EXAMINATION A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for maximum moisture content, alkalinity range, installation tolerances, and other conditions affecting carpet tile performance. Examine carpet tile for type, color, pattern, and potential defects. B. Concrete Subfloors: Verify that concrete slabs comply with ASTM F 710 and the following: 1. Slab substrates are dry and free of curing compounds, sealers, hardeners, and other materials that may interfere with adhesive bond. Determine adhesion and dryness characteristics by performing bond and moisture tests recommended by carpet tile manufacturer. 2. Subfloor finishes comply with requirements specified in Section 03 3000 "Cast -in -Place Concrete" for slabs receiving carpet tile. 3. Subfloors are free of cracks, ridges, depressions, scale, and foreign deposits. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 PREPARATION A. General: Comply with CRI 104, "Site Conditions; Floor Preparation," and with carpet tile manufacturer's written installation instructions for preparing substrates indicated to receive carpet tile installation. B. Use trowelable leveling and patching compounds, according to manufacturer's written instructions, to fill cracks, holes, depressions, and protrusions in substrates. Fill or level cracks, holes and depressions 1/8 inch wide or wider and protrusions more than 1/32 inch unless more stringent requirements are required by manufacturer's written instructions. Broom and vacuum clean substrates to be covered immediately before installing carpet tile. 3.3 INSTALLATION A. General: Comply with CRI 104, "Carpet Modules," and with carpet tile manufacturer's written installation inst uctions. B. Installation Method: Full spread, pressure -sensitive adhesive with antimicrobial. TILE CARPETING 096183-5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Installation Direction: As shown on Drawings. D. Maintain dye lot integrity. Do not mix dye lots in same area. E. Cut and fit carpet tile to butt tightly to vertical surfaces, permanent fixtures, and built-in furniture including cabinets, pipes, outlets, edgings, thresholds, and nosings. Bind or seal cut edges as recommended by carpet tile manufacturer. F. Extend carpet tile into toe spaces, door reveals, closets, open -bottomed obstructions, removable flanges, alcoves, and similar openings. G. Maintain reference markers, holes, and openings that are in place or marked for future cutting by repeating on finish flooring as marked on subfloor. Use nonpermanent, nonstaining marking device. H. Stagger joints of carpet tiles so carpet tile grid is offset from access flooring panel grid. Do not fill seams of access flooring panels with carpet adhesive; keep seams free of adhesive. 3.4 CLEANING AND PROTECTION A. Perform the following operations immediately after installing carpet tile: 1. Remove excess adhesive, seam sealer, and other surface blemishes using cleaner recommended by carpet tile manufacturer. 2. Remove yarns that protrude from carpet tile surface. 3. Vacuum carpet tile using commercial machine with face -beater element. B. Protect installed carpet tile to comply with CRI 104, "Protecting Indoor Installations". C. Protect carpet tile against damage from construction operations and placement of equipment and fixtures during the remainder of construction period. Use protection methods indicated or recommended in writing by carpet tile manufacturer. END OF SECTION 09 6813 TILE CARPETING 096183-6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 09 72 50 - DECORATIVE QUARTZ EPDXY FLOORING PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. Work of this Section as shown or specified shall be in accordance with the requirements of the Contract Documents. 1.2 WORK INCLUDED A. Work of this Section includes all labor, materials, equipment and services necessary to com- plete epoxy flooring incorporating ceramic coated colored inorganic quartz aggregate and inte- gral base as selected on drawings and/or specified herein. 1.2 RELATED WORK A. Concrete - Section 03300 B. Floor drains - Division 15 1.4 SUBMITTALS A. General: Submit the following in accordance with Conditions of Contract and Division 1 Specification Sections. B. Product Data: Submit manufacturer's technical data application instructions and general recommendations for decorative quartz epoxy flooring specified herein. C. Samples for initial selection purposes in form of manufacturer's color charts showing range of standard colors available. 1. Submit 2-1/2" x 4" samples in color and quartz aggregate combination as selected. D. Material certificates signed by manufacturer certifying that the decorative quartz epoxy flooring submitted complies with requirements specified herein. E. Maintenance Instructions: Submit manufacturer's written instructions for recommended maintenance practices. DECORATIVE EPDXY FLOORING 09725-1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.5 QUALITY ASSURANCE A. Installer Qualifications: Engage an experienced installer or applicator who has specialized in installing resinous flooring types similar to that required for this Project and who is acceptable to manufacturer of primary materials. B. Single -Source Responsibility: Obtain epoxy component of floring materials, including primers, resins, hardening agents, and fmish or sealing coats, from a single manufacturer. Obtain ceramic -coated quartz aggregate from primary manufacturer of that product. 1.6 DELIVERY STORAGE AND HANDLING A. Deliver materials in original packages and containers with seals unbroken and bearing manufacturer's labels containing brand name and directions for storage and mixing with other components. B. Store materials to comply with manufacturer's directions to prevent deterioration from moisture, heat, cold, direct sunlight, or other detrimental effects. 1.7 PROJECT CONDITIONS A. Environmental Conditions: Comply with epoxy resin composition flooring manufacturer's directions for maintenance of ambient and substrate temperature, moisture, humidity, ventilation, and other conditions required to execute and protect work. B. Lighting: Permanent lighting will be in place and working before installing decorative quartz epoxy flooring. PART 2- PRODUCTS 2.1 MATERIALS A. Decorative quartz epoxy flooring shall be Dex-O-Tex Decor-Flor as manufactured by Crossfield Products Corp. in Rancho Dominguez, California and Roselle Park, New Jersey. B. Approved alternate Manufacturers Key quartz Sanseam. 2.2 PROPERTIES A. Colors: As indicated, or if not otherwise indicated, as selected by Architect from manufacturer's standard color combinations. DECORATIVE EPDXY FLOORING 09725-2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Physical Properties: Provide flooring system that meets or exceeds the listed minimum physical property requirements when tested according to the referenced standard test method in parenthesis. Compressive Strength Complete System (ASTM C109) Resin Component (ASTM D695) Surface Hardness (ASTM D2240) 8,556 psi. 12,900 psi. Durometer D 85 Aggregate Hardness (Moh's Mineral Scale) 6 1/2-7 Indentation Characteristics (MIL -PRF -3134) Para. 4.7.4.2.1 -Steadily Applied Load) 0.005 indentation Impact Resistance (MIL -PRF -3134) 0.011 indentation Para. (4.7.3) No cracking, loss of bond Adhesion (ACI Comm. 503.1-92) 345 psi. (100% failure in concrete) Water Absorption (MIL -PRF -3134) Less than 1% Abrasion Resistance (ASTM C501) 19 Wear Index (H-22 Wheel) Tensile Strength (ASTM D638) 4,400 psi. Resin Component Elongation (ASTM D638) 19.6% Resin Component 2.3 SUPPLEMENTAL MATERIALS A. Waterproofing Membrane: Type recommended or produced by manufacturer of epoxy resin composition flooring system for type of service and floor condition indicated. B. Anti -Microbial Additive: Incorporate antimicrobial chemical additive to control growth of most bacteria, fungi, algae and actinomycetes. PART 3 - EXECUTION 3.1 INSPECTION A. Examine the areas and conditions where decorative quartz epoxy flooring is to be installed and notify the Architect of conditions detrimental to the proper and timely completion of the work. Do not proceed with the work until unsatisfactory conditions have been corrected by the Contractor in a manner acceptable to the Architect. DECORATIVE EPDXY FLOORING 09725-3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.2 PREPARATION A. Substrate: Perform preparation and cleaning procedures according to flooring manufacturer's instructions for particular substrate conditions involved, and as specified. Provide clean, dry, and neutral substrate for flooring application. B. Concrete Surfaces: Shot -blast, acid etch or power scarify as required to obtain optimum bond of flooring to concrete. Remove sufficient material to provide a sound surface, free of laitance, glaze, efflorescence, and any bond -inhibiting curing compounds or form release agents. Remove grease, oil, and other penetrating contaminates. Repair damaged and deteriorated concrete to acceptable condition. Leave surface free of dust, dirt, laitance, and efflorescence. C. Materials: Mix epoxy resin components when required, and prepare materials according to flooring system manufacturer's instructions. 3.3 APPLICATION A. General: Apply each component of decorative quartz epoxy flooring system according to manufacturer's directions to produce a uniform monolithic flooring surface of thickness indicated. B. Broadcast Coats: Apply liberal application of clear epoxy resin mixture, allow to self -level, broadcast (by hand or spray machine) ceramic coated quartz aggregate, allow to set to hardness, sweep off excess unbonded aggregate and repeat process to achieve total nominal thickness of 1/16"-1/8". C. Finish or Sealing Coats: After quartz filled broadcast coats have cured sufficiently, apply finish coats of type recommended by flooring manufacturer to produce finish matching approved submittal sample and in number of coats and spreading rates recommended by manufacturer. 1. Finished floor shall be 1/16"-1/8" thick, uniform in color and free of trowel marks. D. Cove Base: Apply cove base mix to wall surfaces at locations shown to form cove base height of 4 inches unless otherwise indicated. Follow manufacturer's printed instructions and details including taping, mixing, priming, troweling, sanding, and top -coating of cove base. 3.4 CURING, PROTECTION AND CLEANING A. Cure decorative quartz epoxy flooring materials according to manufacturer's directions, taking care to prevent contamination during application stages and before completing curing process. Close application area for a minimum of 24 hours. END OF SECTION 09725 DECORATIVE EPDXY FLOORING 09725-4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 098433 - SOUND -ABSORBING WALL UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes shop -fabricated, fabric -wrapped panel units tested for acoustical performance, including: 1. Sound -absorbing wall panels. 2. Sound -diffusing wall panels. 1.3 DEFINITIONS A. NRC: Noise Reduction Coefficient. B. SAA: Sound Absorption Average. 1.4 ACTION SUBMITTALS A. Product Data: For each type ofpanel edge, core material, and mounting indicated. B. Shop Drawings: For sound -absorbing wall units. Include mounting devices and details; details at panel head, base, joints, and corners; and details at ceiling, floor base, and wall intersections. Indicate panel edge and core materials. 1. Include elevations showing panel sizes and direction of fabric weave and pattern matching. C. Samples for Initial Selection: For each type of fabric facing from sound -absorbing wall unit manufacturer's full range. D. Samples for Verification: For the following products, prepared on Samples of size indicated below: 1. Panel Edge: 12 -inch- (300 -mm-) long Sample(s) showing each edge profile, comer, and finish. 2. Core Material: 12 -inch- (300 -mm-) square Sample at corner. 3. Mounting Devices: Full-size Samples. SOUND -ABSORBING WALL UNITS 098433 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.5 INFORMATIONAL SUBMITTALS A. Coordination Drawings: Elevations and other details, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved: 1. Items penetrating or covered by sound -absorbing wall units including the following: a. Lighting fixtures. b. Air outlets and inlets. c. Speakers. d. Alarms. e. Sprinklers. f. Access panels. g. B. Product Certificates: For each type of sound -absorbing wall unit, from manufacturer. C. Warranty: Sample of special warranty. 1.6 CLOSEOUT SUBMITTALS A. Maintenance Data: For sound -absorbing wall units to include in maintenance manuals. Include fabric manufacturers' written cleaning and stain -removal recommendations. 1.7 QUALITY ASSURANCE A. Source Limitations: Obtain sound -absorbing wall units from single source from single manufacturer. B. Fire -Test -Response Characteristics: Provide sound -absorbing wall units meeting the following as determined by testing identical products by UL or another testing and inspecting agency acceptable to authorities having jurisdiction: 1. Surface -Burning Characteristics: As determined by testing per ASTM E 84. a. Flame -Spread Index: [25] or less. b. Smoke -Developed Index: [450] or less. 2. Fire Growth Contribution: Meeting acceptance criteria of local code and authorities having jurisdiction when tested according to [NFPA 265] [NFPA 286]. C. Preinstallation Conference: Conduct conference at [Project site]. 1.8 DELIVERY, STORAGE, AND HANDLING A. Comply with fabric and sound -absorbing wall unit manufacturers' written instructions for minimum and maximum temperature and humidity requirements for shipment, storage, and handling. SOUND -ABSORBING WALL UNITS 098433 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Deliver materials and units in unopened bundles and store in a temperature -controlled dry place with adequate air circulation. 1.9 PROJECT CONDITIONS A. Environmental Limitations: Do not install sound -absorbing wall units until spaces are enclosed and weathertight, wet work in spaces is complete and dry, work at and above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use. B. Lighting: Do not install sound -absorbing wall units until a permanent level of lightingis provided on surfaces to receive the units. C. Air -Quality Limitations: Protect sound -absorbing wall units from exposure to airborne odors, such as tobacco smoke, and install units under conditions free from odor contamination of ambient air. D. Field Measurements: Verify locations of sound -absorbing wall units and actual dimensions of openings and penetrations by field measurements before fabrication. 1.10 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of sound -absorbing wall units that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to the following: a. Acoustical performance. b. Fabric sagging, distorting, or releasing from panel edge. c. Warping of core. 2. Warranty Period: Two years from date of Substantial Completion. PART2-PRODUCTS 2.1 SOUND -ABSORBING WALL UNITS A. Manufacturers: Subject to compliance with requirementsavailable manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: B. Basis -of -Desi m Product: Subject to compliance with requirements, provide product indicated or comparable product by one of the following: 1. Acoustical Panel Systems (APS, Inc.). 2. Acoustical Solutions, Inc. 3. Armstrong World industries. SOUND -ABSORBING WALL UNITS 098433 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 4. AVI, Svstems, Ino. 5. Benton Brothers Solutions, I_nc. 6. Coned Desiguscape; an Owens Coming company. 7. Decoustics Limited; a CertainTeed Ceilings unman 8. Essi Acoustical Products. 9. Goltennan c&_Sabo. 10. Kinetics Noise Control, the. 11. Lanvin, Inc. 12. MBI Products Company, Inc. 13. Panel Solutions, Inc. 14. Perdue Acoustics. 15. Pinta Acoustic, Inc. 16. Proudfoot Com any Ina The . 17. Sound Concepts Canada,_Inc. 18. Sound Manacement Group 1JLC. 19. Tectum Inc. 20. Wall Technology, Inc.; an Owens Conlin:, companv. 21. Working Walls Inc. 22. <Insert manufacturer's name>. C. General Requirements for Sound -Absorbing Wall Units: Units shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small -Scale Environmental Chambers." D. Sound -Diffusing Wall Panel 1. Basis -of -Design Product: Tectum V -Line Wall Panels; a. Thiness: 2 inches b. Edge: Long edge beveled c. Color: Custom Colors d. Accessories: Panel Edge Spline- furnich vinyl splines, clips, molding, painted head fastners, and touch-up paint necessary for the intended installation. Colors to be coordinated with panel colors, as selected by Architect. 2.2 MATERIALS A. General: a. Material: Aspen wood fibers bonded with inorganic hydraulic cement PART 3 - EXECUTION 3.1 EXAMINATION A. Examine fabric, fabricated units, substrates, areas, and conditions, for compliance with requirements, installation tolerances, and other conditions affecting performance of sound - absorbing wall units. SOUND -ABSORBING WALL UNITS 098433 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Install sound -absorbing wall units in locations indicated with vertical surfaces and edges plumb, top edges level and in alignment with other units, faces flush, and scribed to fit adjoining work accurately at borders and at penetrations. B. Comply with sound -absorbing wall unit manufacturer's written instructions for installation of units using type of mounting devices indicated. Mount units securely to supporting substrate. C. Align and level fabric pattern and grain among adjacent units. 3.3 INSTALLATION TOLERANCES A. Variation from Plumb and Level: Plus or minus [1/16 inch (1.6 mm)]. B. Variation of Panel Joints from Hairline: Not more than [1/16 inch (1.6 mm)] [1/32 inch (0.79 mmwide. 3.4 CLEANING A. Clip loose threads; remove pills and extraneous materials. B. Clean panels on completion of installation to remove dust and other foreign materials according to manufacturer's written instructions. END OF SECTION 098433 SOUND -ABSORBING WALL UNITS 098433 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 09 90 00 - INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS PART 1 GENERAL 1.1 SECTION INCLUDES A. Interior paint and coatings systems(LEED-09 NC/Cl/CS COMPLIANT) including surface preparation. 1.2 RELATED SECTIONS A. Section 03300 - Concrete: Surface coordination and curing provisions. B. Section 05120 - Structural Steel: Shop priming structural steel. C. Section 05500 - Metal Fabrications: Shop priming ferrous metal. D. Section 06200 - Finish Carpentry: Shop priming architectural woodwork. E. Section 06400 - Architectural Woodwork: Shop -applied stains and transparent finishes. F. Section 08110 - Steel Doors and Frames: Factory priming steel doors and frames. G. Section 09260 - Gypsum Board Assemblies: Surface preparation of gypsum board. H. Section 15050 - Basic Mechanical Materials and Methods: Mechanical identification. L Section 16050 - Basic Electrical Materials and Methods: Mechanical identification. 1.3 REFERENCES A. Steel Structures Painting Council (SSPC): 1. SSPC-SP 1 - Solvent Cleaning. 2. SSPC-SP 2 - Hand Tool Cleaning. 3. SSPC-SP 3 - Power Tool Cleaning. 4. SSPC-SP5/NACE No. 1, White Metal Blast Cleaning. 5. SSPC-SP6/NACE No. 3, Commercial Blast Cleaning. 6. SSPC-SP7/NACE No. 4, Brush -Off Blast Cleaning. 7. SSPC-SP1O/NACE No. 2, Near -White Blast Cleaning. 8. SSPC-SP11, Power Tool Cleaning to Bare Metal. 9. SSPC-SP12/NACE No. 5, Surface Preparation and Cleaning of metals by Waterjetting Prior to Recoating. 10. SSPC-SP 13 / NACE No. 6 Surface Preparation for Concrete. INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS 09900-1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Environmental Protection Agency (EPA): Method 24 - Determination Of Volatile Matter Content, Water Content, Density, Volume Solids, And Weight Solids Of Surface Coatings. C. South Coast Air Quality Management District (SCAQMD): Rule 113 - Architectural Coatings.(January 1, 2004) D. Green Seal, Inc.: 1. GS -11 Standard for Paints and Coatings.(lst Edition, May 20,1993) 2. GC -03 - Environmental Criteria for Anti -Corrosive Paints. E. United States Green Building Council (USGBC): LEED-09 NC/Cl/CS 1.4 SUBMITTALS A. Submit under provisions of Section 01300. B. Product Data: For each paint system indicated, including. 1. Product characteristics. 2. Surface preparation instructions and recommendations. 3. Primer requirements and finish specification. 4. Storage and handling requirements and recommendations. 5. Application methods. 6. Cautions for storage, handling and installation. C. Selection Samples: Submit a complete set of color chips that represent the full range of manufacturer's products, colors and sheens available. D. Verification Samples: For each finish product specified, submit samples that represent actual product, color, and sheen. Provide full 8 x 11 draw down sheets. 1.5 QUALITY ASSURANCE E. Installer Qualifications: A firm or individual experienced in applying paints and coatings similar in material, design, and extent to those indicated for this Project, whose work has resulted in applications with a record of successful in-service performance. F. Paint exposed surfaces. If a color of finish, or a surface is not specifically mentioned, Architect will select from standard products, colors and sheens available. G. Do not paint prefinished items, concealed surfaces, finished metal surfaces, operating parts, and labels unless indicated. H. Mock -Up: Provide a mock-up for evaluation of surface preparation techniques and application workmanship. 1. Finish surfaces for verification of products, colors and sheens. 2. Finish area designated by Architect. 3. Provide samples that designate primer and finish coats. INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS 09900-2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 4. Do not proceed with remaining work until the Architect approves the mock-up. 1.5 DELIVERY, STORAGE, AND HANDLING A. Delivery: Deliver manufacturer's unopened containers to the work site. Packaging shall bear the manufacturer's name, label, and the following list of information. 1. Product name, and type (description). 2. Application and use instructions. 3. Surface preparation. 4. VOC content. 5. Environmental issues. 6. Batch date. 7. Color number. B. Storage: Store and dispose of solvent -based materials, and materials used with solvent -based materials, in accordance with requirements of local authorities having jurisdiction. C. Store materials in an area that is within the acceptable temperature range, per manufacturer's instructions. Protect from freezing. D. Handling: Maintain a clean, dry storage area, to prevent contamination or damage to the coatings. 1.6 PROJECT CONDITIONS A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits. 1.7 EXTRA MATERIALS A. Furnish extra paint materials from the same production run as the materials applied and in the quantities described below. Package with protective covering for storage and identify with labels describing contents. Deliver extra materials to Owner. B. Furnish Owner with an additional one percent of each material and color, but not less than 1 gal (3.8 1) or 1 case, as appropriate. PART 2 PRODUCTS 2.1 MANUFACTURERS A. Acceptable Manufacturer: Sherwin-Williams, which is located at: 101 Prospect Ave. ; Cleveland, OH 44115; Toll Free Tel: 800-524-5979; Tel: 216-566-2000; Fax: 440-826-1989; Email: request info (sherwin ultlead.com); Web: www.sherwin-williams.com/pro/services/architects designers/?WT.mc id=SWRedirect ProSe rvices Architects B. Requests for substitutions will be considered in accordance with provisions of Section 01600. INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS 09900-3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.2 APPLICATIONS/SCOPE A. Interior Paints and Coatings:(LEED-09 NC/CI/CS COMPLIANT) 1. Concrete: Poured, precast, tilt -up, cast -in-place, cement board, plaster. 2. Concrete: Floors. 3. Masonry: Concrete masonry units, including split -face, scored, and smooth block. 4. Metal: Aluminum, galvanized steel. 5. Metal: Structural steel, joists, trusses, beams, partitions and similar items. 6. Wood: Walls, ceilings, doors, trim and similar items. 7. Wood: Floors, painted. 8. Wallboard: Gypsum drywall. 2.3 PAINT MATERIALS - GENERAL A. Paints and Coatings. 1. Unless otherwise indicated, provide factory -mixed coatings. When required, mix coatings to correct consistency in accordance with manufacturer's instructions before application. Do not reduce, thin, or dilute coatings or add materials to coatings unless such procedure is specifically described in manufacturer's product instructions. 2. For opaque finishes, tint each coat including primer coat and intermediate coats, one-half shade lighter than succeeding coat, with final finish coat as base color. Or follow manufactures product instructions for optimal color conformance. B. Primers: Where the manufacturer offers options on primers for a particular substrate, use primer categorized as "best" by the manufacturer. C. Coating Application Accessories: Provide all primers, sealers, cleaning agents, cleaning cloths, sanding materials, and clean-up materials required, per manufacturer's specifications. D. Color: Refer to Finish Schedule for paint colors, and as selected. E. Refer to the current MSDS/EDS for exact VOCs. VOCs may vary by base. Some colors may not be 0 VOC after tinting with conventional colorants. 2.4 INTERIOR PAINT SYSTEMS A. CONCRETE - (Walls and Ceilings, Poured Concrete, Precast Concrete, Unglazed Brick, Cement Board, Tilt -Up, Cast -In -Place) including PLASTER - (Walls, Ceilings). 1. Latex Systems: a. Eg-Shel / Satin Finish (Low Odor - Zero VOC Finish): 1) 1st Coat: S -W Loxon Acrylic Masonry Primer, A24W8300 (8 mils wet, 3.2 mils dry). 2) 2nd Coat: S -W ProMar 200 Zero VOC Latex Eg-Shel, B20-2600 Series. 3) 3rd Coat: S -W ProMar 200 Zero VOC Latex Eg-Shel, B20-2600 Series (4 mils wet, 1.6 mils dry per coat). INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS 09900-4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. METAL - (Structural Steel Columns, Joists, Trusses, Beams, Miscellaneous and Ornamental Iron, Structural Iron, Ferrous Metal) 1. Alkyd System a. Semi -Gloss Finish (Water Base): 1) 1st Coat: S -W Pro Industrial Pro-Cryl Universal Primer, B66-310 Series (5-10 mils wet, 2-4 mils dry). 2) 2nd Coat: S -W ProMar 200 Waterbased Acrylic/Alkyd Semi -Gloss, B34-8200 Series. 3) 3rd Coat: S -W ProMar 200 Waterbased Acrylic/Alkyd Semi -Gloss, B34-8200 Series (4 mils wet, 1.7 mils dry per coat). 2. Epoxy System (Water Base) a. Semi -Gloss Finish: 1) 1st Coat: S -W Pro Industrial Pro-Cryl Universal Primer, B66-310 Series (5-10 mils wet, 2-4 mils dry). 2) 2nd Coat: S -W Waterbased Catalyzed Epoxy, B70W211/ B60V25. 3) 3rd Coat: S -W Waterbased Catalyzed Epoxy, B70W211/ B60V25 (2.5 - 3 mils dry per coat). C. DRYWALL - (Walls, Ceilings, Gypsum Board and similar items) 1. Latex Systems: a. Eg-Shel / Satin Finish (Low Odor - Zero VOC ): 1) 1st Coat: S -W ProMar 200 Zero VOC Interior Latex Primer, B28W2600 (4 mils wet, 1.5 mils dry).. 2) 2nd Coat: S -W ProMar 200 Zero VOC Latex Eg-Shel, B20-2600 Series. 3) 3rd Coat: S -W ProMar 200 Zero VOC Latex Eg-Shel, B20-2600 Series (4 mils wet, 1.6 mils dry per coat). PART 3 EXECUTION 3.1 EXAMINATION A. Do not begin installation until substrates have been properly prepared; notify Architect of unsatisfactory conditions before proceeding. If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding. B. Proceed with work only after conditions have been corrected and approved by all parties, otherwise application of coatings will be considered as an acceptance of surface conditions. 3.2 SURFACE PREPARATION INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS 09900-5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS A. General: Surfaces shall be dry and in sound condition. Remove oil, dust, dirt, loose rust, peeling paint or other contamination to ensure good adhesion. 1. Remove mildew before painting by washing with a solution of 1 part liquid household bleach and 3 parts of warm water. Apply the solution and scrub the mildewed area. Allow the solution to remain on the surface for 10 minutes. Rinse thoroughly with clean water and allow the surface to dry 48 hours before painting. Wear protective glasses or goggles, waterproof gloves, and protective clothing. Quickly wash off any of the mixture that comes in contact with your skin. Do not add detergents or ammonia to the bleach/water solution. 2. Remove items including but not limited to thermostats, electrical outlets, switch covers and similar items prior to painting. After completing painting operations in each space or area, reinstall items removed using workers skilled in the trades involved. 3. No exterior painting should be done immediately after a rain, during foggy weather, when rain is predicted, or when the temperature is below 50 degrees F (10 degrees C), unless products are designed specifically for these conditions. On large expanses of metal siding, the air, surface and material temperatures must be 50 degrees F (10 degrees F) or higher to use low temperature products. B. Aluminum: Remove all oil, grease, dirt, oxide and other foreign material by cleaning per SSPC-SP1, Solvent Cleaning. C. Block (Cinder and Concrete): Remove all loose mortar and foreign material. Surface must be free of laitance, concrete dust, dirt, form release agents, moisture curing membranes, loose cement, and hardeners. Concrete and mortar must be cured at least 30 days at 75 degrees F (24 degrees C). The pH of the surface should be between 6 and 9, unless the products are designed to be used in high pH environments. On tilt -up and poured -in-place concrete, commercial detergents and abrasive blasting may be necessary to prepare the surface. Fill bug holes, air pockets, and other voids with a cement patching compound. D. Concrete, SSPC-SP13 or NACE 6: This standard gives requirements for surface preparation of concrete by mechanical, chemical, or thermal methods prior to the application of bonded protective coating or lining systems. The requirements of this standard are applicable to all types of cementitious surfaces including cast -in-place concrete floors and walls, precast slabs, masonry walls, and shotcrete surfaces. An acceptable prepared concrete surface should be free of contaminants, laitance, loosely adhering concrete, and dust, and should provide a sound, uniform substrate suitable for the application of protective coating or lining systems. E. Cement Composition Siding/Panels: Remove all surface contamination by washing with an appropriate cleaner, rinse thoroughly and allow to dry. Existing peeled or checked paint should be scraped and sanded to a sound surface. Pressure clean, if needed, with a minimum of 2100 psi pressure to remove all dirt, dust, grease, oil, loose particles, laitance, foreign material, and peeling or defective coatings. Allow the surface to dry thoroughly. The pH of the surface should be between 6 and 9, unless the products are designed to be used in high pH environments. F. Copper and Stainless Steel: Remove all oil, grease, dirt, oxide and other foreign material by cleaning per SSPC-SP 2, Hand Tool Cleaning. G. Exterior Composition Board (Hardboard): Some composition boards may exude a waxy material that must be removed with a solvent prior to coating. Whether factory primed or unprimed, exterior composition board siding (hardboard) must be cleaned thoroughly and primed with an alkyd primer. INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS 09900-6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS H. Drywall - Exterior: Must be clean and dry. All nail heads must be set and spackled. Joints must be taped and covered with a joint compound. Spackled nail heads and tape joints must be sanded smooth and all dust removed prior to painting. Exterior surfaces must be spackled with exterior grade compounds. I. Drywall - Interior: Must be clean and dry. All nail heads must be set and spackled. Joints must be taped and covered with a joint compound. Spackled nail heads and tape joints must be sanded smooth and all dust removed prior to painting. J. Galvanized Metal: Clean per SSPC-SP1 using detergent and water or a degreasing cleaner to remove greases and oils. Apply a test area, priming as required. Allow the coating to dry at least one week before testing. If adhesion is poor, Brush Blast per SSPC-SP7 is necessary to remove these treatments. K. Plaster: Must be allowed to dry thoroughly for at least 30 days before painting, unless the products are designed to be used in high pH environments. Room must be ventilated while drying; in cold, damp weather, rooms must be heated. Damaged areas must be repaired with an appropriate patching material. Bare plaster must be cured and hard. Textured, soft, porous, or powdery plaster should be treated with a solution of 1 pint household vinegar to 1 gallon of water. Repeat until the surface is hard, rinse with clear water and allow to dry. L. Steel: Structural, Plate, And Similar Items: Should be cleaned by one or more of the surface preparations described below. These methods are used throughout the world for describing methods for cleaning structural steel. Visual standards are available through the Society of Protective Coatings. A brief description of these standards together with numbers by which they can be specified follow. 1. Solvent Cleaning, SSPC-SP1: Solvent cleaning is a method for removing all visible oil, grease, soil, drawing and cutting compounds, and other soluble contaminants. Solvent cleaning does not remove rust or mill scale. Change rags and cleaning solution frequently so that deposits of oil and grease are not spread over additional areas in the cleaning process. Be sure to allow adequate ventilation. 2. Hand Tool Cleaning, SSPC-SP2: Hand Tool Cleaning removes all loose mill scale, loose rust, and other detrimental foreign matter. It is not intended that adherent mill scale, rust, and paint be removed by this process. Before hand tool cleaning, remove visible oil, grease, soluble welding residues, and salts by the methods outlined in SSPC-SPI. 3. Power Tool Cleaning, SSPC-SP3: Power Tool Cleaning removes all loose mill scale, loose rust, and other detrimental foreign matter. It is not intended that adherent mill scale, rust, and paint be removed by this process. Before power tool cleaning, remove visible oil, grease, soluble welding residues, and salts by the methods outlined in SSPC-SP1. 4. White Metal Blast Cleaning, SSPC-SP5 or NACE 1: A White Metal Blast Cleaned surface, when viewed without magnification, shall be free of all visible oil, grease, dirt, dust, mill scale, rust, paint, oxides, corrosion products, and other foreign matter. Before blast cleaning, visible deposits of oil or grease shall be removed by any of the methods specified in SSPC-SP1 or other agreed upon methods. INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS 09900-7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 5. Commercial Blast Cleaning, SSPC-SP6 or NACE 3: A Commercial Blast Cleaned surface, when viewed without magnification, shall be free of all visible oil, grease, dirt, dust, mill scale, rust, paint, oxides, corrosion products, and other foreign matter, except for staining. Staining shall be limited to no more than 33 percent of each square inch of surface area and may consist of light shadows, slight streaks, or minor discoloration caused by stains of rust, stains of mill scale, or stains of previously applied paint. Before blast cleaning, visible deposits of oil or grease shall be removed by any of the methods specified in SSPC-SP1 or other agreed upon methods. 6. Brush -Off Blast Cleaning, SSPC-SP7 or NACE 4: A Brush -Off Blast Cleaned surface, when viewed without magnification, shall be free of all visible oil, grease, dirt, dust, loose mill scale, loose rust, and loose paint. Tightly adherent mill scale, rust, and paint may remain on the surface. Before blast cleaning, visible deposits of oil or grease shall be removed by any of the methods specified in SSPC-SP 1 or other agreed upon methods. 7. Power Tool Cleaning to Bare Metal, SSPC-SP11: Metallic surfaces that are prepared according to this specification, when viewed without magnification, shall be free of all visible oil, grease, dirt, dust, mill scale, rust, paint, oxide corrosion products, and other foreign matter. Slight residues of rust and paint may be left in the lower portions of pits if the original surface is pitted. Prior to power tool surface preparation, remove visible deposits of oil or grease by any of the methods specified in SSPC-SP1, Solvent Cleaning, or other agreed upon methods. 8. Near -White Blast Cleaning, SSPC-SP10 or NACE 2: A Near White Blast Cleaned surface, when viewed without magnification, shall be free of all visible oil, grease, dirt, dust, mill scale, rust, paint, oxides, corrosion products, and other foreign matter, except for staining. Staining shall be limited to no more than 5 percent of each square inch of surface area and may consist of light shadows, slight streaks, or minor discoloration caused by stains of rust, stains of mill scale, or stains of previously applied paint. Before blast cleaning, visible deposits of oil or grease shall be removed by any of the methods specified in SSPC-SPI or other agreed upon methods. 9. High- and Ultra -High Pressure Water Jetting for Steel and Other Hard Materials: SSPC-SP12 or NACE 5: This standard provides requirements for the use of high- and ultra-high pressure water jetting to achieve various degrees of surface cleanliness. This standard is limited in scope to the use of water only without the addition of solid particles in the stream. 10. Water Blasting, SSPC-SPI2/NACE No. 5: Removal of oil grease dirt, loose rust, loose mill scale, and loose paint by water at pressures of 2,000 to 2,500 psi at a flow of 4 to 14 gallons per minute. M. Vinyl Siding, Architectural Plastics, EIFS and Fiberglass: Clean thoroughly by scrubbing with a warm, soapy water solution. Rinse thoroughly. Do not paint vinyl siding with any color darker than the original color, unless the product and color are designed for such use. Painting with darker colors may cause siding to warp. N. Stucco: Must be clean and free of any loose stucco. If recommended procedures for applying stucco are followed, and normal drying conditions prevail, the surface may be painted in 30 days. The pH of the surface should be between 6 and 9, unless the products are designed to be used in high pH environments such as Loxon. O. Wood: Must be clean and dry. Prime and paint as soon as possible. Knots and pitch streaks must be scraped, sanded, and spot primed before a full priming coat is applied. Patch all nail holes and imperfections with a wood filler or putty and sand smooth. INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS 09900-8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.3 INSTALLATION A. General: Apply all coatings and materials with manufacture specifications in mind. Mix and thin coatings according to manufacturer's recommendations. B. Do not apply to wet or damp surfaces. Wait at least 30 days before applying to new concrete or masonry. Or follow manufacturer's procedures to apply appropriate coatings prior to 30 days. Test new concrete for moisture content. C. Apply coatings using methods recommended by manufacturer. D. Uniformly apply coatings without runs, drips, or sags, without brush marks, and with consistent sheen. E. Apply coatings at spreading rate required to achieve the manufacturers recommended dry film thickness. F. Regardless of number of coats specified, apply as many coats as necessary for complete hide, and uniform appearance. G. Inspection: The coated surface must be inspected and approved by the Architect just prior to each coat. 3.4 PROTECTION A. Protect finished coatings from damage until completion of project. B. Touch-up damaged coatings after substantial completion, following manufacturer's recommendation for touch up or repair of damaged coatings. Repair any defects that will hinder the performance of the coatings. END OF SECTION 09900 INTERIOR, EXTERIOR AND INDUSTRIAL PAINTS AND COATINGS 09900-9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 09 91 13 - EXTERIOR PAINTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes surface preparation and the application of paint systems on the following exterior substrates: 1. Concrete. 2. Cementitious Siding Planks. 3. Concrete masonry units (CMU). 4. Steel. 5. Galvanized metal. 6. Aluminum (not anodized or otherwise coated). 7. Wood. 8. Plastic trim fabrications. B. Related Requirements: 1. Section 09 91 23 "Interior Painting" for surface preparation and the application of paint systems on interior substrates. 1.3 DEFINITIONS A. Gloss Level 1: Not more than 5 units at 60 degrees and 10 units at 85 degrees, according to ASTM D 523. B. Gloss Level 3: 10 to 25 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523. C. Gloss Level 4: 20 to 35 units at 60 degrees and not less than 35 units at 85 degrees, according to ASTM D 523. D. Gloss Level 5: 35 to 70 units at 60 degrees, according to ASTM D 523. E. Gloss Level 6: 70 to 85 units at 60 degrees, according to ASTM D 523. F. Gloss Level 7: More than 85 units at 60 degrees, according to ASTM D 523. EXTERIOR PAINTING 09 91 13 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.4 ACTION SUBMITTALS A. Product Data: For each type of product. Include preparation requirements and application instructions. B. Samples for Initial Selection: For each type of topcoat product. C. Samples for Verification: For each type of paint system and each color and gloss of topcoat. 1. Submit Samples on rigid backing, 8 inches (200 mm) square. 2. Step coats on Samples to show each coat required for system. 3. Label each coat of each Sample. 4. Label each Sample for location and application area. D. Product List: For each product indicated, include the following: 1. Cross-reference to paint system and locations of application areas. Use same designations indicated on Drawings and in schedules. 2. Printout of current "MPI Approved Products List" for each product category specified, with the proposed product highlighted. 3. VOC content. 1.5 MAINTENANCE MATERIAL SUBMITTALS A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Paint: 5 percent, but not less than 1 gal. (3.8 L) of each material and color applied. 1.6 QUALITY ASSURANCE A. MPI Standards: 1. Products: Complying with MPI standards indicated and listed in "MPI Approved Products List." 2. Preparation and Workmanship: Comply with requirements in "MPI Architectural Painting Specification Manual" for products and paint systems indicated. 1.7 DELIVERY, STORAGE, AND HANDLING A. Store materials not in use in tightly covered containers in well -ventilated areas with ambient temperatures continuously maintained at not less than 45 deg F (7 deg C). 1. Maintain containers in clean condition, free of foreign materials and residue. 2. Remove rags and waste from storage areas daily. EXTERIOR PAINTING 09 91 13 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.8 FIELD CONDITIONS A. Apply paints only when temperature of surfaces to be painted and ambient air temperatures are between 50 and 95 deg F (10 and 35 deg C). B. Do not apply paints in snow, rain, fog, or mist; when relative humidity exceeds 85 percent; at temperatures less than 5 deg F (3 deg C) above the dew point; or to damp or wet surfaces. PART 2- PRODUCTS 2.1 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Benjamin Moore & Co. 2. Color Wheel Paints & Coatings. 3. Flex Bon Paints. 4. PPG Architectural Finishes, Inc. 5. Sherwin-Williams Company (The). 6. Tower Paint. 2.2 PAINT, GENERAL A. Material Compatibility: 1. Provide materials for use within each paint system that are compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience. 2. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated. B. Colors: As selected by Architect from manufacturer's full range. 2.3 BLOCK FILLERS A. Interior/Exterior Latex Block Filler: MPI #4. 1. VOC Content: E Range of E2 or E3. 2.4 PRIMERS/SEALERS A. Bonding Primer (Solvent Based): MPI #69. 1. VOC Content: E Range of El, E2 or E3. EXTERIOR PAINTING 09 91 13 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.5 METAL PRIMERS A. Alkyd Anticorrosive Metal Primer: MPI #79. 1. VOC Content: E Range of El or E2. B. Quick -Drying Alkyd Metal Primer: MPI #76. 1. VOC Content: E Range of El, E2 or E3. C. Waterborne Galvanized -Metal Primer: MPI #134. 1. VOC Content: E Range of El, E2 or E3. 2. Environmental Performance Rating: EPR 1, EPR 2 or EPR 3. D. Quick -Drying Primer for Aluminum: MPI #95. 1. VOC Content: E Range of El, E2 or E3. 2.6 EXTERIOR LATEX PAINTS A. Exterior Latex (Flat): MPI #10 (Gloss Level 1). 1. VOC Content: E Range of El, E2 or E3. B. Exterior Latex (Semigloss): MPI #11 (Gloss Level 5). 1. VOC Content: E Range of El, E2 or E3. 2.7 EXTERIOR ALKYD PAINTS Exterior Alkyd Enamel (Semigloss): MPI #94 (Gloss Level 5). 1. VOC Content: E Range of El or E2. 2.8 QUICK -DRYING ENAMELS A. Quick -Drying Enamel (Semigloss): MPI #81 (Gloss Level 5). 1. VOC Content: E Range of El, E2 or E3. 2.9 ALUMINUM PAINT A. Aluminum Paint: MPI #1. 1. VOC Content: E Range of El, E2 or E3. EXTERIOR PAINTING 09 91 13 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of work. B. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows: 1. Concrete: 12 percent. 2. Masonry (CMU): 12 percent. 3. Plaster: 12 percent. C. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers. D. Begin coating application only after unsatisfactory conditions have been corrected and surfaces are dry. 1. Beginning coating application constitutes Contractor's acceptance of substrates and conditions. 3.2 PREPARATION A. Comply with manufacturer's written instructions and recommendations in "MPI Manual" applicable to substrates and paint systems indicated. B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface -applied protection before surface preparation and painting. 1. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface -applied protection. C. Clean substrates of substances that could impair bond of paints, including dust, dirt, oil, grease, and incompatible paints and encapsulants. 1. Remove incompatible primers and reprime substrate with compatible primers or apply tie coat as required to produce paint systems indicated. D. Concrete Substrates: Remove release agents, curing compounds, efflorescence, and chalk. Do not paint surfaces if moisture content or alkalinity of surfaces to be painted exceeds that permitted in manufacturer's written instructions. E. Masonry Substrates: Remove efflorescence and chalk. Do not paint surfaces if moisture content or alkalinity of surfaces or mortar joints exceeds that permitted in manufacturer's written instructions. EXTERIOR PAINTING 09 91 13 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS F. Steel Substrates: Remove rust, loose mill scale, and shop primer if any. Clean using methods recommended in writing by paint manufacturerRetain "Shop -Primed Steel Substrates" Paragraph below if primers are shop applied and are not removed in the field. G. Shop -Primed Steel Substrates: Clean field welds, bolted connections, and abraded areas of shop paint, and paint exposed areas with the same material as used for shop priming to comply with SSPC-PA 1 for touching up shop -primed surfaces. H. Galvanized -Metal Substrates: Remove grease and oil residue from galvanized sheet metal by mechanical methods to produce clean, lightly etched surfaces that promote adhesion of subsequently applied paints. I. Aluminum Substrates: Remove loose surface oxidation. J. Plastic Trim Fabrication Substrates: Remove dust, dirt, and other foreign material that might impair bond of paints to substrates. 3.3 APPLICATION A. Apply paints according to manufacturer's written instructions. 1. Use applicators and techniques suited for paint and substrate indicated. 2. Paint surfaces behind movable items same as similar exposed surfaces. Before final installation, paint surfaces behind permanently fixed items with prime coat only. B. Tint each undercoat a lighter shade to facilitate identification of each coat if multiple coats of same material are to be applied. Tint undercoats to match color of topcoat, but provide sufficient difference in shade of undercoats to distinguish each separate coat. C. If undercoats or other conditions show through topcoat, apply additional coats until cured film has a uniform paint finish, color, and appearance. D. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks. 3.4 FIELD QUALITY CONTROL A. Testing of Paint Materials: Owner reserves the right to invoke the following procedure at any time and as often as Owner deems necessary during the period when paints are being applied: 1. Owner will engage the services of a qualified testing agency to sample paint materials being used. Samples of material delivered to Project site will be taken, identified, sealed, and certified in presence of Contractor. 2. Testing agency will perform tests for compliance of paint materials with product requirements. 3. Owner may direct Contractor to stop applying paints if test results show materials being used do not comply with product requirements. Contractor shall remove noncomplying - paint materials from Project site, pay for testing, and repaint surfaces painted with rejected materials. Contractor will be required to remove rejected materials from EXTERIOR PAINTING 09 91 13 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS previously painted surfaces if, on repainting with complying materials, the two paints are incompatible. 3.5 CLEANING AND PROTECTION A. At end of each workday, remove rubbish, empty cans, rags, and other discarded materials from Project site. B. After completing paint application, clean spattered surfaces. Remove spattered paints by washing, scraping, or other methods. Do not scratch or damage adjacent finished surfaces. C. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition. D. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces. 3.6 EXTERIOR PAINTING SCHEDULE A. Concrete Substrates, Nontraffic Surfaces: 1. Latex System: MPI EXT 3.1A. a. Prime Coat: Exterior latex matching topcoat. b. Intermediate Coat: Exterior latex matching topcoat. c. Topcoat: Exterior latex (flat). B. CMU Substrates: 1. Latex System: MPI EXT 4.2A. a. Prime Coat: Interior/exterior latex block filler. b. Intermediate Coat: Exterior latex matching topcoat. c. Topcoat: Exterior latex (semigloss). C. Steel Substrates: 1. Alkyd System: MPI EXT 5.1D. a. Prime Coat: Alkyd anticorrosive metal primer. b. Intermediate Coat: Exterior alkyd enamel matching topcoat. c. Topcoat: Exterior alkyd enamel (semigloss). D. Galvanized -Metal Substrates: 1. Latex Over Water -Based Primer System: MPI EXT 5.3H. a. Prime Coat: Waterborne galvanized -metal primer. b. Intermediate Coat: Exterior latex matching topcoat. c. Topcoat: Exterior latex (semigloss). E. Aluminum Substrates: 1. Latex System: MPI EXT 5.4H. a. Prime Coat: Quick -drying primer for aluminum. EXTERIOR PAINTING 09 91 13 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS b. Intermediate Coat: Exterior latex matching topcoat. c. Topcoat: Exterior latex (semigloss). F. Plastic Trim Fabrication Substrates: 1. Latex System: MPI EXT 6.8A. a. Prime Coat: Bonding primer (solvent based). b. Intermediate Coat: Exterior latex matching topcoat. c. Topcoat: Exterior latex (semigloss). G. Stucco Substrates: 1. Latex System: MPI EXT 9.IA. a. Prime Coat: Exterior latex matching topcoat. b. Intermediate Coat: Exterior latex matching topcoat. c. Topcoat: Exterior latex (flat). END OF SECTION 09 91 13 EXTERIOR PAINTING 09 91 13 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 09 91 23 - INTERIOR PAINTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes surface preparation and the application of paint systems on the following interior substrates: 1. Concrete. 2. Concrete masonry units (CMU). 3. Steel. 4. Galvanized metal. 5. Aluminum (not anodized or otherwise coated). 6. Wood. 7. Gypsum board. B. Related Requirements: 1. Section 09 91 13 "Exterior Painting" for surface preparation and the application of paint systems on exterior substrates. 1.3 DEFINITIONS A. Gloss Level 1: Not more than 5 units at 60 degrees and 10 units at 85 degrees, according to ASTM D 523. B. Gloss Level 2: Not more than 10 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523. C. Gloss Level 3: 10 to 25 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523. D. Gloss Level 4: 20 to 35 units at 60 degrees and not less than 35 units at 85 degrees, according to ASTM D 523. E. Gloss Level 5: 35 to 70 units at 60 degrees, according to ASTM D 523. F. Gloss Level 6: 70 to 85 units at 60 degrees, according to ASTM D 523. G. Gloss Level 7: More than 85 units at 60 degrees, according to ASTM D 523. INTERIOR PAINTING 09 91 23 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.4 ACTION SUBMITTALS A. Product Data: For each type of product. Include preparation requirements and application instructions. B. Samples for Initial Selection: For each type of topcoat product. C. Samples for Verification: For each type of paint system and in each color and gloss of topcoat. 1. Submit Samples on rigid backing, 8 inches (200 mm) square. 2. Step coats on Samples to show each coat required for system. 3. Label each coat of each Sample. 4. Label each Sample for location and application area. D. Product List: For each product indicated, include the following: 1. Cross-reference to paint system and locations of application areas. Use same designations indicated on Drawings and in schedules. 2. Printout of current "MPI Approved Products List" for each product category specified in Part 2, with the proposed product highlighted. 3. VOC content. 1.5 MAINTENANCE MATERIAL SUBMITTALS A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Paint: 5 percent, but not less than 1 gal. (3.8 L) of each material and color applied. 1.6 QUALITY ASSURANCE A. MPI Standards: 1. Products: Complying with MPI standards indicated and listed in "MPI Approved Products List." 2. Preparation and Workmanship: Comply with requirements in "MPI Architectural Painting Specification Manual" for products and paint systems indicated. 1.7 DELIVERY, STORAGE, AND HANDLING A. Store materials not in use in tightly covered containers in well -ventilated areas with ambient temperatures continuously maintained at not less than 45 deg F (7 deg C). 1. Maintain containers in clean condition, free of foreign materials and residue. 2. Remove rags and waste from storage areas daily. INTERIOR PAINTING 09 91 23 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.8 FIELD CONDITIONS A. Apply paints only when temperature of surfaces to be painted and ambient air temperatures are between 50 and 95 deg F (10 and 35 deg C). B. Do not apply paints when relative humidity exceeds 85 percent; at temperatures less than 5 deg F (3 deg C) above the dew point; or to damp or wet surfaces. PART 2 - PRODUCTS 2.1 MANUFACTURERS Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Benjamin Moore & Co. 2. Color Wheel Paints & Coatings. 3. Flex Bon Paints. 4. ICI Paints. 5. M.A.B. Paints. 6. PPG Architectural Finishes, Inc. 7. Sherwin-Williams Company (The). 8. Tower Paint. 2.2 PAINT, GENERAL A. Material Compatibility: 1. Provide materials for use within each paint system that are compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience. 2. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated. B. VOC Content of Field -Applied Interior Paints and Coatings: Provide products that comply with the following limits for VOC content, exclusive of colorants added to a tint base, when calculated according to 40 CFR 59, Subpart D (EPA Method 24); these requirements do not apply to paints and coatings that are applied in a fabrication or finishing shop: 1. Flat Paints, Coatings, and Primers: VOC content of not more than 50 g/L. 2. Nonflat Paints, Coatings, and Primers: VOC content of not more than 150 g/L. 3. Anti -Corrosive and Anti -Rust Paints Applied to Ferrous Metals: VOC not more than 250 g/L. 4. Floor Coatings: VOC not more than 100 g/L. 5. Shellacs, Clear: VOC not more than 730 g/L. 6. Shellacs, Pigmented: VOC not more than 550 g/L. 7. Flat Topcoat Paints: VOC content of not more than 50 g/L. 8. Nonflat Topcoat Paints: VOC content of not more than 150 g/L. INTERIOR PAINTING 09 91 23 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 9. Anti -Corrosive and Anti -Rust Paints Applied to Ferrous Metals: VOC not more than 250 g/L. 10. Floor Coatings: VOC not more than 100 g/L. 11. Shellacs, Clear: VOC not more than 730 g/L. 12. Shellacs, Pigmented: VOC not more than 550 g/L. 13. Primers, Sealers, and Undercoaters: VOC content of not more than 200 g/L. 14. Dry -Fog Coatings: VOC content of not more than 400 g/L. 15. Zinc -Rich Industrial Maintenance Primers: VOC content of not more than 340 g/L. 16. Pre -Treatment Wash Primers: VOC content of not more than 420 g/L. C. Chemical Components of Field -Applied Interior Paints and Coatings: Provide topcoat paints and anti -corrosive and anti -rust paints applied to ferrous metals that comply with the following chemical restrictions; these requirements do not apply to paints and coatings that are applied in a fabrication or finishing shop: 1. Aromatic Compounds: Paints and coatings shall not contain more than 1.0 percent by weight of total aromatic compounds (hydrocarbon compounds containing one or more benzene rings). 2. Restricted Components: Paints and coatings shall not contain any of the following: a. Acrolein. b. Acrylonitrile. c. Antimony. d. Benzene. e. Butyl benzyl phthalate. f. Cadmium. g. Di (2-ethylhexyl) phthalate. h. Di -n -butyl phthalate. i. Di-n-octyl phthalate. j. 1,2 -dichlorobenzene. k. Diethyl phthalate. I. Dimethyl phthalate. m. Ethylbenzene. n. Formaldehyde. o. Hexavalent chromium. p. Isophorone. q. Lead. r. Mercury. s. Methyl ethyl ketone. t. Methyl isobutyl ketone. u. Methylene chloride. v. Naphthalene. w. Toluene (methylbenzene). x. 1,1,1 -trichloroethane. y. Vinyl chloride. 2.3 BLOCK FILLERS A. Interior/Exterior Latex Block Filler: MPI #4. INTERIOR PAINTING 09 91 23 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.4 PRIMERS/SEALERS A. Interior Latex Primer/Sealer: MPI #50. B. Interior Alkyd Primer/Sealer: MPI #45. C. Wood -Knot Sealer: Sealer recommended in writing by topcoat manufacturer for use in paint systems indicated. 2.5 METAL PRIMERS A. Alkyd Anticorrosive Metal Primer: MPI #79. B. Quick -Drying Alkyd Metal Primer: MPI #76. C. Rust -Inhibitive Primer (Water Based): MPI #107. D. Cementitious Galvanized -Metal Primer: MPI #26. E. Waterborne Galvanized -Metal Primer: MPI #134. F. Vinyl Wash Primer: MPI #80. G. Quick -Drying Primer for Aluminum: MPI #95. 2.6 WOOD PRIMERS A. Interior Latex -Based Wood Primer: MPI #39. 2.7 LATEX PAINTS A. Interior Latex (Flat): MPI #53 (Gloss Level 1). B. Interior Latex (Low Sheen): MPI #44 (Gloss Level 2). C. Interior Latex (Eggshell): MPI #52 (Gloss Level 3). D. Interior Latex (Satin): MPI #43 (Gloss Level 4). E. Interior Latex (Semigloss): MPI #54 (Gloss Level 5). F. Interior Latex (Gloss): MPI #114 (Gloss Level 6, except minimum gloss of 65 units at 60 deg). G. High -Performance Architectural Latex (Low Sheen): MPI #138 (Gloss Level 2). H. High -Performance Architectural Latex (Eggshell): MPI #139 (Gloss Level 3). I. High -Performance Architectural Latex (Satin): MPI #140 (Gloss Level 4). J. High -Performance Architectural Latex (Semigloss): MPI #141 (Gloss Level 5). INTERIOR PAINTING 09 91 23 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.8 ALKYD PAINTS A. Interior Alkyd (Flat): MPI #49 (Gloss Level 1). B. Interior Alkyd (Eggshell): MPI #51 (Gloss Level 3). C. Interior Alkyd (Semigloss): MPI #47 (Gloss Level 5). D. Interior Alkyd (Gloss): MPI #48 (Gloss Level 6). 2.9 QUICK -DRYING ENAMELS A. Quick -Drying Enamel (Semigloss): MPI #81 (Gloss Level 5). B. Quick -Drying Enamel (High Gloss): MPI #96 (Gloss Level 7). 2.10 DRY FOG/FALL COATINGS A. Latex Dry Fog/Fall: MPI #118. B. Waterbome Dry Fall: MPI #133. C. Interior Alkyd Dry Fog/Fall: MPI #55. 2.11 FLOOR COATINGS A. Interior Concrete Floor Stain: MPI #58. B. Interior/Exterior Clear Concrete Floor Sealer (Water Based): MPI #99. C. Interior/Exterior Clear Concrete Floor Sealer (Solvent Based): MPI #104. 2.12 SOURCE QUALITY CONTROL A. Testing of Paint Materials: Owner reserves the right to invoke the following procedure: 1. Owner will engage the services of a qualified testing agency to sample paint materials. Contractor will be notified in advance and may be present when samples are taken. If paint materials have already been delivered to Project site, samples may be taken at Project site. Samples will be identified, sealed, and certified by testing agency. 2. Testing agency will perform tests for compliance with product requirements. 3. Owner may direct Contractor to stop applying coatings if test results show materials being used do not comply with product requirements. Contractor shall remove noncomplying paint materials from Project site, pay for testing, and repaint surfaces painted with rejected materials. Contractor will be required to remove rejected materials from previously painted surfaces if, on repainting with complying materials, the two paints are incompatible. INTERIOR PAINTING 09 91 23 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows: 1. Concrete: 12 percent. 2. Masonry (Clay and CMU): 12 percent. 3. Wood: 15 percent. 4. Gypsum Board: 12 percent. 5. Plaster: 12 percent. C. Gypsum Board Substrates: Verify that fmishing compound is sanded smooth. D. Plaster Substrates: Verify that plaster is fully cured. E. Spray -Textured Ceiling Substrates: Verify that surfaces are dry. F. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers. G. Proceed with coating application only after unsatisfactory conditions have been corrected. 1. Application of coating indicates acceptance of surfaces and conditions. 3.2 PREPARATION A. Comply with manufacturer's written instructions and recommendations in "MPI Manual" applicable to substrates indicated. B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface -applied protection before surface preparation and painting. 1. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface -applied protection if any. C. Clean substrates of substances that could impair bond of paints, including dust, dirt, oil, grease, and incompatible paints and encapsulants. 1. Remove incompatible primers and reprime substrate with compatible primers or apply tie coat as required to produce paint systems indicated. D. Concrete Substrates: Remove release agents, curing compounds, efflorescence, and chalk. Do not paint surfaces if moisture content or allcalinity of surfaces to be painted exceeds that permitted in manufacturer's written instructions. INTERIOR PAINTING 09 91 23 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS E. Masonry Substrates: Remove efflorescence and chalk. Do not paint surfaces if moisture content or alkalinity of surfaces or mortar joints exceed that permitted in manufacturer's written instructions. F. Steel Substrates: Remove rust, loose mill scale, and shop primer, if any. Clean using methods recommended in writing by paint manufacturer. G. Shop -Primed Steel Substrates: Clean field welds, bolted connections, and abraded areas of shop paint, and paint exposed areas with the same material as used for shop priming to comply with SSPC-PA 1 for touching up shop -primed surfaces. H. Galvanized -Metal Substrates: Remove grease and oil residue from galvanized sheet metal fabricated from coil stock by mechanical methods to produce clean, lightly etched surfaces that promote adhesion of subsequently applied paints. L Aluminum Substrates: Remove loose surface oxidation. J. Wood Substrates: 1. Scrape and clean knots, and apply coat of knot sealer before applying primer. 2. Sand surfaces that will be exposed to view, and dust off. 3. Prime edges, ends, faces, undersides, and backsides of wood. 4. After priming, fill holes and imperfections in the finish surfaces with putty or plastic wood filler. Sand smooth when dried. K. Cotton or Canvas Insulation Covering Substrates: Remove dust, dirt, and other foreign material that might impair bond of paints to substrates. 3.3 APPLICATION A. Apply paints according to manufacturer's written instructions. 1. Use applicators and techniques suited for paint and substrate indicated. 2. Paint surfaces behind movable equipment and furniture same as similar exposed surfaces. Before final installation, paint surfaces behind permanently fixed equipment or furniture with prime coat only. 3. Paint front and backsides of access panels, removable or hinged covers, and similar hinged items to match exposed surfaces. B. Tint each undercoat a lighter shade to facilitate identification of each coat if multiple coats of same material are to be applied. Tint undercoats to match color of topcoat, but provide sufficient difference in shade of undercoats to distinguish each separate coat. C. If undercoats or other conditions show through topcoat, apply additional coats until cured film has a uniform paint finish, color, and appearance. D. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks. INTERIOR PAINTING 09 91 23 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS E. Painting Mechanical and Electrical Work: Paint items exposed in equipment rooms and occupied spaces including, but not limited to, the following: 1. Mechanical Work: a. Uninsulated metal piping. b. Uninsulated plastic piping. c. Pipe hangers and supports. d. Tanks that do not have factory -applied final finishes. e. Visible portions of internal surfaces of metal ducts, without liner, behind air inlets and outlets. f Duct, equipment, and pipe insulation having cotton or canvas insulation covering or other paintable jacket material. g. Ductwork both insulated and uninsulated and mechanical equipment that is exposed to view in normally occupied spaces. h. Mechanical equipment that is indicated to have a factory -primed finish for field painting. 2. Electrical Work: a. Switchgear. b. Panelboards. c. Electrical equipment that is indicated to have a factory -primed finish for field painting. 3.4 CLEANING AND PROTECTION At end of each workday, remove rubbish, empty cans, rags, and other discarded materials from Project site. B. After completing paint application, clean spattered surfaces. Remove spattered paints by washing, scraping, or other methods. Do not scratch or damage adjacent finished surfaces. C. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition. D. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces. 3.5 INTERIOR PAINTING SCHEDULE A. Concrete Substrates, Non -traffic Surfaces: 1. Latex System: MPI INT 3.1E. a. Prime Coat. Interior latex matching topcoat. b. Intermediate Coat: Interior latex matching topcoat. c. Topcoat: Interior latex (low sheen). INTERIOR PAINTING 09 91 23 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. High -Performance Architectural Latex System: MPI INT 3.1C. a. Prime Coat: Interior latex primer/sealer. b. Intermediate Coat: High-performance architectural latex matching topcoat. c. Topcoat: High-performance architectural latex (low sheen). B. Concrete Substrates, Traffic Surfaces (where stain is scheduled or indicated): 1. Concrete Stain System: MPI INT 3.2E. a. First Coat: Interior concrete floor stain. b. Topcoat: Interior concrete floor stain. C. CMU Substrates: 1. Latex System: MPI INT 4.2A. a. Prime Coat: Interior/exterior latex block filler. b. Intermediate Coat: Interior latex matching topcoat. c. Topcoat: Interior latex (low sheen). 2. High -Performance Architectural Latex System: MPI INT 4.2D. a. Prime Coat: Interior/exterior latex block filler. b. Intermediate Coat: High-performance architectural latex matching topcoat. c. Topcoat: High-performance architectural latex (low sheen). D. Steel Substrates: 1. Latex Over Alkyd Primer System: MPI INT 5.1Q. a. Prime Coat: Alkyd anticorrosive metal primer. b. Intermediate Coat: Interior latex matching topcoat. c. Topcoat: Interior latex (satin). E. Galvanized -Metal Substrates: 1. High -Performance Architectural Latex System: MPI INT 5.3M. a. Prime Coat: Waterborne galvanized -metal primer. b. Intermediate Coat: High-performance architectural latex matching topcoat. c. Topcoat: High-performance architectural latex (satin). F. Galvanized -Metal Roof Deck at Gymnasium (finish color matching adjacent steel roof structure): 1. Water -Based Dry -Fall System: MPI INT 5.3H. a. Prime Coat: Waterborne dry fall. b. Topcoat: Waterborne dry fall. G. Steel Roof Structure at Gymnasium (fmish color matching adjacent roof deck): INTERIOR PAINTING 09 91 23 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Water -Based Dry -Fall System: MPI INT 5.1C. a. Prime Coat: Alkyd anticorrosive metal primer. b. Topcoat: Waterborne dry fall. H. Aluminum (Not Anodized or Otherwise Coated) Substrates: 1. High -Performance Architectural Latex System: MPI INT 5.4F. a. Prime Coat: Quick -drying primer for aluminum. b. Inteiuiediate Coat: High-performance architectural latex matching topcoat. c. Topcoat: High-performance architectural latex (satin). I. Dressed Lumber Substrates: Including architectural woodwork and doors not indicated to be factory finished. 1. Latex Over Allcyd Primer System: MPI INT 6.3U. a. Prime Coat: Interior alkyd primer/sealer. b. Intermediate Coat. Interior latex matching topcoat. c. Topcoat: Interior latex (semigloss). 2. Alkyd System: MPI INT 6.3B. a. Prime Coat: Interior alkyd primer/sealer. b. Intermediate Coat: Interior alkyd matching topcoat. c. Topcoat: Interior alkyd (semigloss). J. Gypsum Board Corridor Wall Substrates (not where "epoxy paint" is indicated): 1. High -Performance Architectural Latex System: MPI INT 9.2B. a. Prime Coat: Interior latex primer/sealer. b. Intermediate Coat: High-performance architectural latex matching topcoat. c. Topcoat: High-performance architectural latex (low sheen). K. Gypsum Board Non -Corridor Wall and Ceiling Substrates (not where "epoxy paint" is indicated): 1. Latex System: MPI INT 9.2A. a. Prime Coat: Interior latex primer/sealer. b. Intermediate Coat: Interior latex matching topcoat. c. Topcoat: Interior latex (low sheen). L. Plaster Substrates: 1. Latex System: MPI INT 9.2A. a. Prime Coat: Interior latex primer/sealer. b. Intermediate Coat: Interior latex matching topcoat. c. Topcoat: Interior latex (low sheen). INTERIOR PAINTING 09 91 23 - 11 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS END OF SECTION 09 9123 INTERIOR PAINTING 09 91 23 - 12 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 09 60 00 - HIGH PERFORMANCE COATING PART 1 -GENERAL 1.1 GENERAL REQUIREMENTS A. Work of this Section as shown or specified shall be in accordance with the requirements of the Contract Documents. 1.2 WORK INCLUDED A. Work of this Section includes all labor, materials, equipment and services necessary to complete epoxy flooring incorporating ceramic coated colored inorganic quartz aggregate and integral base as selected on drawings and/or specified herein. 1.3 RELATED WORK A. Concrete - Section 03300 (Note to specifier: Concrete should be either water cured or cured using sodium silicate curing compounds only. Other types of curing compounds are generally not acceptable. Concrete should be cured for a minimum of 28 days. On grade floors should have functioning vapor retarder beneath slab.) B. Floor drains - Division 15 (Note to Specifier: Floor drains, clean -outs etc. should be of the floor -flange type manufactured for use with composition floors by most major drain manufacturers.) 1.4 SUBMITTALS A. General: Submit the following in accordance with Conditions of Contract and Division 1 Specification Sections. B. Product Data: Submit manufacturer's technical data application instructions and general recommendations for decorative quartz epoxy flooring specified herein. C. LEED Submittals: 1. Product Data for Credit MR 4.1 and Credit MR 4.2: For products having recycled content, submit documentation indicating percentages by weight of postconsumer and preconsumer recycled content. a. Include statement indicating costs for each product having recycled content. b. Include LEED Product Information Form for LEED Credits MR 4.1 and 4.2. HIGH PERFORMANCE COATING 099600-1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Product Data for Credit EQ 4.2: For field applied, interior, paints coatings and primers, include printed statement of VOC content indicating compliance with Credit requirements. a. Include LEED Product Information Form for LEED Credit EQ 4.2. 3. Provide additional documentation for products as required to achieve each Credit(s). D. Samples for initial selection purposes in form of manufacturer's color charts showing range of standard colors available. 1. Submit 2-1/2" x 4" samples in color and quartz aggregate combination as selected. E. Material certificates signed by manufacturer certifying that the decorative quartz epoxy flooring submitted complies with requirements specified herein. F. Maintenance Instructions: Submit manufacturer's written instructions for recommended maintenance practices. 1.5 QUALITY ASSURANCE A. Installer Qualifications: Engage an experienced installer or applicator who has specialized in installing resinous flooring types similar to that required for this Project and who is acceptable to manufacturer of primary materials. B. Single -Source Responsibility: Obtain epoxy component of flooring materials, including primers, resins, hardening agents, and finish or sealing coats, from a single manufacturer. Obtain ceramic -coated quartz aggregate from primary manufacturer of that product. 1.6 DELIVERY STORAGE AND HANDLING A. Deliver materials in original packages and containers with seals unbroken and bearing manufacturer's labels containing brand name and directions for storage and mixing with other components. B. Store materials to comply with manufacturer's directions to prevent deterioration from moisture, heat, cold, direct sunlight, or other detrimental effects. 1.7 PROJECT CONDITIONS A. Environmental Conditions: Comply with epoxy resin composition flooring manufacturer's directions for maintenance of ambient and substrate temperature, moisture, humidity, ventilation, and other conditions required to execute and protect work. B. Lighting: Permanent lighting will be in place and working before installing decorative quartz epoxy flooring. HIGH PERFORMANCE COATING 099600-2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 2- PRODUCTS 2.1 MATERIALS A. Decorative quartz epoxy flooring shall be Dex-O-Tex Decor-Flor as manufactured by Crossfield Products Corp. in Rancho Dominguez, California and Roselle Park, New Jersey. 2.2 PROPERTIES A. Colors: As indicated, or if not otherwise indicated, as selected by Architect from manufacturer's standard color combinations. B. Physical Properties: Provide flooring system that meets or exceeds the listed minimum physical property requirements when tested according to the referenced standard test method in parentheses. Compressive Strength Complete System (ASTM C109) Resin Component (ASTM D695) 8,556 psi. 12,900 psi. Surface Hardness (ASTM D2240) Durometer D 85 Aggregate Hardness (Moh's Mineral Scale) 6 1/2-7 Indentation Characteristics (MIL -PRF -3134) Para. 4.7.4.2.1 -Steadily Applied Load) 0.005 indentation Impact Resistance (MIL -PRF -3134) 0.011 indentation Para. (4.7.3) No cracking, loss of bond Adhesion (ACI Comm. 503.1-92) 345 psi. (100% failure in concrete) Water Absorption (MIL -PRF -3134) Less than 1% Abrasion Resistance (ASTM C501) 19 Wear Index (H-22 Wheel) Tensile Strength (ASTM D638) 4,400 psi. Resin Component Elongation (ASTM D638) 19.6% Resin Component HIGH PERFORMANCE COATING 099600-3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.3 SUPPLEMENTAL MATERIALS A. Waterproofing Membrane: Type recommended or produced by manufacturer of epoxy resin composition flooring system for type of service and floor condition indicated. (Note to Specifier: The use of waterproof membrane is optional and is generally confined to suspended floors and in rooms having floor drains and subject to very wet spillage and service. All areas requiring membrane treatment should be clearly shown on plans and finish schedules.) B. Anti -Microbial Additive: Incorporate antimicrobial chemical additive to control growth of most bacteria, fungi, algae and actinomycetes. (Note to Specifier: The use of antimicrobial additive is optional. Its use poses no health hazard.) PART 3 - EXECUTION 3.1 INSPECTION A. Examine the areas and conditions where decorative quartz epoxy flooring is to be installed and notify the Architect of conditions detrimental to the proper and timely completion of the work. Do not proceed with the work until unsatisfactory conditions have been corrected by the Contractor in a manner acceptable to the Architect. 3.2 PREPARATION A. Substrate: Perform preparation and cleaning procedures according to flooring manufacturer's instructions for particular substrate conditions involved, and as specified. Provide clean, dry, and neutral substrate for flooring application. B. Concrete Surfaces: Shot -blast, acid etch or power scarify as required to obtain optimum bond of flooring to concrete. Remove sufficient material to provide a sound surface, free of laitance, glaze, efflorescence, and any bond -inhibiting curing compounds or form release agents. Remove grease, oil, and other penetrating contaminates. Repair damaged and deteriorated concrete to acceptable condition. Leave surface free of dust, dirt, laitance, and efflorescence. C. Materials: Mix epoxy resin components when required, and prepare materials according to flooring system manufacturer's instructions. 3.3 APPLICATION A. General: Apply each component of decorative quartz epoxy flooring system according to manufacturer's directions to produce a uniform monolithic flooring surface of thickness indicated. B. Broadcast Coats: Apply liberal application of clear epoxy resin mixture, allow to self -level, broadcast (by hand or spray machine) ceramic coated quartz aggregate, allow to set to hardness, sweep off excess unbonded aggregate and repeat process to achieve total nominal thickness of 1/16"-1/8". HIGH PERFORMANCE COATING 099600-4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Finish or Sealing Coats: After quartz filled broadcast coats have cured sufficiently, apply finish coats of type recommended by flooring manufacturer to produce finish matching approved submittal sample and in number of coats and spreading rates recommended by manufacturer. 1. Finished floor shall be 1/16"-1/8" thick, uniform in color and free of trowel marks. D. Cove Base: Apply cove base mix to wall surfaces at locations shown to form cove base height of 4 inches unless otherwise indicated. Follow manufacturer's printed instructions and details including taping, mixing, priming, troweling, sanding, and top -coating of cove base. 3.4 CURING, PROTECTION AND CLEANING. A. Cure decorative quartz epoxy flooring materials according to manufacturer's directions, taking care to prevent contamination during application stages and before completing curing process. Close application area for a minimum of 24 hours. DEX-O-TEX PRODUCT LINE Crossfield Products Corp. www.dexotex.com END OF SECTION 099600 3000 E. Harcourt Street Rancho Dominguez, CA 90221 Tel: (310) 886-9100 Fax: (310) 886-9119 140 Valley Road Roselle Park, NJ 07204 Tel: (908) 245-2800 Fax: (908) 245-2583 HIGH PERFORMANCE COATING 099600-5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 101100 - VISUAL DISPLAY UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Visual display board assemblies. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. 1. Include construction details, material descriptions, dimensions of individual components and profiles, finishes, and accessories for visual display units. 2. Include electrical characteristics for motorized units. B. Shop Drawings: For visual display units. 1. Include plans, elevations, sections, details, and attachment to other work. 2. 3. Include sections of typical trim members. Samples for Initial Selection: For each type of visual display unit indicated, for units with factory -applied color fmishes, and as follows: 1. Samples of facings for each visual display panel type, indicating color and texture. 2. Actual factory -finish color samples, applied to substrate. 3. Include accessory Samples to verify color selected. D. Samples: For each type of visual display unit indicated. 1. Visual Display Panel: Not less than 8-1/2 by 1.1 inches (215 by 280 mm), with facing, core, and backing indicated for fmal Work. Include one panel for each type, color, and texture required. 2. Trim: 6 -inch- (150 -mm-) long sections of each trim profile. 3. Display Rail: 6 -inch- (150 -mm-) long section of each type. 4. E. Product Schedule: For visual display units. VISUAL DISPLAY UNITS 101100 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.4 INFORMATIONAL SUBMITTALS A. Qualification Data: For qualified Installer. B. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for surface -burning characteristics of tackboards. C. Sample Warranties: For special warranties. 1.5 QUALITY ASSURANCE A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer. 1.6 DELIVERY, STORAGE, AND HANDLING A. Deliver factory -fabricated visual display units completely assembled in one piece. If dimensions exceed maximum manufactured unit size, or if unit size is impracticable to ship in one piece, provide two or more pieces with joints in locations indicated on approved Shop Drawings. 1.7 PROJECT CONDITIONS A. Environmental Limitations: Do not deliver or install visual display units until spaces are enclosed and weathertight, wet -work in spaces is complete and dry, work above ceilings is complete, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period. B. Field Measurements: Verify actual dimensions of construction contiguous with visual display units by field measurements before fabrication. 1. Allow for trimming and fitting where taking field measurements before fabrication might delay the Work. 1.8 WARRANTY A. Special Warranty for Porcelain -Enamel Face Sheets: Manufacturer agrees to repair or replace porcelain -enamel face sheets that fail in materials or workmanship within specified warranty period. I. Failures include, but are not limited to, the following: a. Surfaces lose original writing and erasing qualities. b. Surfaces exhibit crazing, cracking, or flalcing. 2. Warranty Period: 2 years from date of Substantial Completion. VISUAL DISPLAY UNITS 101100 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 2- PRODUCTS 2.1 MANUFACTURERS A. Source Limitations: Obtain each type of visual display unit from single source from single manufacturer. 2.2 PERFORMANCE REQUIREMENTS A. Surface -Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. 1. Flame -Spread Index: 25 or less. 2. Smoke -Developed Index: 50 or less. 2.3 VISUAL DISPLAY BOARD ASSEMBLY A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: B. Basis -of Design Product: Subject to compliance with requirements, provide or comparable product by one of the following: 1. A -I Visual Systems. 2. AARCO Products. Inc. 3. ADI_Lemcoo Inc. 4. Architectural School Products Ltd. 5. Aristocrat industries, Inc. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. Bangor Cork Company, Inc. Best -Rite Manufacturing: a brand division of MooreC:o, Inc. Claridge Products and Equipment, Inc. an_Vt. 1.1 l lnc. 'White: a division ofGlenroa Inc. Csllent Manufacturing, Inc. Marsh Industries, Inc.; Visual Products Group. Newtine Productsjnc. Peter PeePer Products, Inc. Platinum Visual Systems: a division ofABC School Er ui n C. Visual Display Board Assembly: factory fabricated. 1. Assembly: markerboard. 2. Corners: Square. 3. Width: As indicated on Drawings . 4. Height: As indicated on Drawings . 5. Mounting Method: Direct to wall. VISUAL DISPLAY UNITS 101100 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Markerboard Panel: [Porcelain -enamel -faced] faced] markerboard panel on core indicated. 1. Color: White . E. Aluminum Frames and Trim: Fabricated from not less than 0.062 -inch- (1.57 -mm-) thick, extruded aluminum; standard size and shape . [High-pressure laminate -faced] [Melamine - 1. Field -Applied Trim: Manufacturer's standard, snap -on trim with no visible screws or exposed jointsslip-on trim. 2. Aluminum Finish: Clear anodic finish. F. Chalktray: Manufacturer's standard; continuous. 1. Box Type: Extruded aluminum with slanted front, grooved tray, and cast -aluminum end closures. 2. Solid Type: Extruded aluminum with ribbed section and smoothly curved exposed ends. G. Display Rail: Manufacturer's standard, extruded -aluminum display rail with plastic - impregnated -cork insert, end stops, and continuous paper holder, designed to hold accessories. 1. Size: [1 inch (25 mm)] [2 inches (50 mm)] [3 inches (75 rnm)] high by [full length of visual display unit] [length indicated on Drawings]. 2. 2.4 GENERAL FINISH REQUIREMENTS A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes. B. Protect mechanical fmishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping. C. Appearance of Finished Work: Noticeable variations in same piece are unacceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast. 2.5 A. B. C. ALUMINUM FINISHES Clear Anodic Finish: AAMA 611, AA-M12C22A31, Class II, 0.010 mm or thicker. Color Anodic Finish: AAMA 611, AA-M12C22A32/A34, Class II, 0.010 mm or thicker. Baked -Enamel or Powder -Coat Finish: AAMA 2603, except with a minimum dry film thickness of 1.5 mils (0.04 mm). Comply with coating manufacturer's written instructions for cleaning, conversion coating, and applying and baking finish. VISUAL DISPLAY UNITS 101100 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions, with Installer present, for compliance with requirements for installation tolerances, surface conditions of wall, and other conditions affecting performance of the Work. B. Examine roughing -in for electrical power systems to verify actual locations of connections before installation of motorized, sliding visual display units. C. Examine walls and partitions for proper preparation and backing for visual display units. D. Examine walls and partitions for suitable framing depth where sliding visual display units will be installed. E. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 PREPARATION A. Comply with manufacturer's written instructions for surface preparation. B. Clean substrates of substances, such as dirt, mold, and mildew, that could impair the performance of and affect the smooth, finished surfaces of visual display boards. C. Prepare surfaces to achieve a smooth, dry, clean surface free of flaking, unsound coatings, cracks, defects, projections, depressions, and substances that will impair bond between visual display units and wall surfaces. D. Prime wall surfaces indicated to receive visual display units and as recommended in writing by primer/sealer manufacturer and visual display unit manufacturer. E. Prepare recesses for sliding visual display units as required by type and size of unit. 3.3 INSTALLATION A. General: Install visual display surfaces in locations and at mounting heights indicated on Drawings, or if not indicated, at heights indicated below. Keep perimeter lines straight, level, and plumb. Provide grounds, clips, backing materials, adhesives, brackets, anchors, trim, and accessories necessary for complete installation. B. Factory -Fabricated Visual Display Board Assemblies: Attach concealed clips, hangers, and grounds to wall surfaces and to visual display board assemblies with fasteners at not more than 16 inches (400 mm) o.c. Secure tops and bottoms of boards to walls. C. Visual Display Board Assembly Mounting Heights: Install visual display units at mounting heights indicated on Drawings, or if not indicated, at heights indicated below. VISUAL DISPLAY UNITS 101100 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.4 CLEANING AND PROTECTION A. Clean visual display units according to manufacturer's written instructions. Attach one removable cleaning instructions label to visual display unit in each room. B. Touch up factory -applied fmishes to restore damaged or soiled areas. C. Cover and protect visual display units after installation and cleaning. END OF SECTION 101100 VISUAL DISPLAY UNITS 101100 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER100% CONSTRUCTION DOCUMENTS SECTION 101423 - PANEL SIGNAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Illuminated panel signs. 1.3 DEFINITIONS A. Accessible: In accordance with the accessibility standard. B. Illuminated: Illuminated by lighting source integrally constructed as part of the sign unit. 1.4 COORDINATION A. Furnish templates for placement of sign -anchorage devices embedded in permanent construction by other installers. B. Furnish templates for placement of electrical service embedded in peunanent construction by other installers. 1.5 ACTION SUBMITTALS A. Product Data: For each type of product. B. Shop Drawings: For panel signs. 1. Include fabrication and installation details and attachments to other work. 2. Show sign mounting heights, locations of supplementary supports to be provided by others, and accessories. 3. Show message list, typestyles, graphic elementsand layout for each sign at least . 4. Show locations of electrical service connections. 5. Include diagrams for power, signal, and control wiring. C. Samples for Initial Selection: For each type of sign assembly, exposed component, and exposed finish. 1. Include representative Samples of available typestyles and graphic symbols. PANEL SIGNAGE 101423 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER100% CONSTRUCTION DOCUMENTS D. Samples for Verification: For each type of sign assembly showing all components and with the required finish(es), in manufacturer's standard size unless otherwise indicated and as follows: 1. Panel Signs• Not less than 12 inches (300 mm) square, including corner. 2. Exposed Accessories: Full-size Sampleof each accessory type. E. Sign Schedule: Use same designations specified or indicated on Drawings or in a sign schedule. F. Delegated -Design Submittal: 1. Include structural analysis calculations for signs indicated to comply with design loads; signed and sealed by the qualified professional engineer responsible for their preparation. 1.6 INFORMATIONAL SUBMITTALS A. Qualification Data: For Installerandmanufaeturer. B. Sample Warranty: For special warranty. 1.7 CLOSEOUT SUBMITTALS A. Maintenance Data: For signs to include in maintenance manuals. 1.8 QUALITY ASSURANCE A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer. 1.9 FIELD CONDITIONS A. Field Measurements: Verify locations of anchorage devices andelectrical service embedded in permanent construction by other installers by field measurements before fabrication, and indicate measurements on Shop Drawings. 1.10 WARRANTY A. Special Warranty: Manufacturer agrees to repair or replace components of signs that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Deterioration of finishes beyond normal weathering. b. Deterioration of embedded graphic image. c. Separation or delamination of sheet materials and components. 2. Warranty Period: Five years from date of Substantial Completion. PANEL SIGNAGE 101423 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER100% CONSTRUCTION DOCUMENTS PART 2 - PRODUCTS 2.1 PANEL SIGNS, GENERAL A. Regional Materials: Panel signs shall be manufactured within 500 miles (800 km) of Project site. 2.2 PERFORMANCE REQUIREMENTS A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 "Quality Requirements," to design sign structure and anchorage of illuminated panel sign type(s) to withstand design loads . B. Thermal Movements: For exterior signs, allow for thermal movements from ambient and surface temperature changes. 1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces. C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2.3 SIGNS A. Manufacturers: Subject to compliance with requirementsavailable manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. Ac 2. 3. Allen Industies�Ino. 4. Allen ial_ki gs International. 5. APCO Graphics, Inc. 6. ASE, Inc. 7. ASI Si ; Braille -Tac Division. 8. 9. Bun 10. Clarke Systems. 11. Dislce Sian Cern ra 12. 13. InPro Corporation. 14. Mohawk Sign Systems. 15. Nelson -Harkins Industries. 16. Poblocki Si nCom 17. Seton Identifie 18. Su:. ersi 19. 20. Vowar Products, I Vista System. Products. nv The ; Division of Stamp -Rite, Inc. PANEL SIGNAGE 101423 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER100% CONSTRUCTION DOCUMENTS B. Panel Sign : Sign with smooth, uniform surfaces; with message and characters having uniform faces, sharp corners, and precisely formed lines and profiles; and as follows: 1. Illuminated Panel Sign: Backlighted construction with [ LED lighting including transformers, insulators, and other accessories for operability, with provision for servicing and concealing connections to building electrical system. Use tight or sealed joint construction to prevent unintentional light leakage. Space lamps apart from each other and away from sign surfaces as needed to illuminate evenly. a. Power: As indicated on electrical Drawings. b. Weeps: Provide weep holes to drain water at lowest part of exterior signs. Equip weeps with permanent baffles to block light leakage without inhibiting drainage. 2.4 ACCESSORIES A. Fasteners and Anchors: Manufacturer's standard as required for secure anchorage of signage, noncorrosive and compatible with each material joined, and complying with the following: 1. Use concealed fasteners and anchors unless indicated to be exposed. 2. For exterior exposure, furnish [nonferrous -metal] [stainless-steel] [or] [hot -dip galvanized] <Insert requirement devices unless otherwise indicated. 3. Exposed Metal -Fastener Components, General: a. Fabricated from same basic metal and finish of fastened metal unless otherwise indicated. b. Fastener Heads: For nonstructural connections, use [flathead] [or] [oval countersunk] <Insert shape> screws and bolts with tamper-resistant [Allen - head] [spanner -head] [or] [one -way -head] <Insert slot design> slots unless otherwise indicated. 4. Sign Mounting Fasteners: a. Concealed Studs: Concealed (blind), threaded studs welded or brazed to back of sign material or screwed into back of sign assembly, unless otherwise indicated. b. Projecting Studs: Threaded studs with sleeve spacer, welded or brazed to back of sign material or screwed into back of sign assembly, unless otherwise indicated. c. Through Fasteners: Exposed metal fasteners matching sign finish, with type of head indicated, installed in predrilled holes. 5. Inserts: Furnish inserts to be set by other trades into concrete or masonry work. B. Adhesives: As recommended by sign manufacturer and with a VOC content of [70] <Insert value> g/L or less for adhesives used inside the weatherproofing system and applied on-site when calculated according to 40 CFR 59, Subpart D (EPA Method 24). C. Adhesives: As recommended by sign manufacturer and that comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small -Scale Environmental Chambers." PANEL SIGNAGE 101423 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER100% CONSTRUCTION DOCUMENTS D. Two -Face Tape: Manufacturer's standard high -bond, foam -core tape, 0.045 inch (1.14 mm) thick, with adhesive on both sides. E. Hook -and -Loop Tape: Manufacturer's standard two-part tape consisting of hooked part on sign back and looped side on mounting surface. F. Magnetic Tape: Manufacturer's standard magnetic tape with adhesive on one side. G. Bituminous Paint: Cold -applied asphalt emulsion complying with ASTM D 1187. 2.5 FABRICATION A. General: Provide manufacturer's standard sign assemblies according to requirements indicated. 1. Preassemble signs and assemblies in the shop to greatest extent possible. Disassemble signs and assemblies only as necessary for shipping and handling limitations. Clearly mark units for reassembly and installation; apply markings in locations concealed from view after final assembly. 2. Mill joints to a tight, hairline fit. Form assemblies and joints exposed to weather to resist water penetration and retention. 3. Comply with AWS for recommended practices in welding and brazing. Provide welds and brazes behind finished surfaces without distorting or discoloring exposed side. Clean exposed welded and brazed connections of flux, and dress exposed and contact surfaces. 4. Conceal connections if possible; otherwise, locate connections where they are inconspicuous. 5. Internally brace signs for stability and for securing fasteners. 6. Provide rebates, lugs, and brackets necessary to assemble components and to attach to existing work. Drill and tap for required fasteners. Use concealed fasteners where possible; use exposed fasteners that match sign finish. B. Surface -Engraved Graphics: Machine engrave characters and other graphic devices into panel surface indicated to produce precisely formed copy, incised to uniform depth. 1. Engraved Metal: Fill engraved graphics with manufacturer's standard baked enamel. 2. Engraved Opaque Acrylic Sheet: Fill engraved graphics with manufacturer's standard enamel. 3. Face -Engraved Clear Acrylic Sheet: Fill engraved copy with manufacturer's standard enamel. Apply manufacturer's standard opaque background color coating to back face of acrylic sheet. 4. Engraved Plastic Laminate- Engrave through exposed face ply of plastic -laminate sheet to expose contrasting core ply. 2.6 GENERAL FINISH REQUIREMENTS A. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping PANEL SIGNAGE 101423 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER100% CONSTRUCTION DOCUMENTS B. Appearance of Finished Work: Noticeable variations in same piece are not acceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast. C. Directional Finishes: Run grain with long dimension of each piece and perpendicular to long dimension of finished trim or border surface unless otherwise indicated. D. Organic, Anodic, and Chemically Produced Finishes: Apply to formed metal after fabrication but before applying contrasting polished finishes on raised features unless otherwise indicated. 2.7 ALUMINUM FINISHES A. Clear Anodic Finish: AAMA 611, [Class I, 0.018 mm] [Class II, 0.010 mm] or thicker. B. Color Anodic Finish: AAMA 611, [Class I, 0.018 mm] [Class II, 0.010 mm] or thicker. C. Baked -Enamel or Powder -Coat Finish: AAMA 2603 except with a minimum dry film thickness of 1.5 mils (0.04 mm). Comply with coating manufacturer's written instructions for cleaning, conversion coating, and applying and baking finish. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of signage work. B. Verify that sign -support surfaces are within tolerances to accommodate signs without gaps or irregularities between backs of signs and support surfaces unless otherwise indicated. C. Verify that anchor inserts are correctly sized and located to accommodate signs. D. Verify that electrical service is correctly sized and located to accommodate signs. E. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. General: Install signs using mounting methods indicated and according to manufacturer's written instructions. 1. Install signs level, plumb, true to line, and at locations and heights indicated, with sign surfaces free of distortion and other defects in appearance. 2. Install signs so they do not protrude or obstruct according to the accessibility standard. 3. Before installation, verify that sign surfaces are clean and free of materials or debris that would impair installation. PANEL SIGNAGE 101423 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER100% CONSTRUCTION DOCUMENTS 4. Corrosion Protection: Coat concealed surfaces of exterior aluminum in contact with grout, concrete, masonry, wood, or dissimilar metals, with a heavy coat of bituminous paint. 3.3 ADJUSTING AND CLEANING A. Remove and replace damaged or deformed signs and signs that do not comply with specified requirements. Replace signs with damaged or deteriorated finishes or components that cannot be successfully repaired by finish touchup or similar minor repair procedures. B. Remove temporary protective coverings and strippable films as signs are installed. C. On completion of installation, clean exposed surfaces of signs according to manufacturer's written instructions, and touch up minor nicks and abrasions in fmish. Maintain signs in a clean condition during construction and protect from damage until acceptance by Owner. END OF SECTION 101423 PANEL SIGNAGE 101423 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 10 21 13 - PLASTIC TOILET COMPARTMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Solid -plastic toilet compartments configured as toilet enclosures, entrance screens and urinal screens. B. Related Requirements: 1. Section 06 10 00 "Rough Carpentry" for overhead support of floor -and -ceiling -anchored compartments. 2. Section 10 28 00 "Toilet and Bath Accessories" for toilet tissue dispensers, grab bars, sanitary napkin disposals, and similar accessories mounted on toilet compartments. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. 1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for toilet compartments. B. Shop Drawings: For toilet compaiAuents. 1. Include plans, elevations, sections, details, and attachment details. 2. Show locations of cutouts for compartment -mounted toilet accessories. 3. Show locations of centerlines of toilet fixtures. 4. Show locations of floor drains. 5. Show floor and ceiling -mounted items, as well as overhead support or bracing locations. C. Samples for Initial Selection: For each type of toilet compartment material indicated. 1. Include Samples of hardware and accessories involving material and color selection. D. Samples for Verification: For the following products, in manufacturer's standard sizes unless otherwise indicated: 1. Each type of material, color, and finish required for toilet compartments, prepared on 6- inch- (152 -mm-) square Samples of same thickness and material indicated for Work. PLASTIC TOILET COMPARTMENTS 10 21 13 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Each type of hardware and accessory. E. Product Schedule: For toilet compartments, prepared by or under the supervision of supplier, detailing location and selected colors for toilet compartment material. 1.4 INFORMATIONAL SUBMITTALS A. Product Certificates: For each type of toilet compartment. 1.5 CLOSEOUT SUBMITTALS A. Maintenance Data: For toilet compaitments to include in maintenance manuals. 1.6 MAINTENANCE MATERIAL SUBMITTALS A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents and source. 1. Door Hinges: One hinge with associated fasteners. 2. Latch and Keeper: One latch and keeper(s) with associated fasteners. 3. Door Bumper: One bumper with associated fasteners. 4. Door Pull: One door pull with associated fasteners. 5. Fasteners: Ten fasteners of each size and type. 1.7 PROJECT CONDITIONS A. Field Measurements: Verify actual locations of toilet fixtures, walls, columns, ceilings, and other construction contiguous with toilet compartments by field measurements before fabrication. PART 2 - PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Surface -Burning Characteristics: Comply with NFPA 286; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. Independent testing might be required. 2.2 SOLID -PLASTIC TOILET COMPARTMENTS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: PLASTIC TOILET COMPARTMENTS 10 21 13 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Accurate Partitions Corporation. 2. American Sanitary Partition Corporation. 3. Ampco, Inc. 4. Bradley Corporation; Mills Partitions. 5. General Partitions Mfg. Corp. 6. Global Steel Products Corp. 7. Hadrian Manufacturing Inc. 8. Knickerbocker Partition Corporation. 9. Metpar Corp. 10. Partition Systems Incorporated of' South Carolina; Columbia Partitions. 11. Scranton Products. B. Toilet -Enclosure Style: Floor to ceiling anchored. C. Entrance -Screen Style: Floor to ceiling anchored. D. Urinal -Screen Style: Floor to ceiling anchored. E. Door, Panel, Screen, and Pilaster Construction: Solid, high-density polyethylene (HDPE) panel material, not less than 1 inch thick, seamless, with eased edges and with homogenous color and pattern throughout thickness of material. 1. Integral Stealth Hinges: Configure doors and pilasters to receive integral hinges. 2. Color and Pattern: as selected by Architect from manufacturer's full range. F. Pilaster Shoes and Sleeves (Caps): Manufacturer's standard design; plastic shoes at floor location and stainless steel sleeves at ceiling location. G. Urinal -Screen Post: Manufacturer's standard post design of material matching the thickness and construction of pilasters; with shoe and sleeve as stated above. H. Brackets (Fittings): 1. Stirrup Type: Ear or U -brackets, plastic construction. 2.3 HARDWARE AND ACCESSORIES A. Hardware and Accessories: Manufacturer's heavy-duty operating hardware and accessories. 1. Hinges: Manufacturer's standard paired, self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees, allowing emergency access by lifting door. Mount with through -bolts. 2. Latch and Keeper: Manufacturer's heavy-duty surface -mounted aluminum latch unit designed to resist damage due to slamming, with combination rubber -faced door strike and keeper, and with provision for emergency access. Provide units that comply with regulatory requirements for accessibility at compartments designated as accessible. Mount with through -bolts. 3. Coat Hook: Manufacturer's standard hook and rubber -tipped bumper, sized to prevent in - swinging door from hitting compartment -mounted accessories. Mount with through -bolts. PLASTIC TOILET COMPARTMENTS 10 21 13 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 4. Door Bumper: Manufacturer's standard heavy-duty rubber -tipped bumper at out -swinging doors and entrance -screen doors. Mount with through -bolts. 5. Door Pull: Manufacturer's standard heavy-duty pull at out -swinging doors that complies with regulatory requirements for accessibility. Provide units on both sides of doors at compartments designated as accessible. Mount with through -bolts. B. Overhead Bracing: If required manufacturer's standard continuous, extruded -aluminum head rail with antigrip profile and in manufacturer's standard finish. C. Anchorages and Fasteners: Manufacturer's standard exposed fasteners of stainless steel, finished to match the items they are securing, with theft -resistant -type heads. Provide security torx head bolts for through -bolt applications. For concealed anchors, use plastic anchors. D. Aluminum Extrusions: ASTM 64663-T5 alloy. E. Stainless -Steel Sheet: ASTM A 666, Type 304, stretcher -leveled standard of flatness. 2.4 FABRICATION A. Fabrication, General: Fabricate toilet compartment components to sizes indicated. Coordinate requirements and provide cutouts for through -partition toilet accessories where required for attachment of toilet accessories. B. Floor -and -Ceiling -Anchored Units: Provide manufacturer's standard corrosion -resistant anchoring assemblies with leveling adjustment nuts at tops and bottoms of pilasters. Provide shoes and sleeves as specified. C. Urinal -Screen Posts: Provide manufacturer's standard corrosion -resistant anchoring assemblies with leveling adjustment nuts at tops and bottoms of posts. Provide shoes and sleeves as specified. D. Door Size and Swings: Unless otherwise indicated, provide 24 -inch wide, in -swinging doors for standard toilet compartments and 36 -inch wide, out -swinging doors with a minimum 32 -inch - wide, clear opening for compartments designated as accessible. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine areas and conditions, with Installer present, for compliance with requirements for fastening, support, alignment, operating clearances, and other conditions affecting performance of the Work. 1. Confirm location and adequacy of blocking and supports required for installation. B. Proceed with installation only after unsatisfactory conditions have been corrected. PLASTIC TOILET COMPARTMENTS 10 21 13 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.2 INSTALLATION A. General: Comply with manufacturer's written installation instructions. Install units rigid, straight, level, and plumb. Secure units in position with manufacturer's recommended anchoring devices. Installer shall have five years experience. 1. Maximum Clearances: a. Pilasters and Panels: 1/2 inch (13 mm). b. Panels and Walls: 1 inch (25 mm). 2. Full -Height (Continuous) Brackets: Secure panels to walls and to pilasters with full - height brackets. a. Locate bracket fasteners so holes for wall anchors occur in masonry or tile joints if possible. b. Align brackets at pilasters with brackets at walls. B. Floor -and -Ceiling -Anchored Units: Secure pilasters to supporting construction and level, plumb, and tighten. Hang doors and adjust so doors are level and aligned with panels when doors are in closed position. C. Urinal Screens: Attach with anchoring devices to suit supporting structure. Set units level and plumb, rigid, and secured to resist lateral impact. 3.3 ADJUSTING A. Hardware Adjustment: Adjust and lubricate hardware according to hardware manufacturer's written instructions for proper operation. Set hinges on in -swinging doors to hold doors open approximately 30 degrees from closed position when unlatched. Set hinges on out -swinging doors return doors to fully closed position. END OF SECTION 10 21 13 PLASTIC TOILET COMPARTMENTS 10 21 13 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 102113 - TOILET COMPARTMENTS PART 1 GENERAL 1.1 SECTION INCLUDES A. Solid Color Reinforced Composite (SCRC) Substrate: (Bobrick SierraSeries®) 1. Toilet Partitions: a. Configuration: Ceiling -Hung. 2. Urinal Privacy Screens: a. Configuration: Wall -Hung. 1.2 RELATED REQUIREMENTS A. Section 055000 - Metal Fabrications, coordination with overhead supports; steel beams above finished ceiling to secure Ceiling -Hung and floor -to -ceiling stiles. B. Section 061000 - Rough Carpentry, coordination with blocking in walls to secure panels, wall posts and stiles. C. Section 095000 - Ceilings, coordination with layout and installation. D. Section 092000 - Plaster and Gypsum Board, coordination with blocking. E. Section 093000 - Tiling, coordination with layout and installation. F. Section 102800 - Washroom Accessories, for accessories. G. Section 102814 - Baby Changing Stations, for baby changing stations. 1.3 SUBMITTALS A. Product Data: Submit manufacturer's data sheets for each product specified. B. Shop Drawings: Submit manufacturer's shop drawings for each product specified, including the following: 1. Plans, elevations, details of construction and attachment to adjacent construction. 2. Show anchorage locations and accessory items. 3. Verify dimensions with field measurements prior to fmal production of toilet compartments. TOILET COMPARTMENTS 102113-1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.4 QUALITY ASSURANCE A. Manufacturer: Provide products manufactured by a company with a minimum of 10 years successful experience manufacturing similar products. B. Single Source Requirements: To the greatest extent possible provide products from a single manufacturer. C. Accessibility Requirements: Comply with requirements applicable in the jurisdiction of the project, including but not limited to ADA and ICC/ANSI A117.1 requirements as applicable. 1.5 DELIVERY, STORAGE, AND HANDLING A. Deliver, store and handle materials and products in strict compliance with manufacturer's instructions and recommendations. Protect from damage. 1.6 WARRANTY A. Manufacturer's Warranty (SierraSeries): Manufacturer's standard 25 year limited warranty for panels, doors, and stiles against breakage, corrosion, and defects in factory workmanship. Manufacturer's standard 1 year guarantee against defects in material and workmanship for stainless steel door hardware and mounting brackets. PART 2 PRODUCTS 2.1 MANUFACTURER A. Basis -of -Design Products: Based on the quality and performance requirements of the project, specifications are based solely on the products of Bobrick Washroom Equipment, Inc.. www.bobrick.com. Location of manufacturing shall be the United States. B. Substitutions: The Architect will consider products of comparable manufacturers as a substitution, pending the contractor's submission of adequate documentation of the substitution in accordance with procedures in Division 1 of the Project Manual. Documentation shall include a list of five similar projects of equivalent size where products have been installed for a minimum of two years, and manufacturer's certification that products are fabricated in the United States. 2.2 SOLID COLOR REINFORCED COMPOSITE (SCRC) SUBSTRATE (SierraSeries) A. Solid Color Reinforced Composite (SCRC) Partitions: Bobrick SierraSeries. 1. Color: As indicated on Drawings. B. Toilet Partitions: TOILET COMPARTMENTS 102113-2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Configuration: Ceiling -Hung partitions, 10 ft (3048 mm) maximum ceiling height. a. Basis -of -Design: Bobrick 1098G SierraSeries Toilet Partitions, gap -free. 1) Design: Gap -free interlocking design. 2) Hardware: Standard hardware. 2. Fire Resistance: a. Flame Spread Index (ASTM E 84): 45 for panels, doors and stiles. b. Smoke Developed Index (ASTM E 84): 120 for panels, 95 for doors and stiles. c. National Fire Protection Association/International Building Code Interior Wall and Ceiling Finish: Class B. d. Uniform Building Code: Class II. C. Urinal Privacy Screens: 1. Basis -of -Design: Bobrick 1095 SierraSeries Wall -Hung Urinal Privacy Screens. a. Brackets: 11 gauge (3 mm), double thickness. 2. Hardware: To match partition hardware. 3. Fire Resistance: a. Flame Spread Index (ASTM E 84): 45 for panels and stiles. b. Smoke Developed Index (ASTM E 84): 120 for panels, 95 for stiles. c. National Fire Protection Association/International Building Code Interior Wall and Ceiling Finish: Class B. d. Uniform Building Code: Class 11. D. Materials: Solid color reinforced composite (SCRC) material for stiles, panels, doors, and screens with Bobrick GraffitiOfl coating, thermoset and integrally fused into homogenous piece; high density polyethylene (HDPE), high density polypropylene not acceptable. 1. Composition: Dyes, organic fibrous material, and polycarbonate/phenolic resins. 2. Surface Treatment: Non -ghosting, graffiti resistant surface integrally bonded to core through a series of manufacturing steps requiring thermal and mechanical pressure. 3. Edges: Same color as the surface. 4. Acceptable SCRC Products: Or manufacturer approved equal. a. Ultimate Corian System by Shower Shapes. b. WilsonArt Gibraltar Material. c. WilsonArt EarthStone Material. E. Performance Requirements: 1. Graffiti Resistance (ASTM D 6578): Passed cleanability test; 5 staining agents. 2. Scratch Resistance (ASTM D 2197): Maximum load value exceeds 10 kilograms. 3. Impact Resistance (ASTM D 2794): Maximum impact force exceeds 30 inch -pounds. 4. Smoke Developed Index (ASTM E 84): Less than 450. 5. Flame Spread Index (ASTM E 84): Less than 75. TOILET COMPARTMENTS 102113-3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS F. Finished Thickness: 1. Stiles and Doors: 3/4 inch (19 mm) a. Finished thickness of doors and stiles to ensure flush front. 2. Panels and Screens: 1/2 inch (13 mm). G. Wall Posts: Pre -drilled for door hardware, 18-8, Type 304, 16 gauge (1.6 mm) stainless steel with satin fmish; 1 inch (25 mm) x 1-1/2 inches (38 mm) x 58 inches high (1473 mm). H. Anchors: Expansion shields and threaded rods at floor connections as applicable. Threaded rods secured to supports above ceiling as applicable. Supports above ceiling furnished and installed as Work of Section 055000. I. Hardware: 1. Compliance: Operable with one hand, without tight grasping, pinching, or twisting of the wrist, and force to operate does not exceed five pounds. 2. Emergency Access: Hinges, latch allow door to be lifted over keeper from outside compartment on inswing doors. 3. Materials: 18-8, Type 304, heavy -gauge stainless steel with satin finish. Chrome -plated "Zamak", aluminum, or extruded plastic hardware not acceptable. 4. Fastening: Hardware secured to door and stile by through -bolted, theft -resistant, pin -in - head Torx stainless steel machine screws into factory -installed, threaded brass inserts. Fasteners secured directly into core not acceptable. a. Threaded Brass Inserts: Factory -installed; withstand direct pull force exceeding 1500 lb (680 kg) per insert. 5. Clothes Hooks: Projecting no more than 1-1/8 inch (29 mm) from face of door. 6. Hardware Type: Standard, commercial hardware. a. Latching: Track of door latch prevents inswing doors from swinging out beyond stile; on outswing doors, door keeper prevents door from swinging in beyond stile; 14 gauge (2 mm) sliding door latch, 11 gauge (3.2 nun) keeper. Twist -style door latch operation not acceptable. b. Hinges: Balanced, with field -adjustable cam to permit door to be fully closed or partially open when compartment is unoccupied. c. Locking: Door locked from inside by sliding door latch into keeper. d. Mounting Brackets: Mounted inside compartment; exposed brackets on exterior of compartment not acceptable with the exception of outswing doors. 7. Hardware Type: Institutional Hardware (.67). a. Latching: 14 gauge (2 mm) sliding door latch, 11 gauge (3.2 mm) keeper; latch slides on a shock -resistant nylon track. Twist -style door latch operation not acceptable. b. Hinges: 16 gauge (1.6 mm) stainless steel, self-closing, 3 section hinges. TOILET COMPARTMENTS 102113-4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS c. Mounting Brackets: 18 gauge (1.2 mm) stainless steel and extend full height of panel. 1) U -Channels: Secure panels to stiles. 2) Angle Brackets: Secure stiles -to -walls and panels -to -walls. PART 3 EXECUTION 3.1 PREPARATION A. Prepare substrates including but not limited to blocking and supports in walls and ceilings at points of attachment using methods recommended by the manufacturer for achieving the best result for the substrates under the project conditions. 1. Inspect areas scheduled to receive compartments for correct dimensions, plumbness of walls, and soundness of surfaces that would affect installation of mounting brackets. 2. Verify spacing of plumbing fixtures to assure compatibility with installation of compartments. B. If preparation is the responsibility of another installer, notify Architect in writing of deviations from manufacturer's recommended installation tolerances and conditions. C. Do not proceed with installation until substrates have been properly prepared with blocking and supports in walls and ceilings at points of attachment and deviations from manufacturer's recommended tolerances are corrected. Commencement of installation constitutes acceptance of conditions. 3.2 INSTALLATION A. Install products in strict compliance with manufacturer's written instructions and recommendations, including the following: 1. Verify blocking and supports in walls and ceilings have been installed properly at points of attachment. 2. Verify location does not interfere with door swings or use of fixtures. 3. Use fasteners and anchors suitable for substrate and project conditions 4. Install units rigid, straight, plumb, and level. 5. Conceal evidence of drilling, cutting, and fitting to room finish. 6. Test for proper operation. 3.3 ADJUSTING, CLEANING AND PROTECTION A. Adjust hardware for proper operation after installation. Set hinge cam on in -swinging doors to hold doors open when unlatched. Set hinge cam on out -swinging doors to hold unlatched doors in closed position. TOILET COMPARTMENTS 102113-5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Touch-up, repair or replace damaged products. C. Clean exposed surfaces of compartments, hardware, and fittings. END OF SECTION 102113 TOILET COMPARTMENTS 102113-6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 102239 - FOLDING GLASS -PANEL PARTITIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes manually operated, glass -panel partitions. B. Related Requirements: 1. Section 055000 "Metal Fabrications" for supports that attach supporting tracks to overhead structural system. 1.3 DEFINITIONS A. STC: Sound Transmission Class. 1.4 PREINSTALLATION MEETINGS A. Preinstallation Conference: Conduct conference at Project site . 1.5 ACTION SUBMITTALS A. Product Data: For each type of product. B. Shop Drawings: For operable glass -panel partitions. 1. Include plans, elevations, sections, details, numbered panel installation sequence, and attachments to other work. 2. Indicate stacking and operating clearances. Indicate location and installation requirements for hardware and track, blocking, and direction of travel. C. Samples for Initial Selection: For each type of exposed material, finish, covering, or facing. 1. Include Samples of accessories involving color selection. D. Samples for Verification: For each type of exposed material, finish, covering, or facing, prepared on Samples of size indicated below: I. Panel Edge Material: Not less than 3 inches (75 nun) long. FOLDING GLASS -PANEL PARTITIONS 102239.13 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Glass: Units 12 inches (300 mm) square. 3. Hardware: One of each exposed door -operating device. E. Delegated -Design Submittal: For operable glass -panel partitions. 1. Include design calculations for seismic restraints. 1.6 INFORMATIONAL SUBMITTALS A. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved: 1. Partition track, track supports and bracing, switches, turning space, and storage layout. 2. Suspended ceiling components. 3. Structural members to which suspension systems are attached. 4. Size and location of initial access modules for acoustical tile. 5. Items penetrating finished ceiling, including the following: a. Lighting fixtures. b. HVAC ductwork, outlets, and inlets. c. Speakers. d. Sprinklers. e. Smoke detectors. f. Access panels. B. Qualification Data: For qualified Installermanufacturerandvendor. C. Product Certificates: For each type of operable glass -panel partition. D. Product Test Reports: For each operable glass -panel partition, for tests performed by a qualified testing agency. E. Sample Warranty: For manufacturer's special warranty. 1.7 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For operable glass -panel partitions to include in maintenance manuals. 1. In addition to items specified in Section 017823 "Operation and Maintenance Data," include the following: a. Panel fmish and finishes for exposed trim and accessories. Include precautions for cleaning materials and methods that could be detrimental to finishes and performance. b. Seals, hardware, track, track switches, carriers, and other operating components. FOLDING GLASS -PANEL PARTITIONS 102239.13 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.8 QUALITY ASSURANCE A. Manufacturer Qualifications: A qualified manufacturer that is certified for chain of custody by an FSC -accredited certification body. B. Vendor Qualifications: A vendor that is certified for chain of custody by an FSC -accredited certification body. C. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer. 1.9 DELIVERY, STORAGE, AND HANDLING A. Protectively package and sequence panels in order for installation. Clearly mark packages and panels with numbering system used on Shop Drawings. Do not use permanent markings on panels. 1.10 WARRANTY A. Special Warranty: Manufacturer agrees to repair or replace components of operable glass -panel partitions that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Faulty operation of operable glass -panel partitions. b. Deterioration of metals, metal finishes, and other materials beyond normal use. 2. Warranty Period: Two years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 "Quality Requirements," to design seismic bracing of tracks to structure above. B. Acoustical Performance: Provide operable glass -panel partitions tested by a qualified testing agency for the following acoustical properties according to test methods indicated: 1. Sound -Transmission Requirements: Operable glass -panel partition assembly tested for laboratory sound -transmission loss performance according to ASTM E 90, determined by ASTM E 413, and rated for not less than the STC indicated. C. Fire -Test -Response Characteristics: Provide wood -framed panels complying with one of the following as determined by testing identical products by UL or another testing and inspecting agency acceptable to authorities having jurisdiction: FOLDING GLASS -PANEL PARTITIONS 102239.13 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Surface -Burning Characteristics: Comply with ASTM E 84 or UL 723; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. a. Flame -Spread Index: [25] [75] <Insert value> or less. b. Smoke -Developed Index: [450] <Insert value> or less. 2.2 OPERABLE GLASS PANELS A. Operable Glass Panels: Aluminum-framedglass-panel partition system, including panels, [seals, ]suspension system, operators, and accessories. 1. Basis -of -Design Product: Subject to compliance with requirements, NanaWall Systemsor comparable product by one of the following: a. Hufcor Inc. b. KW1K-WAi,I, Company. c. Moderco Inc. d. N'[odernfold Inc .• a DORMA Grou co B. Panel Operation: Manually operated, continuously hinged panels. C. Panel Construction: As required to support panel from suspension components and with reinforcement for hardware attachment. Fabricate panels with tight hairline joints and concealed fasteners. Fabricate panels so finished in-place partition is rigid; level; plumb; aligned, with tight joints and uniform appearance; and free of bow, warp, twist, deformation, and surface and finish irregularities. 1. Factory -Glazed Fabrication: Glaze operable glass panels in the factory where practical and possible for applications indicated. Comply with manufacturer's written instructions and with requirements in Section 088000 "Glazing." D. Glass and Glazing: Glass type <Insert description as specified in Section 088000 "Glazing." E. Glass and Glazing: As follows: 1. Safety Glass Standard for Partition Panels: Provide glass products complying with testing requirements in 16 CFR 1201, Category II, or ANSI Z97.1, Class A. F. Dimensions: Fabricate operable glass -panel partitions to form an assembled system of dimensions indicated and verified by field measurements. 1. Panel Width: Equal widths. G. STC: Not less than 36 . H. 3 inches (76 min. I. Panel Frame Materials: FOLDING GLASS -PANEL PARTITIONS 102239.13 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Aluminum: Alloy and temper recommended by aluminum producer and finisher for type of use, corrosion resistance, and finish indicated; ASTM B 221 (ASTM B 221M) for extrusions; manufacturer's standard strengths and thicknesses for type of use. a. Frame Reinforcement: Manufacturer's standard steel or aluminum. J. Panel Closure:[Manufacturer's standard unless otherwise indicate]. K. Hardware: Manufacturer's standard as required to operate operable glass -panel partition and accessories; with decorative, protective finish. 1. Hinges: Manufacturer's standard . L. Panel Frame Finishes: 1. Exposed MetalAs selected by Architect from manufacturer's full rangeas follows: 2.3 SEALS A. General: Provide seals that produce operable glass -panel partitions complying with performance requirements and the following: 1. Manufacturer's standard seals unless otherwise indicated. 2. Seals made from materials and in profiles that minimize sound leakage. 3. Seals fitting tight at contact surfaces and sealing continuously between adjacent panels and between operable glass -panel partition perimeter and adjacent surfaces, when operable glass -panel partition is extended and closed. 2.4 SUSPENSION SYSTEMS A. Tracks: Steel or aluminum designed for operation, size, and weight of operable glass -panel partition indicated. Size track to support partition operation and storage without damage to suspension system, operable glass -panel partitions, or adjacent construction. Limit track deflection to no more than 0.10 inch (2.54 mm) between bracket supports. Provide a continuous system of track sections and accessories to accommodate configuration and layout indicated for partition operation and storage. 1. Panel Guide: Aluminum guide on both sides of the track to facilitate straightening of the panels; finished with factory -applied, decorative, protective finish. 2. Head Closure Trim: As required for acoustical performance; with factory -applied, decorative, protective finish. B. Carriers: Trolley system as required for configuration type, size, and weight of partition and for easy operation; with ball-bearing wheels. 1. Multidirectional Carriers: Capable of negotiating intersections without track switches. C. Track Intersections, Switches, and Accessories: As required for operation, storage, track configuration, and layout indicated for operable glass -panel partitions, and compatible with partition assembly specified. Fabricate track intersections and switches from steel or aluminum. FOLDING GLASS -PANEL PARTITIONS 102239.13 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 1.00% CONSTRUCTION DOCUMENTS 1. Curve-and-Diverter Switches: Allow radius turns to divert panels to an auxiliary track. 2. L Intersections: Allow panels to change 90 degrees in direction of travel. 3. T Intersections: Allow panels to pass through or change 90 degrees to another direction of travel. 4. X Intersections: Allow panels to pass through or change travel direction full circle in 90 - degree increments, and allow one partition to cross track of another. 5. Multidirectional Switches: Adjustable switch configuring track into L, T, or X intersections and allowing panels to be moved in all pass-through, 90 -degree change, and cross-over travel direction combinations. 6. Center carrier stop. D. Aluminum Finish: Mill finish or manufacturer's standard, factory -applied, decorative finish unless otherwise indicated. E. Steel Finish: Manufacturer's standard, factory -applied, corrosion -resistant, protective coating unless otherwise indicated. 2.5 ACCESSORIES a. B. Vertical Edge Trim: Manufacturer's standard thin aluminum astragal trim to protect vertical edges of glass in frameless panels. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine flooring, structural support, and opening, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of operable glass -panel partitions. B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. General: Comply with ASTM E 557 except as otherwise required by operable glass -panel partition manufacturer's written installation instructions. B. Install operable glass -panel partitions and accessories after other finishing operations, including painting, have been completed in area of partition installation. C. Install panels from marked packages in numbered sequence indicated on Shop Drawings. D. Broken, cracked, chipped, deformed, or unmatched panels are not acceptable. E. Broken, cracked, deformed, or unmatched gasketing or gasketing with gaps at butted ends is not acceptable. FOLDING GLASS -PANEL PARTITIONS 102239.13 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS F. Light -Leakage Test: Illuminate one side of partition installation and observe vertical joints and top and bottom seals for voids. Adjust partitions for alignment and full closure of vertical joints and full closure along top and bottom seals. 3.3 ADJUSTING A. Adjust operable glass -panel partitions, hardware, and other moving parts to function smoothly, and lubricate as recommended by manufacturer. B. Adjust [pass doors] [and] [storage pocket doors] to operate smoothly and easily, without binding or warping. C. Verify that safety devices are properly functioning. 3.4 MAINTENANCE SERVICE A. Maintenance Service: Beginning at Substantial Completion, maintenance service shall include 12 months' full maintenance by manufacturer's authorized service representative. Include quarterly preventive maintenance, repair or replacement of worn or defective components, lubrication, cleaning, and adjusting as required for proper operable -partition operation. Parts and supplies shall be manufacturer's authorized replacement parts and supplies. 3.5 DEMONSTRATION A. Engage a factory -authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain operable glass -panel partitions. END OF SECTION 102239.13 FOLDING GLASS -PANEL PARTITIONS 102239.13 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 10 28 00 — TOILET AND BATH ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Public -use washroom accessories. 2. Warm -air dryers. 3. Childcare accessories. 4. Underlavatory guards. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. Include the following: 1. Construction details and dimensions. 2. Anchoring and mounting requirements, including requirements for cutouts in other work and substrate preparation. 3. Material and finish descriptions. 4. Features that will be included for Project. 5. Manufacturer's warranty. B. Samples: Full size, for each accessory item to verify design, operation, and finish requirements. 1. Approved full-size Samples will be returned and may be used in the Work. C. Product Schedule: Indicating types, quantities, sizes, and installation locations by room of each accessory required. 1. Identify locations using room designations indicated. 2. Identify products using designations indicated. 1.4 INFORMATIONAL SUBMITTALS A. Warranty: Sample of special warranty. TOILET AND BATH ACCESSORIES 10 28 00 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.5 CLOSEOUT SUBMITTALS A. Maintenance Data: For toilet and bath accessories to include in maintenance manuals. 1.6 QUALITY ASSURANCE A. Source Limitations: For products listed together in the same Part 2 articles, obtain products from single source from single manufacturer. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 1.7 COORDINATION A. Coordinate accessory locations with other work to prevent interference with clearances required for access by people with disabilities, and for proper installation, adjustment, operation, cleaning, and servicing of accessories. B. Deliver inserts and anchoring devices set into concrete or masonry as required to prevent delaying the Work. 1.8 WARRANTY A. Special Mirror Warranty: Manufacturer's standard form in which manufacturer agrees to replace mirrors that develop visible silver spoilage defects and that fail in materials or workmanship within specified warranty period. 1. Warranty Period: 15 years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 MATERIALS A. Stainless Steel: ASTM A 666, Type 304, 0.031 -inch (0.8 -mm) minimum nominal thickness unless otherwise indicated. B. Brass: ASTM B 19, flat products; ASTM B 16B 16M, rods, shapes, forgings, and flat products with finished edges; or ASTM B 30, castings. C. Steel Sheet: ASTM A 1008/A 1008M, Designation CS (cold rolled, commercial steel), 0.036 - inch (0.9 -mm) minimum nominal thickness. D. Galvanized -Steel Sheet: ASTM A 653/A 653M, with G60 (Z180) hot -dip zinc coating. E. Galvanized -Steel Mounting Devices: ASTM A 153/A 153M, hot -dip galvanized after fabrication. TOILET AND BATH ACCESSORIES 10 28 00 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS F. Fasteners: Screws, bolts, and other devices of same material as accessory unit and tamper -and - theft resistant where exposed, and of galvanized steel where concealed. G. Chrome Plating: ASTM B 456, Service Condition Number SC 2 (moderate service). H. Mirrors: ASTM C 1503, Mirror Glazing Quality, clear -glass mirrors, nominal 6.0 mm thick. I. ABS Plastic: Acrylonitrile -butadiene -styrene resin formulation. 2.2 PUBLIC -USE WASHROOM ACCESSORIES A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. A & J Washroom Accessories Inc. 2. American Specialties, Inc. 3. Bobrick Washroom Equipment, Inc. 4. Bradley Corporation. 5. GAMCO Specialty Accessories; a division of Bobrick Washroom Equipment, Inc. 6. Tubular Specialties Manufacturing Inc. A. Surface Mounted Toilet Tissue Dispenser: 1. Basis -of -Design Product: Basis -of -Design Product: Bobrick Double -Roll Toilet Tissue Dispenser with Controlled Delivery (B-2764) with satin finish. B. Liquid -Soap Dispenser: 1. Basis -of -Design Product: Bobrick B-4112 ConturaSeries Surface Mounted Soap Dispenser. C. Grab Bars: 1. Basis -of -Design Product: Bradley Model 832 2. Mounting: Flanges with concealed fasteners. 3. Material: Stainless steel, minimum 0.05 inch thick. a. Finish: Smooth, No. 4, satin finish. 4. Outside Diameter: 1-1/4 inches. D. Configuration and Length: Straight, in nominal lengths of 36 inches long at rear of water closet and 42 -inches long at side walls, 24" vertical side bar in shower, L -Shaped grab bar in shower enclosure with actual gripping surface lengths in accordance with Florida Accessibility Code E. Sanitary -Napkin Disposal Unit: 1. Basis -of -Design Product: Bradley Model No. 4731-15. 2. Mounting: Recessed mounted. 3. Door or Cover: Self-closing disposal -opening cover. TOILET AND BATH ACCESSORIES 10 28 00 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 4. Receptacle: Removable 22 gauge stainless steel. 5. Material and Finish: Stainless steel, No. 4 finish (satin). F. Semi-Recessed/Recessed Waste Receptacle: 1. Basis -of -Design Product: Bobrick Model B-3644 or similar. 2. Mounting: Recessed mounted or Semi -recessed 3. Material: Stainless steel, 22-guage a. Finish: Stainless Steel, No. 4 satin fmish G. Mirror Unit: 1. Basis -of -Design Product: Bradley Model 780-1836 2. Frame: Stainless-steel angle, 0.05 inch thick. a. Corners: Welded and ground smooth. 3. Hangers: Produce rigid, tamper- and theft -resistant installation, using method indicated below. a. One-piece, galvanized steel, wall -hanger device with spring -action locking mechanism to hold mirror unit in position with no exposed screws or bolts. 4. Size: 30 -inches high and 18 -inches wide and 60 -inches high and 24 -inches wide as located on drawings. 2.3 WARM -AIR DRYERS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. A & J Washroom Accessories, Inc. 2. American Dryer, Inc. 3. American Specialties, Inc. 4. Bobrick Washroom Equipment, Inc. 5. Bradley Corporation. 6. Dyson Corporation. 7. Excel Dryer Corporation. 8. GAMCO Specialty Accessories; a division of Bobrick Washroom Equipment, Inc. 9. Tubular Specialties Manufacturing, Inc. 10. World Dryer Corporation. B. Warm -Air Dryer: 1. Basis -of -Design Product: Subject to compliance provide Dyson Airblade dB or comparable. 2. Mounting: Surface mounted. 3. Operation: Electronic -sensor activated with timed power cut-off switch. TOILET AND BATH ACCESSORIES 10 28 00 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Operation Time: 30 to 40(s)> seconds. 4. Cover Material and Finish: finish in color selected by Architect 2.4 UNDERLAVATORY GUARDS A. Basis -of -Design Product: The design for accessories is based on products indicated. Subject to compliance with requirements, provide the named product or a comparable product by one of the following: 1. Plumberex Specialty Products, Inc. 2. TCI Products. 3. Truebro, Inc. B. Underlavatory Guard: 1. Basis -of -Design Product: Truebro "Lav Shield." 2. Description: Insulating pipe covering for supply and drain piping assemblies that prevent direct contact with and burns from piping, and allow service access without removing coverings. 3. Material and Finish: Antimicrobial, molded -plastic, white. 2.5 FABRICATION A. General: Fabricate units with tight seams and joints, and exposed edges rolled. Hang doors and access panels with full-length, continuous hinges. Equip units for concealed anchorage and with corrosion -resistant backing plates. B. Keys: Provide universal keys for internal access to accessories for servicing and resupplying. Provide minimum of ten keys to Owner's representative. PART 3 - EXECUTION 3.1 INSTALLATION A. Install accessories according to manufacturers' written instructions, using fasteners appropriate to substrate indicated and recommended by unit manufacturer. Install units level, plumb, and firmly anchored in locations and at heights indicated. B. Grab Bars: Install to withstand a downward load of at least 250 lbf (1112 N), when tested according to ASTM F 446. 3.2 ADJUSTING AND CLEANING A. Adjust accessories for unencumbered, smooth operation. Replace damaged or defective items. B. Remove temporary labels and protective coatings. TOILET AND BATH ACCESSORIES 10 28 00 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Clean and polish exposed surfaces according to manufacturer's written recommendations. END OF SECTION 10 28 00 TOILET AND BATH ACCESSORIES 10 28 00 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 10 44 13 - FIRE PROTECTION CABINETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Fire -protection cabinets for the following: a. Portable fire extinguishers. B. Related Requirements: 1. Section 10 44 16 "Fire Extinguishers." 1.3 PREINSTALLATION CONFERENCE A. Preinstallation Conference: Conduct conference at Project site. 1. Review methods and procedures related to fire -protection cabinets including, but not limited to, the following: a. Schedules and coordination requirements. 1.4 ACTION SUBMITTALS A. Product Data: For each type of product. Show door hardware, cabinet type, trim style, and panel style. Include roughing -in dimensions and details showing recessed-, semi recessed-, or surface - mounting method and relationships of box and trim to surrounding construction. B. Shop Drawings: For fire -protection cabinets. Include plans, elevations, sections, details, and attachments to other work. C. Samples: For each type of exposed finish required. D. Samples for Initial Selection: For each type of exposed finish required. E. Samples for Verification: For each type of exposed finish required, prepared on Samples 6 by 6 inches (150 by 150 mm) square. FIRE PROTECTION CABINETS 10 4413 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS F. Product Schedule: For fire -protection cabinets. Indicate whether recessed, semi recessed, or surface mounted. Coordinate final fire -protection cabinet schedule with fire-extinguisher schedule to ensure proper fit and function. 1.5 CLOSEOUT SUBMITTALS A. Maintenance Data: For fire -protection cabinets to include in maintenance manuals. 1.6 COORDINATION A. Coordinate size of fire -protection cabinets to ensure that type and capacity of fire extinguishers indicated are accommodated. B. Coordinate sizes and locations of fire -protection cabinets with wall depths. 1.7 SEQUENCING A. Apply vinyl lettering on field -painted fire -protection cabinets after painting is complete. PART 2- PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Fire -Rated Fire -Protection Cabinets: Listed and labeled to comply with requirements in ASTM E 814 for fire -resistance rating of walls where they are installed. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2.2 FIRE -PROTECTION CABINET A. Cabinet Type: Suitable for fire extinguisher. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include the following: a. Fire -End & Croker Corporation. b. GMR International Equipment Corporation. c. Guardian Fire Equipment, Inc. d. JL Industries, Inca a division of the Activar Construction Products Group. e. Larsens Manufacturing Company. f. Modem Metal Products Division of Technico Inc. g. Nystrom, Inc. h. Potter Roemer LLC. Strike First Corporation of America. FIRE PROTECTION CABINETS 10 4413 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Cabinet Construction: As per wall assembly ratings in which cabinet is installed unless otherwise indicated. 1. Fire -Rated Cabinets: Construct fire -rated cabinets with double walls fabricated from 0.043 -inch- (1.09 -mm-) thick cold -rolled steel sheet lined with minimum 5/8 -inch- (16- mm-) thick fire -barrier material. Provide factory -drilled mounting holes. C. Cabinet Material: Stainless-steel sheet. 1. Shelf: Same metal and finish as cabinet. D. Recessed Cabinet: 1. Trimless with Concealed Flange: Surface of surrounding wall finishes flush with exterior finished surface of cabinet frame and door, without overlapping trim attached to cabinet. Provide recessed flange, of same material as box, attached to box to act as drywall bead 2. Trimless with Hidden Flange: Flange of same metal and fmish as box overlaps surrounding wall finish and is concealed from view by an overlapping door. 3. Exposed Flat Trim: One-piece combination trim and perimeter door frame overlapping surrounding wall surface with exposed trim face and wall return at outer edge (backbend). E. Semirecessed Cabinet: One-piece combination trim and perimeter door frame overlapping surrounding wall surface with exposed trim face and wall return at outer edge (backbend). 1. Rolled -Edge Trim: 2 -1/2 -inch (64 -mm backbend depth. F. Surface -Mounted Cabinet: Cabinet box fully exposed and mounted directly on wall with no trim. G. Cabinet Trim Material: Same material and finish as door. H Door Material: Stainless-steel sheet. I. Door Style: Flush opaque panel, frameless, with no exposed hinges. J. Door Glazing: Tempered float glass (clear). K. Door Hardware: Manufacturer's standard door -operating hardware of proper type for cabinet type, trim style, and door material and style indicated. 1. Provide manufacturer's standard. 2. Provide manufacturer's standard hinge permitting door to open 180 degrees. L. Accessories: 1. Mounting Bracket: Manufacturer's standard steel, designed to secure fire extinguisher to fire -protection cabinet, of sizes required for types and capacities of fire extinguishers indicated, with plated or baked -enamel fmish. 2. Lettered Door Handle: One-piece, cast-iron door handle with the word "FIRE" embossed into face. FIRE PROTECTION CABINETS 10 44 13 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3. Identification: Lettering complying with authorities having jurisdiction for letter style, size, spacing, and location. Locate as directed by Architect. a. Identify fire extinguisher in fire -protection cabinet with the words "FIRE EXTINGUISHER." 1) Location: Applied to cabinet door. 2) Application Process: Decals. 3) Lettering Color: RED. 4) Orientation: Vertical. M. Materials: 1. Stainless Steel: ASTM A 666, Type 304. a. Finish: No. 4 directional satin finish. 2. Clear Float Glass: ASTM C 1036, Type I, Class 1, Quality q3, 6 mm thick. 2.3 FABRICATION A. Fire -Protection Cabinets: Provide manufacturer's standard box (tub) with trim, frame, door, and hardware to suit cabinet type, trim style, and door style indicated. 1. Weld joints and grind smooth. 2. Provide factory -drilled mounting holes. 3. Prepare doors and frames to receive locks. 4. Install door locks at factory. B. Cabinet Doors: Fabricate doors according to manufacturer's standards, from materials indicated and coordinated with cabinet types and trim styles. 1. Fabricate door frames with tubular stiles and rails and hollow -metal design, minimum 1/2 inch thick. 2. Fabricate door frames of one-piece construction with edges flanged. 3. Miter and weld perimeter door frames. C. Cabinet Trim: Fabricate cabinet trim in one piece with corners mitered, welded, and ground smooth. 2.4 GENERAL FINISH REQUIREMENTS A. Comply with NAAMM's AMP 500, "Metal Finishes Manual for Architectural and Metal Products," for recommendations for applying and designating finishes. B. Protect mechanical finishes on exposed surfaces of fire -protection cabinets from damage by applying a strippable, temporary protective covering before shipping. C. Finish fire -protection cabinets after assembly. FIRE PROTECTION CABINETS 10 44 13 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Appearance of Finished Work: Noticeable variations in same piece are not acceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine walls and partitions for suitable framing depth and blocking where recessed and semirecessed cabinets will be installed. B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 PREPARATION A. Prepare recesses for recessed and semi recessed fire -protection cabinets as required by type and size of cabinet and trim style. 3.3 INSTALLATION A. General: Install fire -protection cabinets in locations and at mounting heights indicated or, if not indicated, at heights acceptable to authorities having jurisdiction. 1. Fire -Protection Cabinets: 54 inches (1372 mm) above fmished floor to top of cabinet. B. Fire -Protection Cabinets: Fasten cabinets to structure, square and plumb. 1. Unless otherwise indicated, provide recessed fire -protection cabinets. If wall thickness is inadequate for recessed cabinets, provide semirecessed fire -protection cabinets. 2. Provide inside latch and lock for break -glass panels. 3. Fasten mounting brackets to inside surface of fire -protection cabinets, square and plumb. 4. Fire -Rated Cabinets: a. Install cabinet with not more than 1/16 -inch (1.6 -mm) tolerance between pipe OD and knockout OD. Center pipe within knockout. b. Seal through penetrations with firestopping sealant as specified in Section 078413 "Penetration Firestopping." C. Identification: Apply decals at locations indicated. 3.4 ADJUSTING AND CLEANING A. Remove temporary protective coverings and strippable films, if any, as fire -protection cabinets are installed unless otherwise indicated in manufacturer's written installation instructions. B. Adjust fire -protection cabinet doors to operate easily without binding. Verify that integral locking devices operate properly. FIRE PROTECTION CABINETS 10 4413 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. On completion of fire -protection cabinet installation, clean interior and exterior surfaces as recommended by manufacturer. D. Touch up marred fmishes, or replace fire -protection cabinets that cannot be restored to factory- fmished appearance. Use only materials and procedures recommended or furnished by fire - protection cabinet and mounting bracket manufacturers. E. Replace fire -protection cabinets that have been damaged or have deteriorated beyond successful repair by finish touchup or similar minor repair procedures. END OF SECTION 10 44 13 FIRE PROTECTION CABINETS 10 44 13 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 10 44 16 - FIRE EXTINGUISHERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes portable, hand -carried fire extinguishers and mounting brackets for fire extinguishers. B. Related Requirements: 1. Section 10 44 13 "Fire Protection Cabinets." 1.3 PREINSTALLATION MEETINGS A. Preinstallation Conference: Conduct conference at Project site. 1. Review methods and procedures related to fire extinguishers including, but not limited to, the following: a. Schedules and coordination requirements. 1.4 ACTION SUBMITTALS A. Product Data: For each type of product. Include rating and classification, material descriptions, dimensions of individual components and profiles, and finishes for fire extinguisher and mounting brackets. B. Product Schedule: For fire extinguishers. Coordinate final fire-extinguisher schedule with fire - protection cabinet schedule to ensure proper fit and function. 1.5 INFORMATIONAL SUBMITTALS A. Warranty: Sample of special warranty. 1.6 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For fire extinguishers to include in maintenance manuals. FIRE EXTINGUISHERS 10 44 16 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.7 COORDINATION A. Coordinate type and capacity of fire extinguishers with fire -protection cabinets to ensure fit and function. 1.8 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace fire extinguishers that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Failure of hydrostatic test according to NFPA 10. b. Faulty operation of valves or release levers. 2. Warranty Period: Six years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. NFPA Compliance: Fabricate and label fire extinguishers to comply with NFPA 10, "Portable Fire Extinguishers." B. Fire Extinguishers: Listed and labeled for type, rating, and classification by an independent testing agency acceptable to authorities having jurisdiction. 1. Provide fire extinguishers approved, listed, and labeled by FM Global. 2.2 PORTABLE, HAND -CARRIED FIRE EXTINGUISHERS A. Fire Extinguishers: Type, size, and capacity for each fire -protection cabinet and mounting bracket indicated. 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Amerex Corporation. b. Ansul Incorporated. c. Badger Fire Protection. d. Guardian Fire Equipment, Inc. e. JL Industries Inc.• a division of the Activar Construction Products Group. f. Kidde Residential and Commercial Division; Subsidiary of Kidde plc. g. Larsens Manufacturing Company. h. Pero -Chem; Tyco Safety Products. i. Strike First Corporation of America. FIRE EXTINGUISHERS 10 44 16 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Valves: Manufacturer's standard. 3. Handles and Levers: Manufacturer's standard 4. Instruction Labels: Include pictorial marking system complying with NFPA 10, Appendix B, and bar coding for documenting fire-extinguisher location, inspections, maintenance, and recharging B. Multipurpose Dry -Chemical Type: UL -rated 10 lb. nominal capacity, with monoammonium phosphate -based dry chemical in manufacturer's standard enameled container. C. Multipurpose Dry -Chemical Type in Steel Container: UL -rated 4-A:60-B:C, 10 -Ib (4.5 -kg) nominal capacity, with monoammonium phosphate -based dry chemical in enameled -steel container. 2.3 MOUNTING BRACKETS A. Mounting Brackets: Manufacturer's standard steel, designed to secure fire extinguisher to wall or structure, of sizes required for types and capacities of fire extinguishers indicated, with plated or red baked -enamel finish. 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Amerex Corporation. b. Ansul Incorporated. c. Badger Fire Protection. d. Guardian Fire Equipment, Inc. e. JL Industries, Inc.; a division of the Activar Construction Products Group. f. Kidde Residential and Commercial Division; Subsidiary of Kidde plc. g. Larsens Manufacturing Company. h. Pyro-Chem; Tyco Safety Products. i. Strike First Corporation of America. B. Identification: Lettering complying with authorities having jurisdiction for letter style, size, spacing, and location. Locate as indicated by Architect. 1. Identify bracket -mounted fire extinguishers with the words "FIRE EXTINGUISHER" in red letter decals applied to mounting surface. a. Orientation: Vertical. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine fire extinguishers for proper charging and tagging. 1. Remove and replace damaged, defective, or undercharged fire extinguishers. FIRE EXTINGUISHERS 10 44 16 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. General: Install fire extinguishers and mounting brackets in locations indicated and in compliance with requirements of authorities having jurisdiction. 1. Mounting Brackets: 54 inches (1372 mm) above finished floor to top of fire extinguisher. B. Mounting Brackets: Fasten mounting brackets to surfaces, square and plumb, at locations indicated. END OF SECTION 10 44 16 FIRE EXTINGUISHERS 10 44 16 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 107343 - TRANSPORTATION STOP SHELTERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Modular aluminum shelters. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. 1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for shelters. B. Shop Drawings: For shelters. Include plans, elevations, sections, details, and attachments to other work. 1. Anchor -Bolt Plans: Submit anchor -bolt plans and templates. Include location, diameter, and projection of anchor bolts required to attach shelters to concrete bases. Indicate post reactions at each location. C. Samples for Initial Selection: For each type of exposed finish. D. Samples for Verification: For each type of exposed finish in manufacturer's standard sizes. 1.4 INFORMATIONAL SUBMITTALS A. Evaluation Reports: For anchors, from ICC -ES. B. Sample Warranty: For special warranty. 1.5 CLOSEOUT SUBMITTALS A. Maintenance Data: For shelters to include in maintenance manuals. TRANSPORTATION STOP SHELTERS 107343 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.6 COORDINATION A. Cast -in Anchorage: Coordinate installation of anchorages for shelters. Furnish sleeves, concrete inserts, anchor bolts, and items with integral anchors that are to be embedded in concrete bases. Include setting drawings, templates, and directions for installing anchorages. Deliver such items to Project site in time for installation. 1.7 WARRANTY A. Special Warranty: Manufacturer agrees to repair finish or replace shelters that fail in materials or workmanship within specified warranty period. 1. Warranty Period: Five years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Structural Performance: Shelters shall withstand the following loads and stresses within limits and under conditions indicated according to ASCE/SEI 7 : 1. Design Loads: As indicated on Drawings. B. Theirnal Movements: Allow for thermal movements from ambient and surface temperature changes. Base calculations on surface temperatures of materials due to both solar heat gain and nighttime -sky heat loss. 1. Temperature Change (Range): 120 deg F (67 deg C), ambient; 180 deg F (100 de material surfaces C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2.2 MODULAR ALUMINUM SHELTERS A. Fabricate shelters as an integrated set of modular components ready for assembly on Project site. 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. AustinMohawk and Comnanv, Inc. b. Brasco International, Inc. c. Canada Kiosk. d. Columbia Equipment Company Inc. e. Duo -Gard Industries Inc. f. Sandi -Hut Inc. TRANSPORTATION STOP SHELTERS 107343 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS g. Keystone Structures Inc. h. MEI fvlardan Fabricators. i. Par -Kut International.' j. Poi,tafab Corporation. k. 'Takeo Corp. 1. Iblar Manufaeturina Comp4iny, B. Building Style: As indicated on Drawings. C. Structural Framework: Fabricated from manufacturer's standard 2.5 -by -2.5 -by -0.125 -inch (64.- by-64-by-3.18-mm) 64-by-64-by-3.18-mm) aluminum tubing, channel, angle, or tee extrusions. Connect framework with exposed mechanical fasteners. D. Post Bases: Externally adjustable, flanged, aluminum sleeves; minimum 3 -inch (76-1nm) vertical adjustment. Include shims for leveling. E. AnchoragePostinstalled anchors, fabricated from stainless steel, with allowable load or strength design capacities calculated to be greater than or equal to the design load. F. Roof: Flatwith full perimeter gutter. 1. Exterior Roof Panels: Fabricated from 0.032 -inch- (0.81 -mm-) thick aluminum sheet with protective plastic sheet finish. 2. Canopy Fascia: Fabricated from 0.063 -inch- (1.60 -mm-) thick aluminum sheet, of manufacturer's standard design. a. Height: 8 inches (203 mm). b. Overhang: [3 inches (76 mm 3. Downspouts: Integral �• G. Electrical Power Service: 125-A, 120/240-V ac, single phase, three wire. Run copper wiring in 1/2 -inch (13 -mm) EMT conduit. Exterior weatherproof connection box and lockable interior circuit breaker panel. H. Lighting Fixtures: Activated by photocell 1. Ceiling -mounted LED lighting. I. Materials: 1. Aluminum: Alloy and temper recommended by aluminum producer and manufacturer for type of use and finish indicated, and as follows: a. Sheet: ASTM B 209 (ASTM B 209M). b. Extruded Shapes: ASTM B 221 (ASTM B 221M). J. Clear Anodic Finish: AAMA 611, AA-M12C22A41, Class I, 0.018 nim or thicker. 1. ColorAs selected by Architect from full range of industry colors and color densities. TRANSPORTATION STOP SHELTERS 107343 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS K. Baked -Enamel or Powder -Coat Finish: AAMA 2603 except with a minimum dry film thickness of 1.5 mils (0.04 mm). Comply with coating manufacturer's written instructions for cleaning, conversion coating, and applying and baking finish. 1. Color and Gloss: As selected by Architect from manufacturer's full range . PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances, including concrete bases; accurate placement, pattern, and orientation of anchor bolts; critical dimensions; and other conditions affecting performance of the Work. B. Examine roughing -in for electrical system to verify actual locations of connections before shelter installation. C. Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work. D. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Install shelters according to manufacturer's written instructions. B. Set shelters plumb and aligned with full bearing on concrete bases. C. Fasten shelters securely to concrete base with anchorage indicated. D. Connect to electrical power. 3.3 ADJUSTING A. After completing installation, inspect exposed finishes and repair damaged finishes. END OF SECTION 107343 TRANSPORTATION STOP SHELTERS 107343 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 115213 - PROJECTION SCREENS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Manually operated, front -projection screens. 2. Electrically operated, front -projection screens and controls. B. Related Requirements: 1. Section 055000 "Metal Fabrications" for metal support framing for front -projection screens. 2. [Section 061000 "Rough Carpentry"] [Section 061053 "Miscellaneous Rough Carpentry"] for wood backing for screen installation. 3. Section 064600 "Wood Trim" for [wood trim] [wood trim and wood ceiling closure panel] for recessed screen installation. 4. Section 115213.19 'Rear Projection Screens." 1.3 DEFINITIONS A. Gain: Ratio of light reflected from screen material to that reflected perpendicularly from a magnesium carbonate surface as determined per SMPTE RP 94. B. Half -Gain Angle: The angle, measured from the axis of the screen surface to the most central position on a perpendicular plane through the horizontal centerline of the screen where the gain is half of the peak gain. 1.4 ACTION SUBMITTALS A. Product Data: For each type of product. B. Shop Drawings: Show layouts and types of front -projection screens. Include the following: 1. Drop lengths. 2. Location of seams in viewing surfaces. 3. Location of screen centerline relative to ends of screen case. 4. Anchorage details, including connection to supporting structure for suspended units. 5. Details of juncture of exposed surfaces with adjacent finishes. PROJECTION SCREENS 115213 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 6. Location of wiring connections for electrically operated units. 7. Wiring diagrams for electrically operated units. 8. Accessories. C. Samples for Initial Selection: For finishes of surface -mounted screen cases. 1.5 CLOSEOUT SUBMITTALS A. Maintenance Data: For front -projection screens to include in maintenance manuals. 1.6 DELIVERY, STORAGE, AND HANDLING Environmental Limitations: Do not deliver or install front -projection screens until spaces are enclosed and weathertight, wet work in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period. 1.7 COORDINATION A. Coordinate layout and installation of front -projection screens with adjacent construction, including ceiling suspension systems, light fixtures, HVAC equipment,[ fire -suppression system,] and partitions. PART 2 - PRODUCTS 2.1 MANUFACTURERS Source Limitations for Projection Screens: Obtain front -projection screensfrom single manufacturer. Obtain accessories, including necessary mounting hardware, from screen manufacturer. 2.2 ELECTRICALLY OPERATED, FRONT -PROJECTION SCREENS A. General: Manufacturer's standard units consisting of case, screen, motor, controls, mounting accessories, and other components necessary for a complete installation 1. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NEPA 70, by a qualified testing agency, and marked for intended location and application. 2. Controls: Remote,[ key -operated,] three -position control switch installed in recessed device box with flush cover plate[ matching other electrical device cover plates in room where switch is installed]. a. Provide [two] [three] <Insert number> control switches[ for each screen]. b. Provide number of control switches indicated[ for each screen]. c. Provide power supply for low -voltage systems if required. PROJECTION SCREENS 115213 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS d. Provide locking cover plates for switches. e. Provide key -operated, power -supply switch. f. Provide [infrared] [radio-frequency] remote control consisting of battery - powered transmitter and receiver. g. Provide video interface control for connecting to projector. Projector provides signal to raise or lower screen. 3. Motor in Roller: Instant -reversing motor of size and capacity recommended by screen manufacturer; with permanently lubricated ball bearings, automatic thermal -overload protection, preset limit switches to automatically stop screen in up and down positions, and positive -stop action to prevent coasting. Mount motor inside roller with vibration isolators to reduce noise transmission. 4. End -Mounted Motor: Instant -reversing, gear -drive motor of size and capacity recommended by screen manufacturer; with permanently lubricated ball bearings, automatic thermal -overload protection, preset limit switches to automatically stop screen in up and down positions, and positive -stop action to prevent coasting. Locate motor in its own compartment [on right end of screen unless otherwise indicated] [on Left end of screen unless otherwise indicated] [on end of screen indicated]. 5. Screen Mounting: Top edge securely anchored to rigid metal roller and bottom edge formed into a pocket holding a 3/8 -inch- (9.5 -mm-) diameter metal rod with ends of rod protected by plastic caps. a. Roller for end -mounted motor is supported by self -aligning bearings in brackets. b. Roller for motor in roller is supported by vibration- and noise -absorbing supports. 6. Tab Tensioning: Provide units that have a durable low -stretch cord, such as braided polyester, on each side of screen that is connected to edge of screen by tabs to pull screen flat horizontally.[ In lieu of tab tensioning, screens may be constructed from vinyl - coated screen cloth that contains horizontal stiffening monofilaments to resist edge curling.] B. Suspended, Electrically Operated Screens with Automatic Ceiling Closure, with Motor -in - Roller, and without Tab Tensioning: Units designed and fabricated for suspended mounting; with bottom of case composed of two panels, fully enclosing screen, motor, and wiring; one panel hinged and designed to open and close automatically when screen is lowered and fully raised, the other removable or openable for access to interior of case. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Da -Lute Screen Company; [Advantage Deluxe Electrol] [Boardroom Electrol]. b. Draper Ine; [Envoy] [Signature/Series E] [Ultimate Access/Series E]. 2. Provide metal or metal -lined wiring compaihuent. 3. Screen Case: Made from metal. 4. Provide screen case constructed to be installed with underside flush with ceiling. 5. Finish on Exposed Surfaces: baked enamel. PROJECTION SCREENS 115213 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.3 FRONT -PROJECTION SCREEN MATERIAL A. Matte -White Viewing Surface: Peak gain of not less than 0.9, and gain of not less than 0.8 at an angle of 50 degrees from the axis of the screen surface. 1. Products: Subject to compliance with requirementsavailable products that may be incorporated into the Work include, but are not limited to, the following: a. BEI Audio -Visual Products; Matte White. b. Bretfurd, Inc; Matte White. c. Da -Lite Screen Company; Matte White. d. Draper ineMatte White. e. Stewart Filmscreen Corporation; Snomatte 100. B. C. Size of Viewing Surface: 84 by 84 inches (2133 by 2133 PART 3 - EXECUTION 3.1 INSTALLATION Install front -projection screens at locations indicated to comply with screen manufacturer's written instructions. B. Install front -projection screens with screen cases in position and in relation to adjoining construction indicated. Securely anchor to supporting substrate in a manner that produces a smoothly operating screen with vertical edges plumb and viewing surface flat when screen is lowered. 1. Install low -voltage controls according to NEPA 70 and complying with manufacturer's written instructions. a. Wiring Method: Install wiring in raceway except in accessible ceiling spaces and in gypsum board partitions where unenclosed wiring method may be used. Use UL -listed plenum cable in environmental air spaces, including plenum ceilings. Conceal raceway and cables except in unfinished spaces. 2. Test electrically operated units to verify that screen controls, limit switches, closures, and other operating components are in optimum functioning condition. 3. Test manually operated units to verify that screen -operating components are in optimum functioning condition. END OF SECTION 115213 PROJECTION SCREENS 115213 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 116623 - GYMNASIUM EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Basketball equipment. 2. Volleyball equipment. B. Related Requirements: 1. Section 033000 "Cast -in -Place Concrete" for installation of floor insert sleevesto be cast in concrete slabs and footings. 2. Section 096466 "Wood Athletic Flooring" for game lines and markers. 3. Section 116653 "Gymnasium Dividers." 1.3 DEFINITIONS A. BWF: Badminton World Federation. B. FIBA: Federation Internationale de Basketball Amateur (The International Basketball Federation). C. FIVB: Federation Internationale de Volleyball (The International Volleyball Federation). D. NCAA: The National Collegiate Athletic Association. E. NFHS: National Federation of State High School Associations. F. USAV: USA Volleyball. 1.4 ACTION SUBMITTALS A. Product Data: For each type of product. 1. If applicable, include assembly, disassembly, and storage instructions for removable equipment. 2. Motors: Show nameplate data, ratings, characteristics, and mounting arrangements. GYMNASIUM EQUIPMENT 116623 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Shop Drawings: For gymnasium equipment. 1. Include plans, elevations, sections, details, and attachments to other work. 2. Include details of field assembly for removable equipment, connections, installation, mountings, floor inserts, attachments to other work, and operational clearances. 3. Include transport and storage accessories for removable equipment. 1.5 INFORMATIONAL SUBMITTALS A. Coordination Drawings: Court layout plans, drawn to scale, and coordinated with floor inserts, game lines, and markers applied to finished flooring. B. Qualification Data: For Installer. C. Product Certificates: For each type of gymnasium equipment. D. Sample Warranty: For special warranty. 1.6 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For gymnasium equipment to include in emergency, operation, and maintenance manuals. 1.7 QUALITY ASSURANCE A. Installer Qualifications: Fabricator of productsAn entity that employs installers and supervisors who are trained and approved by manufacturer. 1.8 FIELD CONDITIONS A. Environmental Limitations: Do not install gymnasium equipment until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use. B. Field Measurements: Verify position and elevation of floor inserts and layout for gymnasium equipment. 1.9 COORDINATION A. Coordinate installation of floor inserts with structural floors and finish flooring installation and with court layout and game lines and markers on finish flooring. B. Coordinate layout and installation of overhead -supported gymnasium equipment and suspension -system components with other construction including light fixtures, HVAC equipment, fire -suppression -system components, and partition assemblies. GYMNASIUM EQUIPMENT 116623 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.10 WARRANTY A. Special Warranty: Manufacturer agrees to repair or replace components of gymnasium equipment that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Basketball backboard failures including glass breakage. b. Faulty operation of basketball backstops. 2. Warranty Period: Fiveyears from date of Substantial Completion. PART 2 - PRODUCTS 2.1 MANUFACTURERS, GENERAL A. Source Limitations: Obtain gymnasium equipment] from single source from single manufacturer. 2.2 BASKETBALL EQUIPMENT A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. PALCO Ulagtizfacturing. 2. ADP Lcmco. 3. Arizona Courtlines. Inc. 4. Bison. Inc. 5. Dou rlas Industries. Inc 6. Draper, Inc. 7. Institutional_Products,_Inc. 8. Iavpro Sports Construction 9. L. A. Ste -act -aft. 10. Perfonnamee Sports Svste ns _a Cra 11. Porter Athletic, Inc. 12. Schelde iNorl:h Anerica. 13. Spalding Equipment. d B. Protruding fasteners or exposed bolt heads on front face of backboards are not permitted. C. Provide manufacturer's recommended connections complying with Section 055000 "Metal Fabrications" of size and type required to transfer loads to building structure. D. Overhead-SupportedBackstops: 1. Folding Type: Provide manufacturer's standard assembly for forward -folding, front- bracedbackstop, with hardware and fittings to permit folding. 2. Framing: Steel pipe, tubing, and shapes. Design framing to minimize vibration during play. GYMNASIUM EQUIPMENT 116623 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Center -Mast Frame: Welded] with side sway bracing. b. Finish: Manufacturer's standard polyester powder -coat finish. 3. Goal Height Adjuster: Adjustable from 8 to 10 feet (2.4 to 3 m) with gear -drive mechanism, locking in any position within adjustment range, with visible height scale attached to side of framing. a. Operation: Manual with detachable crank handle. E. Backstop Safety Device: Designed to limit free fall if support cable, chains, pulleys, fittings, winch, or related components fail; with mechanical automatic reset; [6000-11) (2722 -kg)] load capacity; one per folding backstop]. F. Backstop Electric Operator: Provide operating machine of size and capacity recommended by manufacturer for equipment specified, with electric motor and factory -prewired motor controls, starter, gear -reduction unit, and remote controls. Coordinate wiring requirements and electrical characteristics with building electrical system. 1. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2. Operator Type: Cable drum with grooved drum and cable tension device to automatically take up cable slack and retain cable in grooves. 3. Operator Mounting: Wall -mounted board 4. Limit Switches: Adjustable switches, interlocked with motor controls and set to automatically stop basketball equipment at fully retracted and fully lowered positions. G. Basketball Backboards: 1. Shape and Size: a. Rectangular, [72 by 42 inches (1800 by 1067 mm)] [72 by 48 inches (1800 by 1200 nim)] <Insert dimensions> width by height[, with rounded corners]. 2. 3. Backboard Material: With predrilled holes or preset inserts for mounting goals, and as follows: a. Glass: Not less than i/2 -inch- (13 -mm-) thick, transparent tempered glass complying with ASTM C 1048 Kind FT (fully tempered) and with impact testing requirements in 16 CFR 1201 Category II or ANSI Z97.1 Class A for safety glazingProvide glass with impact -absorbing resilient rubber or PVC gasket around perimeter in a fully welded, painted steelframe, with steel subframe, reinforcement, bracing, and mounting slots for mounting backboard frame to backboard support framing. 1) Standard Mount: Provide steel comer reinforcement with mounting slots for mounting backboard frame to backstop at standard mounting centers. 2) Direct Mount: Designed for mounting backboard frame to center mast of backstop to maximize relief of stresses on backboard frame and glass. GYMNASIUM EQUIPMENT 116623 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3) Rim -Restraining Device: Complying with NCAA and NFHS rules and designed to ensure that basket remains attached if glass backboard breaks. b. Steel: Single -piece, steel face sheet, not less than [0.1046 -inch (2.7 -mm)] nominal thickness, with 1 -1./2 -inch- (38 -mm-) deep, roll -edged perimeter flange and with steel -reinforced, welded frame welded to back side of backboard; with mounting slots for mounting backboard frame to backboard support framing at standard mounting centers. 4. Target Area and Border Markings: Permanently etched in white color, marked in manufacturer's standard pattern and stripe width. H. Basketball Goals: Complete with flanges, braces, attachment plate, and evenly spaced loops welded around underside of ring. 1. Single -Rim Basket Ring Competition Goal: Materials, dimensions, and fabrication per manufacturer's standard design. 2. Breakaway Characteristics: Positive -lock movable breakaway design, with manufacturer's standard breakaway mechanism including preset pressure release, set to release at 180- and 230 -Ib load, and automatic reset. Provide movable ring with rebound characteristics identical to those of fixed, nonmovable ring. 3. Field Adjustment: Provide rim that is field -adjustable for rebound elasticity without being removed from the backboard. 4. Net Attachment: No -tie loops for attaching net to rim without tying 5. Finish: Manufacturer's standardfinish. Basketball Nets: 12 -loop -mesh net, between 1.5 and 18 inches (380 to 460 min) long, sized to fit rim diameter, and as follows: 1. Competition Cord: Antiwhip, made from white nylon cord not less than 120 -gm thread and not more than 144 -gm thread. J. Backboard Safety Pads: Designed for backboard thickness indicated and extending continuously along bottom and up sides of backboard and over goal mounting and backboard supports per manufacturer's standard design 1. Attachment: Manufacturer's standard. 2. Color: As selected by Architect from manufacturer's full range. 2.3 VOLLEYBALL EQUIPMENT A. Manufacturers: Subject to compliance with requirementsavailable manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. AALCO Manufacturing 2. ADP Lerne°. 3. Arizona Courtl nes,[ac. 4. Bison Inc. 5. Douglas lndustdes, Inc. 6. Draper, Inc. GYMNASIUM EQUIPMENT 116623 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 7. Jaypro Sports Construction Group. 8. L. A. Steelcraft. S.orts Svs ems a C ared Hold'n s co 9. Pe 10. Porter AthIetie, Inc. 11. de North America. 12. Spading Equipment. 13. Sports Imports. B. Floor Insert: Solid-brassfloor plate; and steel pipe sleeve, concealed by floor plate, with capped bottom end, sized with ID to fit post standards, not less than [9 inches (228 mm) long] [12 inches (305 mm) longto securely anchor pipe sleeve; with anchors designed for securing floor insert to floor substrate indicated; one per post standard] C. Post Standards: Removable, paired volleyball post standards as indicated. Adjustable, telescoping height. Designed for easy removal from permanently placed floor insert supports. Fabricated from manufacturer's standard metal pipe or tubing, with nonmarking plastic or rubber end cap or floor bumper to protect permanent flooring. Finished with manufacturer's standard factory -applied, polyester powder -coat finish complying with finish manufacturer's written instructions for surface preparation, including pretreatment, application, baking, and minimum dry film thickness or plated metal finish. 1. Net Height Adjuster: Manufacturer's standard mechanism for height adjustment, complete with fittings; designed for positioning net at heights indicated. a. Net Heights: Between tennis net height and boys'/men's volleyball net height, 42 and 95-5/8 inches (1067 and 2430 min) > or more. 2. Height Markers: Clearly marked at regulation play heights for elementary school girls/womenboys/men tennis D. Net: 32 feet (9.75 m) long; one per pair of paired post standards; and as follows: 1. Width and Mesh: 36 inches (910 min) with 4 -1/2 -inch- (114 -mm-) square mesh made of black polyester string. a. Hem Band Edges: White, 2 -inch- (50 -mm -1 wide top binding; black, [3/4 -inch - (19 -mm-)] [1 -inch- (25 -mm-)] wide bottom and side bindings; tie offs at top and bottom of each side end of net; and 1/4 -inch- (6 -mm-) diameter rope, at least 42 feet (12.8 m) long, threaded through top hem of binding. 2. Width and Mesh: Competition volleyball net, [36 inches (910 mm)] [39 inches (990 mm)] with 4 -inch- (102 -mm-) square[ knotless] mesh made of black nylon string. a. Hem Band Edges: White, not less than 2 -inch- (50 -mm-) wide top, bottom, and side bindings; [tie offs at top, bottom, and midpoint of each side end of net] [not less than 1 -inch- (25 -ram-) wide tension straps at top, bottom, and midpoint of each side end of net]; end sleeves for dowels; and lines with linkage fittings threaded through top and bottom hems of binding. Provide lengths of lines and linkage fittings as required to properly connect to and set up net for post standard spacing indicated on Drawings. GYMNASIUM EQUIPMENT 116623 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1) Top Line: Not less than [1/4 -inch- (6 -mm-) diameter rope] [1/8 -inch- (3- mm-) diameter, galvanized- or coated -steel cable] <Insert description>. 2) Bottom Line: Not less than [1/4 -inch- (6 -mm-) diameter rope] [1/8 -inch - (3 -mm-) diameter, galvanized- or coated -steel cable] <Insert description>. 3. Dowels: Not less than 1/2 -inch- (13 -mm;) diameter fiberglass or 1 -inch- (25 -mm-) diameter wood. Provide two dowels per net threaded through each side hem sleeve for straightening net side edges. 4. Net Antennas: 3/8 -inch- (9.5 -mm-) diameter, high -tensile -strength, extruded -fiberglass or plastic rods, 72 inches (1800 mm) long, extending above top hem band of net, with alternating white and red bands according to competition rules. Provide two antennas per net. a. Clamps: Designed to secure antenna to top and bottom of net. 5. Boundary Tape Markers: 2 -inch- (50 -mm.-) wide white strip[ with sleeve for securing net antenna], secured to net top and bottom with hook -and -loop attachment. Provide two tape markers per net for marking court boundaries. E. Net -Tensioning System: Designed to adjust and hold tension of net. Fully enclosed, nonslip manufacturer's standard -type winch with cable length and fittings for connecting to net lines, positive -release mechanism, manufacturer's standard handle. Provide end post with post top pulley. Provide opposing post with welded -steel loops, hooks, pins, or other devices for net attachment and post top grooved line guide. F. Bottom Net Lock Tightener: Provide manufacturer's standard quick -release -type tension strap; a spring-loaded, self-locking tensioner; a turnbuckle; a pulley; or other device and linkage fittings designed to quickly and easily tighten bottom line or net. G. Safety Pads: Comply with NCAA and NFHS requirements. Provide pads consisting of not less than [1 -inch- (25 -mm-)] [1 -1/4 -inch- (32 -min )] thick, multiple -impact -resistant manufacturer's standard foam filler covered by puncture- and tear -resistant fabric covermanufacturer's standard ; with fire -test -response characteristics indicated. Provide pads with hook -and -loop closure or attachments for the following components: 1. Post Standards: Wraparoundstyle, designed to totally enclose each standard to a height of not less 72 inches (1800 mm; one per post. 2. Net Lines: Four per net. 3. Fabric Color: As selected by Architect from full range of industry standard colors and color densities. H. Post Standard Transporter: Manufacturer's standard wheeled unit designed for transporting a single post. I. Wall Storage Rack: Manufacturer's standard unit designed for mounting on walls and for storing post standards in vertical position with retaining arms, fittings for padlock, and mounting hardware; number of units as required to provide storage for specified equipment. J. Storage Cart: Manufacturer's standard wheeled unit designed for transporting and storing volleyball equipment and passing through 36 -inch- (910 -mm-) wide door openings. Fabricate GYMNASIUM EQUIPMENT 116623 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS welded -steel tubing units with heavy-duty casters, including no fewer than two swivel casters. Fabricate wheels from materials that do not damage or mark floors; number of units as required to provide transport and storage for specified equipment. 2.4 MATERIALS A. Aluminum: Alloy and temper recommended by manufacturer for use and finish type indicated. 1. Extruded Bars, Profiles, and Tubes: ASTM B 221 (ASTM B 221M.). 2. Cast Aluminum: ASTM B 179. 3. Flat Sheet: ASTM B 209 (ASTM 13 209M). B. Steel: Comply with the following: 1. Steel Plates, Shapes, and Bars: ASTM A 36/A 36M. 2. Steel Tubing: ASTM A 500/A 500M or ASTM A 513, cold formed. 3. Steel Sheet: ASTM A 1011/A 1011M. C. Support Cable: [1/4 -inch- (6 -mm-) diameter, 7x19] [Manufacturer's standard] galvanized - stranded -steel wire rope[ with a breaking strength of 7000 lb (3173 kg)]. Provide fittings complying with wire rope manufacturer's written instructions for size, number, and installation method. D. Support Chain and Fittings: For chains used for overhead lifting, provide Grade 80 heat-treated alloy steel chains, complying with ASTM A 391/A 391M, with commercial -quality, hot -dip galvanized steel connectors and hangars. E. General -Purpose Chain: For chains not used for overhead lifting, provide carbon steel chain, complying with ASTM A 413/A 413M, Grade 30 proof coil chain or other grade recommended by gymnasium equipment manufacturer. Provide coating type, chain size, number, and installation method complying with manufacturer's written instructions. F. Castings and Hangers: Malleable iron, complying with ASTM A 47/A 47M; grade required for structural loading. G. Composite Wood Products: Products shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small -Scale Environmental Chambers." H. Softwood Plywood: DOC PS 1, exterior. I. Anchors, Fasteners, Fittings, and Hardware: Manufacturer's standard corrosion -resistant or noncorrodible units; concealed[; tamperproof, vandal- and theft -resistant design]. J. Grout: Nonshrink, nonmetallic, premixed, factory -packaged, nonstaining, noncorrosive, nongaseous grout, complying with ASTM C 1107/C 1107 with minimum strength recommended in writing by gymnasium equipment manufacturer. GYMNASIUM EQUIPMENT 116623 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for play court layout, alignment of mounting substrates, installation tolerances, operational clearances, accurate locations of connections to building electrical system, and other conditions affecting performance of the Work. 1. Verify critical dimensions. 2. Examine supporting structure, subfloors, and footings below finished floor. 3. Examine wall assemblies, where reinforced to receive anchors and fasteners, to verify that locations of concealed reinforcements are clearly marked. Locate reinforcements and mark locations. B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION, GENERAL A. General: Comply with manufacturer's written installation instructionsand competition rules indicated for each type of gymnasium equipment. Complete equipment field assembly where required. B. Unless otherwise indicated, install gymnasium equipment after other finishing operations, including painting, are completed. C. Permanently Placed Gymnasium Equipment and Components: Install rigid, level, plumb, square, and true; anchored securely to supporting structure; positioned at locations and elevations indicated; in proper relation to adjacent construction; and aligned with court layout. 1. Floor Insert Location: Coordinate location with application of game lines and markers. 2. Floor Insert Elevation: Coordinate installed heights of floor insert with installationof finish flooring and floor -plate type. 3. Operating Gymnasium Equipment: Verify clearances for movable components of gymnasium equipment throughout entire range of operation and for access to operating components. D. Floor Insert Setting: Position sleeve in oversized, recessed voids in concrete Clean voids of debris. Fill void around sleeves with grout, mixed and placed to comply with grout manufacturer's written instructions. Protect portion of sleeve above subfloor[ and footing] from splatter. Verify that sleeves are set plumb, aligned, and at correct height and spacing; hold in position during placement and finishing operations until grout is sufficiently cured. Set insert so top surface of completed unit is flush with finished flooring surface. E. Cut-out Trim: Limit cuts in face of padding from trim unit's corner -to -corner outside dimensions. Install with ends of cuts concealed behind trim flange. GYMNASIUM EQUIPMENT 116623 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS F. Anchoring to In -Place Construction: Use anchors and fasteners where necessary to secure built- in and permanently placed gymnasium equipment to structural support and to properly transfer load to in-place construction. G. Connections: Connect electric operators to building electrical system. H. Removable Gymnasium Equipment and Components: Assemble in place to verify that equipment and components are complete and in proper working order. Instruct Owner's designated personnel in properly handling, assembling, adjusting, disassembling, transporting, storing, and maintaining units. Disassemble removable gymnasium equipment after assembled configuration is approved by [Architect] [Owner], and store units in location indicated on Drawings. 3.3 ADJUSTING A. Adjust movable components of gymnasium equipment to operate safely, smoothly, easily, and quietly, free from binding, warp, distortion, nonalignment, misplacement, disruption, or malfunction, throughout entire operational range. Lubricate hardware and moving parts. 3.4 CLEANING A. After completing gymnasium equipment installation, inspect components. Remove spots, dirt, and debris and touch up damaged shop -applied fmishes according to manufacturer's written instructions. B. Replace gymnasium equipment and finishes that cannot be cleaned and repaired, in a manner approved by Architect, before time of Substantial Completion. 3.5 DEMONSTRATION A. Engage a factory -authorized service representative to trainOwner's maintenance personnel to adjust, operate, and maintain gymnasium equipment. END OF SECTION 116623 GYMNASIUM EQUIPMENT 116623 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 11 66 23 PROTECTIVE GYMNASIUM FLOOR COVERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Protective gymnasium floor covers. B. Cover handling system. C. Accessories: 1. Power winder. 2. Dual -brush system. 3. Walk -behind tape dispenser. 4. Seaming tape. 5. Protective gymnasium floor cover cleaner. 1.2 RELATED SECTIONS A. Section 09644 (09 64 66) — Wood Athletic Flooring. 1.3 REFERENCES A. ASTM D 751 — Standard Test Methods for Coated Fabrics. B. ASTM D 1894 — Standard Test Method for Static and Kinetic Coefficients of Friction of Plastic Film and Sheeting. C. Fed. Std. 191-5100 — Strength and Elongation, Breaking of Woven Cloth; Grab Method. D. Fed. Std. 191-5134 — Strength of Cloth, Tearing: Tongue Method. E. NEPA 701 — Standard Methods of Fire Tests for Flame Propagation of Textiles and Films. F. UL 214 — Tests for Flame Propagation of Fabrics and Films. 1.4 SUBMITTALS A. Comply with Submittal Procedures. B. Product Data: Submit manufacturer's product data. C. Samples: Submit manufacturer's samples of protective gymnasium floor covers, minimum 6 inches by 6 inches. D. Manufacturer's Certification: Submit manufacturer's certification that materials comply with specified requirements and are suitable for intended application. PROTECTIVE GYM FLOORCOVERS 11 66 23 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Operation and Maintenance Manual: Submit manufacturer's operation and maintenance manual, including the following: 1. Assembly, operation, maintenance, adjustment, and cleaning instructions. 2. Parts list. F. Warranty: Submit manufacturer's standard warranty. 1.5 QUALITY ASSURANCE A. Manufacturer's Qualifications: Manufacturer regularly engaged, for preceding 10 years, in manufacture of protective gymnasium floor covers and cover handling systems. 1.6 DELIVERY, STORAGE, AND HANDLING A. Delivery: Deliver materials to site in manufacturer's original, unopened containers and packaging, with labels clearly identifying product name and manufacturer. B. Storage: 1. Store materials in accordance with manufacturer's instructions. 2. Store protective gymnasium floor covers and cover handling system [in clean, dry area indoors] [as indicated on the Drawings] [at location directed by Owner]. C. Handling: Protect materials and finish during handling to prevent damage 1.7 WARRANTY A. Warranty Period: 1. Protective Gymnasium Floor Covers: c. "Ultima 3000": 12 years. 4. Dual -Brush System: 5 years. PART 2 PRODUCTS 2.1 MANUFACTURER A. Basis of Design Product: Subject to compliance with requirements provide; Covermaster Inc., 100 Westmore Drive, Unit 11D, Rexdale, Ontario M9V 5C3. Toll Free (800) 387-5808. Phone (416) 745- 1811. Fax (416) 742-6837. Website www.covermaster.com. E-mail info@covermaster.com or comparable product. 2.2 PROTECTIVE GYMNASIUM FLOOR COVERS C. Protective Gymnasium Floor Covers: "Ultima 3000". 1. Material Properties: a. Surface Finish: Safety, slip -resistant, holographic -cube pattern. PROTECTIVE GYM FLOORCOVERS 11 66 23 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS b. Surface Treatment: Cover -Guard treated to resist odors and germs. Rot and mildew resistant. c. Fabric Core: Single layer, woven polyester. d. Weave Count: 18 by 18. e. Coating: PVC, knife/spread-coating process. f. Weight: 1) Outer Vinyl Wear Coating, Top and Bottom: 8.5 ounces per square yard on each side. 2) Inner Fabric Core: 4.0 ounces per square yard. 3) Total Cover: 21 ounces per square yard. g. Can be used with either side up. 2. Mechanical Properties: a. Slip -Resistant Surface, Coefficient of Friction, ASTM D 1894: 0.66. ADA compliant. b. Tensile Strength, Fed. Std. 191-5100: 375 pounds. c. Tear Strength, Fed. Std. 191-5134: 90 pounds. d. Adhesion, ASTM D 751: 35 pounds per inch. e. Hydrostatic Resistance, ASTM D 751: 430 pounds per inch. 3. Fire Resistance Compliance: a. UL 214. b. NFPA 701, large-scale test. c. California Fire Marshall. d. Connecticut Fire Marshall: Class 1 rating. e. State of New York: Class A rating. 4. Construction: a. Section Length: Match length of floor. b. Section Width: 10 feet. c. Seams: Thermally welded. d. Lap Weld: Minimum 1 inch. 5. Dual -Color Combination: Twilight gold on 1 side, dark grey on other side. 2.3 COVER HANDLING SYSTEM A. Cover Handling System: "Ultima Series Covermate II". 1. Size: a. Width: 1) Outriggers Retracted: 34 inches. 2) Outriggers Extended: 57-1/2 inches. b. Length: 13'-2". c. Height: 1) Six -Roller Model: 5'-6". 2) Eight -Roller Model: 5'-6". 3) Ten -Roller Model: 6'-6". 2. Frame: 1 -1/2 -inch and 2 -inch rectangular -tubular frame. 3. Frame Finish: a. Powder coat. b. Color: Silver. 4. Outriggers: a. Provides stability against tipping. b. Retractable. c. Two adjustable, swivel casters on each outrigger. d. Locking pins secure outriggers in extended or retracted positions. e. Color: Safety orange. PROTECTIVE GYM FLOORCOVERS 11 6623 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 5. Pressure Floor Locks: a. Two floor -locking brakes, 1 at each end of unit. b. Foot operated. c. Bolted to frame. d. Locks cover handling system to floor. 6. Casters: a. Six Colson ball-bearing casters. b. Non -marking Santoprene SofTreads treads. c. One of 3 casters at each end is offset to spread load over larger area and to better protect floor. d. Diameter: 6 inches. e. Tread Width: 2 inches. f. Tread Thickness: 3/4 inch. 7. Roller Collars: a. On each end of each roller. b. Holds roller captive. c. No exposed pins. Prevents sideways movement of roller. d. Eliminates finger pinch points. e. Color: Bright yellow. 8. Roller -Bearing Brackets: a. Polycarbonate brackets with Delrin roller bearings. b. Mounted with 1/8 -inch -thick shock -absorbing rubber pads. c. Safety bolt on each roller -bearing bracket holds roller captive to prevent roller pop -ups. 9. Rollers: a. Flo -Coat galvanized steel with clear topcoat. b. Diameter: 2-1/2 inches. 10. Fastening Clips: a. Four push -on clips for each roller. b. Extruded, flexible plastic. c. Color: Orange. 11. Loading Covers on Rollers: Two 1 -piece Lexan polycarbonate hand cranks. 12. Certified Load Capacity: 5,400 pounds. 13. Assembly: Field assembled. Include instruction manual. 2.4 ACCESSORIES B. Dual -Brush System: "Ultima Series Coverclean". 1. Mounting: a. Quick connect/disconnect. b. 1 -5/8 -inch, 14 -gauge drawn channel. c. Mounts on both sides of system. 2. Brush Angle: Brush mounted at 35 -degree angle to match path of cover travel at each roller height. 3. Brush Heads: Dual -opposing heads sweep debris and dust from both sides of cover during wind- up. 4. Bristles: a. Two rows of 3 -inch bristles. b. Black, Styrene -Fiber Bristle Row: Fine sweeping. c. Red, Polystyrene -Fiber Bristle Row: Heavy debris. C. Walk -Behind Tape Dispenser: "Tapemate". PROTECTIVE GYM FLOORCOVERS 11 66 23 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Material: Enameled steel. 2. Front Wheel: Applies tape to cover as you walk it along. 3. Handle: Adjusts to operator's height. 4. Tape Support: Drop-in place. 5. Tape Size: Accommodates 3 -inch wide tape. D. Seaming Tape: "Covertape". 1. Temporarily covers overlap seams. 2. Transparent. 3. Easy to remove. 4. Leaves no messy glue residue behind. 5. Width: 3 inches. 6. Length per Roll: 36 yards. E. Protective Gymnasium Floor Cover Cleaner: "Cleanmate". 1. Concentrated, anti -static cleaning solution. 2. Cleans and conditions protective gymnasium floor covers. PART 3 EXECUTION 3.1 ASSEMBLY A. Cover Handling System: 1. 2. Field assemble cover handling system by manufacturer -approved assembly service. 3. Ensure casters and rollers operate smoothly without binding. B. Dual -Brush System: Mount dual -brush system on cover handling system in accordance with manufacturer's instructions. 3.2 PROTECTION A. Protect protective gymnasium floor covers and cover handling system from damage during construction. B. Do not use protective gymnasium floor covers or cover handling system to protect gymnasium floors during construction. END OF SECTION PROTECTIVE GYM FLOORCOVERS 11 66 23 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 116653 - GYMNASIUM DIVIDERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY Section Includes: 1. Walk -draw divider systems. 2. Fold -up divider systems. 3. Radius -fold divider systems. 4. Peak -fold divider systems. 5. Roll -up divider systems. 6. Top -roll divider systems. 7. Center -Roll divider systems. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. 1. Motors: Show mounting arrangements and wiring diagram to power source and controls. B. Shop Drawings: For gymnasium dividers. 1. Include plans showing alignment of curtains in relation to court layout. 2. Include elevations, sections, details, and attachments to other work. 3. Include system clearances, stacking requirements, and limits for fitting into adjacent construction. 4. Include loads, point reactions, and locations for attachment of gymnasium dividers to structure. C. Samples for Initial Selection: For each type of gymnasium divider curtain fabric. D. Samples for Verification: For divider curtain fabric, not less than 12 inches (305 mm) square of mesh andof solid fabric. 1.4 INFORMATIONAL SUBMITTALS A. Qualification Data: For Installer. B. Product Certificates: For each type of gymnasium divider. GYMNASIUM DIVIDERS 116653 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Sample Warranty: For special warranty. 1.5 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For gymnasium dividers to include in operation and maintenance manuals. 1.6 QUALITY ASSURANCE A. Installer Qualifications: Fabricator of products 1.7 FIELD CONDITIONS A. Environmental Limitations: Do not install gymnasium dividers until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use. B. Field Measurements: Verify size of space, available clearances, obstructions, and position for gymnasium dividers. 1.8 COORDINATION A. Coordinate installation of overhead -supported gymnasium dividers and suspension -system components with other construction including light fixtures, HVAC equipment, fire - suppression -system components, and partition assemblies. B. Electrically Operated Dividers: Coordinate electrical requirements for type and location of power supply, conduit, wiring, and control boxes. 1.9 WARRANTY A. Special Warranty: Manufacturer agrees to repair or replace components of gymnasium dividers that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Faulty operation of gymnasium dividers. b. Tearing or deterioration of fabric, seams, or other materials beyond normal use. 2. Warranty Period: Five years from date of Substantial Completion. GYMNASIUM DIVIDERS 116653 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 2- PRODUCTS 2.1 MANUFACTURERS, GENERAL A. Source Limitations: Obtain gymnasium dividers] from single source from single manufacturer. 2.2 TOP -ROLL DIVIDER SYSTEMS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. AALCO Manufacturing. 2. ADP Lemco. 3. Draper, Inc. 4. Javpro Sports Construction Group. 5. Performance Sports Systems: a Cared Holdings company. 6. S•aldin" Ec ui.ment. 7. <Insert manufacturer's name>. B. Divider Curtain System: Electrically operated, top -roll drive pipe, and as follows: 1. Outer Edge Hems: Double tumed[ and welded]. 2. Supports and Fittings: Corrosion -resistant steel clamps and hangers. 3. Drive Pipe: 3 -1/8 -inch (79 -mm) nominal diameter, fabricate from steel, aluminum, or PVC pipe or tubing with a minimum number of joints, as necessary for required lengths. Steel shall be galvanized or shop primed and shop finished with black paint. 4. Curtain Battens: 1 -1/2 -inch (38 -mm) nominal diameter, fabricated from steel pipe or tubing with a minimum number of joints, as necessary for required lengths. Provide galvanized steel, or shop prime and shop finish with black paint. 2.3 MATERIALS A. Support Chain and Fittings: For chains used for overhead lifting, provide Grade 80 heat-treated alloy steel chains, complying with ASTM A 391/A 391M, with commercial -quality, [hot -dip galvanized] [or] [zinc -plated] steel connectors and hangers. B. General -Purpose Chain: For chains not used for overhead lifting, provide carbon steel chain, complying with ASTM A 413/A 413M, Grade 30 proof coil chain or other grade recommended by gymnasium divider manufacturer. Provide coating type, chain size, number, and installation method complying with manufacturer's written instructions. C. Anchors, Fasteners, Fittings, and Hardware: Manufacturer's standard corrosion -resistant or noncorrodible units; concealed[; tamperproof, vandal -resistant design]. GYMNASIUM DIVIDERS 116653 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.4 ELECTRIC OPERATORS A. General: Factory -assembled electric operation system of size and capacity recommended and provided by gymnasium divider manufacturer for gymnasium dividers specified, with electric motors, thermal -overload protection, factory -prewired motor controls, control devices, and accessories required for proper operation. Include wiring from control stations to motors. Coordinate operator wiring requirements and electrical characteristics with building electrical system. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. C. Limit Switches: Adjustable switches, interlocked with motor controls and set to automatically stop dividers at fully extended and fully retracted positions. D. Control System: 1. Key Operation: NEMA ICS 6, Type 1 enclosure, momentary -contact, three -position switch -operated control. a. Keys: Provide one key(s) per station. 2.5 DIVIDER CURTAINS A. Upper Curtain, Mesh: Woven mesh of polyester yarn coated with vinyl, weighing not less than 9 oz./sq. yd. (305 1. Mesh Color: As selected by Architect from full range of industry colors and color densities B. Lower Curtain, Solid: Woven polyester fabric coated with vinyl, 22 oz./sq. yd. (745 g/sq. in, [1.0 -foot (3M -m height above floor. 1. Fabric Color(sas selected by Architect from full range of industry colors and color densities C. Hems: Folded and electronically welded. D. Seams: Electronically welded. E. Overall Curtain Height: Floor to ceiling, within installation clearances required. F. Bottom of Curtain: Approximately 2 inches (50 mm) above finished floor. G. Divider Curtain Flame -Resistance Ratings: Passes NFPA 701, Test 2. GYMNASIUM DIVIDERS 116653 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for alignment of mounting substrates, installation tolerances, operational clearances, building electrical system connection types and locations, and other conditions affecting performance of the Work. 1. Verify critical dimensions. 2. Examine supporting structure. 3. Examine wall assemblies, where reinforced to receive anchors and fasteners, to verify that Locations of concealed reinforcements are clearly marked. Locate reinforcements and mark locations. B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION, GENERAL A. General: Comply with manufacturer's written installation instructions. B. Unless otherwise indicated, install gymnasium dividers after other finishing operations, including painting, are completed. C. Gymnasium Dividers and Components: Install level, plumb, square, and true; anchored securely to supporting structure; positioned at locations and elevations indicated; in proper relation to adjacent construction; and aligned with court layout. 1. Verify clearances for movable components of gymnasium dividers throughout entire range of operation and for access to operating components. D. Anchoring to In -Place Construction: Use anchors and fasteners where necessary to secure gymnasium dividers to structural support and to properly transfer load to in-place construction. E. Connections: Connect automatic operators to building electrical system. 3.3 ADJUSTING A. Adjust movable components of gymnasium dividers to operate safely, smoothly, easily, and quietly, free from binding, warp, distortion, uneven tension, nonalignment, misplacement, disruption, or malfunction, throughout entire operational range. Lubricate hardware and moving parts. B. Limit Switch Adjustment: Set and adjust upper and lower limit controls. GYMNASIUM DIVIDERS 116653 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.4 CLEANING A. After completing gymnasium divider installation, inspect components. Remove spots, dirt, and debris and touch up damaged shop -applied finishes according to manufacturer's written instructions. B. Replace gymnasium divider components and finishes that cannot be cleaned and repaired, in a manner approved by Architect, before time of Substantial Completion. 3.5 DEMONSTRATION A. Engage a factory -authorized service representative to trainOwner's maintenance personnel to adjust, operate, and maintain gymnasium dividers. END OF SECTION 116653 GYMNASIUM DIVIDERS 116653 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 124816 - ENTRANCE FLOOR GRILLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes recessed floor grilles and frames. 1.3 COORDINATION A. Coordinate size and location of recesses in concrete to receive floor grilles and frames. 1.4 ACTION SUBMITTALS A. Product Data: For each type of product. 1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for entrance floor grilles and foot grilles. B. Shop Drawings: 1. Items penetrating floor grilles and frames, including door control devices. 2. Divisions between grille sections. 3. Perimeter floor moldings. C. Samples: For the following products, in manufacturer's standard sizes: 1. Floor Grille: Assembled section of floor grille. 2. Frame Members: Sample of each type and color. 1.5 CLOSEOUT SUBMITTALS A. Maintenance Data: For floor grilles and frames to include in maintenance manuals. 1.6 FIELD CONDITIONS A. Field Measurements: Indicate measurements on Shop Drawings. ENTRANCE FLOOR GRILLES 124816 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: B. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated or a comparable product by one of the following: 1. Arden Architectural Sjpedallies, Inc. 2. 13alco Inc. 3. Cactus Mat Mfg. Co. 4. Crowder, K. N. Manufacturing, inc. 5. „c2/5i(1 too. 6. J. L. Industries, Inc. 7. Kadee Industries, Inc. 8. ;Mats Inc. 9. Pawling Comoratior Arch tec nnl Products Division. 10. 2.2 ENTRANCE FLOOR GRILLES, GENERAL A. Structural Performance: Provide floor grilles and frames capable of withstanding the following loads and stresses: 1. Uniform floor load of [300 Ibf/sq. ft. (14.36 kN sq. in)] B. Regulatory Requirements: Comply with applicable provisions in the U.S. Architectural & Transportation Barriers Compliance Board's ADA -ABA Accessibility Guidelines for Buildings and Facilities. 2.3 FLOOR GRILLES A. General: Provide manufacturer's standard floor -grille assemblies consisting of treads of type and profile indicated, interlocked or joined together by cross members, and with support legs (if any) and other components needed to produce a complete installation. B. Aluminum Floor Grilles: Provide manufacturer's standard floor grilles with extruded members, top -surfaced tread rails, and as follows: 1. Tread Rails: Extruded-aluminumtread rails a. Aluminum Color:As selected by Architect from full range of industry colors and color densities. 2. Top Surface: Fusion -bonded, level -cut -pile nylon carpet insert; 1/4 inch (6.4 mm) high, 28 oz./sq. yd. (950 g/sq, m). ENTRANCE FLOOR GRILLES 124816 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Top Surface Color: As selected by Architect from manufacturer's full range of industry colors. C. Lockdown: Hidden. 2.4 FRAMES A. Provide manufacturer's standard frames of size and style for grille type, for permanent recessed installation in subfloor, complete with installation anchorages and accessories. Unless otherwise indicated, fabricate frame of same material and finish as grilles. 2.5 SUPPORT SYSTEM A. Level Bed Applications: Provide manufacturer's standard, vinyl cushion support system. B. Drainage Pit Applications: Provide manufacturer's special deep -pit frame and support extrusion system with intermediate support beams, sized and spaced as recommended by manufacturer for indicated spans and equipped with vinyl support cushions. 2.6 DRAIN PANS A. Provide manufacturer's standard[, 0.060 -inch- (L52 -mm-) thick], aluminum sheet drain pan with NPS 2 (DN 50) drain outlet for each floor -grille unit. Coat bottom of pan with protective coating recommended by manufacturer. 2.7 MATERIALS A. Aluminum Sheet: ASTM B 209 (ASTM B 209M), alloy and temper recommended by aluminum producer and finisher for type of use and finish indicated, and with not less than strength and durability properties of Alloy 5005-H15. B. Extruded Aluminum: ASTM B 221 (ASTM'13 22IM), Alloy 6061-T6 or Alloy 6063-T5, T6, or T52 as standard with manufacturer. Coat surface of frame in contact with cementitious materials with manufacturer's standard protective coating. 2.8 FABRICATION Shop fabricate floor grilles to greatest extent possible in sizes as indicated. Unless otherwise indicated, provide each grille as a single unit; do not exceed manufacturer's recommended maximum sizes for units that are removed for maintenance and cleaning. Where joints in grilles are necessary, space symmetrically and away from normal traffic lanes. B. Fabricate frame members in single lengths or, where frame dimensions exceed maximum available lengths, provide minimum number of pieces possible, with hairline joints equally spaced and pieces spliced together by straight connecting pins. ENTRANCE FLOOR GRILLES 124816 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.9 ALUMINUM FINISHES A. Clear Anodic Finish: AAMA 611, AA-M12C22A41, Class I, 0.018 mmor thicker. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and floor conditions for compliance with requirements for location, size, minimum recess depth, and other conditions affecting installation of floor grilles and frames. B. Examine roughing -in for drainage piping systems to verify actual locations of piping connections before floor grille and frame and drain pan installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Install recessed floor grilles and frames and drain pans to comply with manufacturer's written instructions at locations indicated and with top of floor grilles and frames in relationship to one another and to adjoining finished flooring as recommended by manufacturer. Set floor -grille tops at height for most effective cleaning action. Coordinate top of floor -grille surfaces with doors that swing across grilles to provide clearance under door. 3.3 PROTECTION A. After completing frame installations, provide temporary filler of plywood or fiberboard in floor - grille recesses and cover frames with plywood protective flooring. Maintain protection until construction traffic has ended and Project is near Substantial Completion. END OF SECTION 124816 ENTRANCE FLOOR GRILLES 124816 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 126613 — TELESCOPIC BLEACHERS SPECIFICATION PART 1— GENERAL 1.01 SUMMARY A. Section Includes: Telescoping Gym Seating includes, either manually or electrically operated systems of multiple -tiered seating rows comprising of seat, deck components, understructure that permits closing without requiring dismantling, into a nested configuration for storing or for moving purposes. 1. Typical applications include the following: a. Wall Attached Telescoping Gym Seats. b. Recessed Telescoping Gym Seats. c. Floor -Attached (Freestanding) Telescoping Gym Seats. d. Portable/Movable Telescoping Gym Seats. e. Reverse Fold Telescoping Gym Seats. f. Traveling Telescopic Seating Unit A. Related Sections: 1. Division 9 finishes sections for adequate floor & wall construction for operation of Telescoping Gym Seats. Flooring shall be level and rear wall plumb within 1/8" [3min] in 8'-0 [2438mm]. Maximum bleacher force on the floor, of a 25'-6" [7772] section, shall be a static point load of less than 300 psi [2.068 N/mm2]. 2. Division 16 Electrical sections for electrical wiring and connections for electrically operated Telescoping Gym Seats. B. Qualifications and Capabilities: 1. BIDDER QUALIFICATIONS: Bidders are required to be an authorized dealer or manufacturer for equipment proposed which on a day-to-day basis regularly provide the equipment offered. Bidders are further advised that only standard production models or standard options will be acceptable for award. Equipment offered shall be currently manufactured on an active assembly line. The State is only interested in proven equipment; provided, installed, and serviced by Authorized Dealers capable of providing references. 2. INSTALLER QUALIFICATIONS: Bleacher installer shall be Factory Certified by the Manufacturer. Proof of Factory Certified Installation_Certificate shall be provided along with the Invitation to Bid. Failure to provide this information shall result in rejection of bid. (No Exceptions Taken) 1.02 REFERENCE A. International Building Code (IBC) B. ICC 300 — Standard for Bleachers, Folding and Telescopic Seating and Grandstands TELESCOPIC BLEACHERS 126613-1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. American Welding Society (AWS) 1. AWS D1.1 Structural Welding Code — Steel 2. WS D1.3 Structural Welding Code - Sheet Steel D. American Institute of Steel Construction (AISC): 1. AISC - Design of Hot Rolled Steel Structural Members. E. American National Standards Institute (ANSI). F. American Iron & Steel Institute (AISI): 1. AISI - Design Cold Formed Steel Structural Members. G. Aluminum Association (AA): 1. AA - Aluminum Structures, Construction Manual Series. H. American Society for Testing Materials (ASTM): 1. ASTM - Standard Specification for Properties of Materials. I. National Forest Products Association (NFoPA): 1. NFoPA - National Design Specification for Wood Construction. J. Southern Pine Inspection Bureau (SPIB): 1. SPIB - Standard Grading Rules for Southern Pine. K. National Bureau of Standards/Products Standard (NBS/PS): 1. PS1 - Construction and Industrial Plywood. L. Americans with Disability Act (ADA) 1. ADA - Standards for Accessible Design. TELESCOPIC BLEACHERS 12 66 13 -2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.03 MANUFACTURER'S SYSTEM ENGINEERING DESCRIPTION A. Structural Performance: Engineer, fabricate and install telescopic gym seating systems to the following structural loads without exceeding allowable design working stresses of materials involved, including anchors and connections. Apply each load to produce maximum stress in each respective component of each gym seat unit. 1. Design Loads: Comply with ICC 300 —2012 Edition B. Manufacturer's System Design Criteria: 1. Gymnasium seat assembly; Design to support and resist, in addition to it's own weight, the following forces: a. Live load of 120 lbs per linear foot [162.69 N/m] on seats and decking b. Uniformly distributed live load of not less than 100 lbs per sq. ft. [135.58N/m] of gross horizontal projection. c. Parallel sway load of 24 lbs. [32.53 N/m] per linear foot of row combined with (b.) above d. Perpendicular sway load of 10 lbs. [13.56 N -m] per linear foot of row combined with (b.) above 2. Hand Railings, Posts and Supports: Engineered to withstand the following forces applied separately: a. Concentrated load of 200 lbs. [90.72 kg] applied at any point and in any direction. b. Uniform load of 50 lbs. per foot [.344 N/mm2] applied in any direction. 3. Guard Railings, Post and Supports: Engineered to withstand the following forces applied separately: a. Concentrated load of 200 lbs. [90.72 kg] applied at any point and in any direction along top rail. b. Uniform load of 50 lbs. per foot [.344 N/mm2] applied horizontally at top rail and a simultaneous uniform load of 100 lbs. per foot [.689 N/mm2] applied vertically downward. 4. Member Sizes and Connections: Design criteria (current edition) of the following shall be the basis for calculation of member sizes and connections: a. AISC: Manual of Steel Construction b. AISI: Specification for Design of Cold Formed Steel Structural Members c. AA: Specification for Aluminum Structures d. NFOPA: National Design Guide For Wood Construction. 1.04 SUBMITTIALS A. Section Cross -Reference: Required submittals in accordance with "Conditions of the Contract" and Division 1 General Requirements sections of this "Project Manual." B. Project Data: Manufacturer's product data for each system. Include the following: 1. Project list: Ten(10) seating projects of similar size, complexity and in service for at least five (5) years. 2. Deviations: List of deviations from these project specifications, if any. TELESCOPIC BLEACHERS 12 66 13 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Shop Drawings: Indicate Telescoping Gym Seat assembly layout. Show seat heights, row spacing and rise, aisle widths and locations, assembly dimensions, anchorage to supporting structure, material types and finishes. 1. Wiring Diagrams: Indicate electrical wiring and connections. 2. Graphics Layout Drawings: Indicate pattern of contrasting or matching seat colors D. Samples: Seat materials and color finish as selected by Architect from manufacturers standard offered color finishes. E. Manufacturer Qualifications: manufacturing experience of manufacturer, and copy of a telescopic load test to all loads described in 1.03 above, observed by a qualified independent testing laboratory, and certified by a registered professional structural engineer verifying the integrity of the manufacturer's geometry design and base structural assumptions. F. Installer Qualifications: Installer qualifications indicating capability, experience, and official Certification Card issued by manufacturer of telescopic seating. G. Engineer Qualifications: Certification by a professional engineer registered in the state of manufacturer that the equipment to be supplied meets or exceeds the design criteria of this specification. H. Operating/Maintenance Manuals: Provide to Owner maintenance manuals. Demonstrate operating procedures, recommended maintenance and inspection program. I. Warranty: Manufacturers standard warranty documents. TELESCOPIC BLEACHERS 12 66 13 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.05 QUALITY ASSURANCE A. Seating Layout: Comply with ICCC 300 -2012 Standard for Bleachers, Folding Telescopic Seating and Grandstands, except where additional requirements are indicated or imposed by authorities having jurisdiction. B. Welding Standards & Qualification: Comply with AWS D1.1 Structural Welding Code - Steel and AWS D1.3 Structural Welding Code - Sheet Steel. C. Manufacturer Qualifications: Manufacturer who has a minimum of 10 years of experience manufacturing telescoping gym seats and can demonstrate continual design enhancement and 5 -year minimum product life -cycle support of telescopic seating. D. Installer Qualifications: Engage experienced Installer who has specialized in installation of telescoping gym seat types similar to types required for this project and who carries an official Certification Card issued by telescoping gym seat manufacturer. E. Engineer Qualifications: Engage licensed professional engineer experienced in providing engineering services of the kind indicated that have resulted in the successful installation of telescoping bleachers similar in material, design, fabrication, and extent to those types indicated for this project. 1.06 DELIVERY, STORAGE AND HANDLING A. Deliver telescopic gym seats in manufacturers packaging clearly labeled with manufacturer name and content. B. Handle seating equipment in a manner to prevent damage. C. Deliver the seating at a scheduled time for installation that will not interfere with other trades operating in the building. 1.07 PROJECT CONDITIONS A. Field Measurements: Coordinate actual dimensions of construction affecting telescoping bleachers installation by accurate field measurements before fabrication. Show recorded measurements on final shop drawings. Coordinate field measurements and fabrication schedule with construction progress to avoid delay of Work. 1.08 WARRANTY A. Manufacturer's Product Warranty: Submit manufacturer's standard warranty form for telescoping bleachers. This warranty is in addition to, and not a limitation of other rights Owner may have under Contract Documents. TELESCOPIC BLEACHERS 12 66 13 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Warranty Period: Five years from Date of Acceptance. 2. Beneficiary: Issue warranty in legal name of project Owner. 3. PART 2— PRODUCTS 2.01 MANUFACTURERS A. Basis -of -Design: Subject to compliance with requirements, provide : Hussey Seating Company, U.S.A. or comparable product. 1. Address: North Berwick, Maine, 03906 2. Telephone: (207) 676-2271; Fax: (207) 676-9690 3. Product: MAXAM Telescopic Gym Seat System by Hussey Seating Company TELESCOPIC BLEACHERS 12 66 13 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Model: MAXAM26 Series Telescopic Gym Seats, adjustable row spacing in two inch increments from 22 inches [559] to 26 inches [660]. b. MAXAM26 Series Telescopic Gym Seats, Rise Spacing: 11 5/8" [295] Aisle Type:, foot level aisles. c. Seat Type: 12" Courtside Collection (1) Seat color fmish: : manufacturers 15 standard for Courtside Collection (2) Rail Type:: Self -storing end rail, (3) Rail color finish:: Standard black or 15 standard colors to match Courtside Collection seat. (See Personalization and Creativity under Accessories section). d. Operation: : Electric e. Electrical Power System: Integral power with pendant Control limit switches, key switches 4. Product Description/Criteria a. Bank Length:52'-0" b. Net Capacity; 300 c. 5. Handicap Seating Provisions: : Provide first tier modular recoverable Flex -rows, handicap first-tier fixed end -section cutouts B. Other Acceptable Manufacturers: Will be considered if in compliance with these specifications. Deviations must be submitted with bid in order that a fair and proper evaluation be made. Those bidders not submitting a list of deviations will be presumed to have bid as specified. TELESCOPIC BLEACHERS 12 66 13 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. 2.02 MATERIALS A. Lumber: ANSI/Voluntary Product 20, B & B Southern Pine B. Plywood: ANSI/Voluntary Product PSI, APA A -C Exterior Grade. C. Structural Steel Shapes, Plates and Bars: ASTM A 36. D. Uncoated Steel Strip (Non -Structural Components): ASTM A569, Commercial Quality, Hot -Rolled Strip. E. Uncoated Steel Strip (Structural Components): ASTM A570 Grade 33, 40, 45, or 50, Structural Quality, Hot -Rolled Strip. F. Uncoated Steel Strip (Structural Components): ASTM A607 Grade 45 or 50, High -Strength, Low Alloy, Hot -Rolled Strip. G. Galvanized Steel Strip: ASTM A653 Grade 40, zinc coated by the hot -dip process, structural quality. H. Structural Tubing: ASTM A500 Grade B, cold -formed. I. Polyethylene Polymer: ASTM D 1248, Type III, Class B; molded, color -pigmented, textured, impact - resistant, structural formulation; in color indicated or, if not otherwise indicated, as selected by Architect from manufacturer's standard colors. J. Fasteners: Vibration -proof, of size and material standard with manufacturer. 2.03 UNDERSTRUCTURE FABRICATION A. Frame System: 1. Wheels: Not less than 5" [127] diameter by 1 1/4" [32] with non -marring soft rubber face to protect wood and synthetic floor surfaces, with molded -in sintered iron oil -impregnated bushings to fit 3/8" [10] diameter axles secured with E -type snap rings. 2. Lower Track: Continuous Positive Interglide System interlocks each adjacent CPI unit using an integral, continuous, anti -drift feature and through -bolted guide at front to prevent separation and misalignment. CPI units at end sections of powered banks and manual sections shall contain a Low Profile Posi-Lock LX to lock each row in open position and allow unlocking automatically. Provide adjustable stops to allow field adjustment of row spacings. 3. Slant Columns: High tensile steel, tubular shape. 4. Sway Bracing: High tensile steel members through -bolted to columns. 5. Deck Stabilizer: High tensile steel member through -bolted to nose and riser at three locations per section. Interlocks with adjacent stabilizer on upper tier using low -friction nylon roller to prevent separation and misalignment. Incorporates multiple stops to allow field adjustment of row spacings. TELESCOPIC BLEACHERS 12 66 13 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 6. Deck Support: Securely captures front and rear edge of decking at rear edge of nose beam and lower edge of riser beam for entire length of section. B. Deck System: 1. Section Lengths: Each bank shall contain sections not to exceed 25'-6" [7772] in length with a minimum of two supporting frames per row, each section. 2. Nose beam and Rear Riser beam: Nose beam shall be continuously roll -formed closed tubular shape of ASTM A653 grade 40, Riser beam shall be continuously roll -formed of ASTM A653 grade 40. Nose and Riser beam shall be designed with no steel edges exposed to spectator after product assembly. 3. Attachment: Through -Bolted fore/aft to deck stabilizers, and frame cantilevers. 4. Decking: 5/8" [16], AC grade clear -top -coated tongue and groove Southern Yellow Pine; or BC grade polyethylene -top -coated tongue and groove Douglas Fir plywood; both of interior type with exterior glue, 5 -ply, all plies with plugged cross -bands, produced in accordance with National Bureau of Standards PS -1-97. Plywood shall be cut and installed with top, center and bottom ply grain -oriented from front of deck to rear of deck (nose beam to riser beam). Adjacent pieces shall be locked together with tongue and groove joint from front to rear of deck. Longest unsupported span: MAXAM 26, 21 %2" [546]. 5. Deck End Overhang: Not to exceed frame support by more than 5'-11" [1804]. 2.04 SEAT FABRICATION A. Polymer Seat System — Courtside Collection XCS 12 (12"): Hussey Courtside Collection Series embodies the latest leading edge innovations in linear telescopic seating modules. Courtside seats utilize a harmonious blend of advanced ergonomic principals, architecturally appealing design, safety, value and performance. Seat Modules: 18" [457] long assembled, gas assisted injection -molded, high density, 100% recyclable HDPE (high density polyethylene) modules in monochromatic colors providing, dual textured scuff resistant 12" [305] wide seat surface with 'A" [13] minimum interlock on seat and face. Unit structural tested to 600 lbs occupant load. 1. CourtSide XCS12 Seat Module a. XCS12 — 12" [305] Comfort Profile (1) Individual ergonomically contoured seat module (2) Compound contoured seats with fore/aft and horizontally contoured curves provide a "scalloped" surface area for maximum spectator comfort. Forward edge "waterfall" for enhanced spectator comfort and minimization of sensitive pressure point area, regardless of leg positioning. (3) Fore & Aft contoured seat surface for uniform support and minimize high pressure points under the buttocks. (4) Seat height ranges from deck to t/o seat range from 16-1/8" [410] to 18-1/8" [460] (5) 21-1/8" [537] clear foot space area. b. Bold contoured design lines for maximum architectural appeal and application with modern or traditional facility spaces. c. Integrally molded end caps at aisle end locations for clean fmished appearance. TELESCOPIC BLEACHERS 12 66 13 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS d. Integrally molded recess pockets to accept seat number and row letters. e. Integrally molded rear closure panel at back of seat to allow for "continuous clean sweep" of debris at deck level and minimized visibility of structural ribbing. f. Seat Attachment: Each polymer seat module shall be securely anchored by a 12 ga steel clamp bracket that provides steel -to -steel, through bolted attachment to the front nose beam of the bleacher. Attachment eliminates fore / aft movement of the seat module on the nose beam. 2.05 SHOP FINISHES A. Understructure: For rust resistance, steel understructure shall be finished on all surfaces with black "Dura - Coat" enamel. Understructure finish shall contain a silicone additive to improve scratch resistance of finish. B. Wear Surfaces: Surface subject to normal wear by spectators shall have a finish that does not wear to show different color underneath: 1. Steel nosing and rear risers shall be pre -galvanized with a minimum spangle of G-60 zinc plating. 2. Decking shall have use -surfaces to receive both a sealer coat and wear -resistant high gloss clear urethane finish. Optional decking to have 0.030" laminated polyethylene wear surface. 3. Injection Molded Courtside seats shall be per manufacturer standard 15 colors. C. Railings: Steel railings shall be finished with powder -coated semi - gloss black or optional 15 standard colors to match polymer seat color. D. High Humidity finish: Above shop fmishes shall include following modifications: 1. Understructure: All frames and other structural components shall be hot -dip galvanized per ASTM A103 2. All top -side rails shall be e -coated prior to powder paint coating 3. All hardware to be zinc -plated 4. All posi-locks and other steel wear surfaces to be electroless-nickel plated 5. Decking to be polyethylene -laminated plywood 2.06 FASTENINGS A. Welds: Performed by welders certified by AWS standards for the process employed. B. Structural Connections: Secured by structural bolts with prevailing torque lock nuts, free -spinning nuts in combination with lock washers, or Riv-nuts in combination with lock washers. 2.07 ELECTRICAL OPERATION A. Integral Power 1. Default operation shall be with a removable pendant control unit which plugs into seating bank for tethered operator management of stop, start, forward, and reverse control of the power operation. Other modes of operation are optional. 2. PF1/2/3/4: Furnish and install Hussey PF(1/2/3/4), an integral automatic electro mechanical powered frame propulsion system, to open and close telescopic seating. TELESCOPIC BLEACHERS 12 66 13 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Electrical - Seating Manufacturer shall provide all wiring within seating bank, including pendant control. Motors, housing, and wiring shall be installed and grounded in complete accord with the National Electrical Code. The electrical contractor shall perform all connections at and upstream of the equipment specified herein, and ensure that supplied voltage drops no more than 4% below nominal where power connects thereto.To prevent 3rd party control of the system, power is made available to the Remote Control Receiver for a limited time by a Radio Frequency Identification (RFID) system that requires activation by the operator. Once the power system is activated, an audio beep and visual light is active to notify the user that the system is energized and ready for operation. The wireless remote shall be used by trained authorized operators to open and close the system with continuous pressure applied to the desired button. b. Each unit for PF(1/2/3/4) is driven by a 1/2 horsepower, 1725 RPM motor. c. Plug & Play Power (1) The Plug & Play option enables safe cord and plug connection of the power system to the power supply, eliminates the need for a separate disconnect, and eliminates lockout tagout procedures at the bleacher. Electrical contractor shall provide and install the disconnect -rated receptacle and associated parts specified by the manufacturer. Manufacturer shall specify facility preparations for, and furnish and install a cord -and -plug connected power system. This option is available only with 208V 3 Phase. d. Limit Switches (1) Limit switches will automatically stop integral power operation when seating has reached the fully extended or closed position. Manufacturer shall furnish and install both open and closed limit switches for the integral power system. Power operation shall utilize a combination of contactors and limit switches to insure the wiring is not energized except during operation. Straight wired electric system is not allowed. e. Key Switch Control (1) Manufacturer shall furnish parts and instructions for installing a key -operated controller on the fixed structure of the facility. f. Portable Power Assist (1) Portable Power Assist is a walk -behind, self-contained portable electro -mechanical power unit enabling operator management of stop, start, forward, and reverse control of a bleacher. Multiple bleachers may be operated independently by attaching to / detaching from one bleacher and moving to another. None of the above described options are available with Portable Power Assist. (2) Manufacturer to furnish and install two attachments for Portable Power Assist on every applicable section of bleacher and one Portable Power Assist unit per facility. Portable Power Assist shall have a 100' long heavy duty cord and be cord and plug connected to a 120V 20 amp outlet convenient to the bleachers to be operated. (3) Tractor unit shall be fitted with rugged operating handle with convenient switches controlling forward / reverse separate from spring loaded on / off switch. Power drive unit shall consist of a gearmotor with dual output shafts and 6" [152] diameter wheels covered with non -marring 1/2" [13] thick molded polyurethane. Average operating speed shall be 35 feet / min [12.8 meters / min] with pulling capacity of PF3 (see above). TELESCOPIC BLEACHERS 12 66 13 - 11 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS TELESCOPIC BLEACHERS 12 66 13 - 12 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.08 ACCESSORIES1 STANDARD TELESCOPIC GYMSEAT ACCESSORIES A. Flex -Row: Provide first row modular recoverable seating units to be utilized by persons in wheelchairs and able-bodied persons. Each Flex -Row unit shall have an unlock handle for easy deployment if wheelchair or team seating access is needed. Unlock handle shall lock the bleacher seats into position when fully opened. 1. Provide a black full -surround steel skirting with no more than 3/a" floor clearance for safety and improved aesthetics. 2. Provide a black injection molded end cap for the nose beam for safety and improved aesthetics.. 3. Provide a mechanical positive lock when the Flex -Row system is in the open and used position. 4. Flex -Row modular units are designed to achieve multi -use front row seating to accommodate team seating, ADA requirements and facility specific requirements. Flex -Row units are available in modular units from 2 to 7 seats wide as well as full section widths. B. Front Aisle Steps: Provide at each vertical aisle location front aisle step. Front steps shall engage with front row to prevent accidental separation or movement. Steps shall be fitted with four non-skid rubber feet each 1/2" [13] in diameter. Blow molded end caps shall have full radius on all four edges. Quantity and location as indicated. C. Non -Slip Tread: Provide at front edge of each aisle location an adhesive -backed abrasive non -slip tread surface. D. Foot Level Aisles: Provide deck level full width vertical aisles located as indicated. E. Intermediate Aisle Steps: Intermediate aisle steps shall be of boxed fully enclosed type construction. Blow molded end caps shall have full radius on all four edges. Step shall have adhesive -backed abrasive non- slip tread surface. Quantity and location as indicated. F. Intermediate Aisle Handrails: Provide single pedestal mount handrails 34" [864] high with terminating mid rail. Handrails shall be attached to the socket and shall lift and rotate 90° for easy storage in socket. Aisle handrails that are detached from the socket for storage are unacceptable. G. Intermediate Folding Aisle Handrails: Provide single pedestal mount handrails 34" [864] high with terminating mid rail. Handrail to be permanently mounted to a rotating socket for rail storage on the intermediate aisle step. H. Front Panel: Provide front closure panels for truncated sections, permanent end cutouts or elevated front aisles. Panels shall extend vertically from underside of front row to within 1 1/2" [38] or floor. Paneling to be 5/8" [16] Southern Pine Plywood or grey Polydeck attached to a steel framework. I. End' Panel: Provide closure end panels for closed stack position at each exposed bank end. End panels shall be constructed of 5/8" [ 16] Southern pine plywood or grey Polydeck. TELESCOPIC BLEACHERS 12 66 13 - 13 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS J. Rear Panel: Provide required seating units with full width rear closure panels. Panels shall extend vertically full height or up to 8'-0" [2438] high to within 1 1/2" [38] of floor. Paneling to be 5/8" [16] Southern Pine Plywood or grey Polydeck attached to a steel framework. Rear panels cannot extend above 8'-0" [2438] on portable sections. K. Front Rail: Provide not less than 30" [762] high above deck, steel rails with tubular supports and intermediate members designed with 4" [ 102] sphere passage requirements. Rails to be located at each required seating location. L. Self -Storing End Rails: Provide steel self -storing 42" [1066] high above seat, end rail with tubular supports and intermediate members designed with 4" [102] sphere passage requirements. TELESCOPIC BLEACHERS 12 66 13 - 14 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3— EXECUTION 3.01 EXAMINATION A. Verification of Conditions: Verify area to receive telescoping gym seats are free of impediments interfering with installation and condition of installation substrates are acceptable to receive telescoping gym seats in accordance with telescoping gym seats manufacturer's recommendations. Do not commence installation until conditions are satisfactory. 3.02 INSTALLATION A. Manufacturer's Recommendations: Comply with telescoping gym seats manufacturer's recommendations for product installation requirements. B. General: Manufacturer's Certified Installers to install telescoping gym seats in accordance with manufacturer's installation instructions and final shop drawings. Provide accessories, anchors, fasteners, inserts and other items for installation of telescoping gym seats and for permanent attachment to adjoining construction. 3.03 ADJUSTMENT AND CLEANING A. Adjustment: After installation completion, test and adjust each telescoping gym seats assembly to operate in compliance with manufacturer's operations manual. B. Cleaning: Clean installed telescoping gym seats on both exposed and semi -exposed surfaces. Touch-up finishes restoring damage or soiled surfaces. 3.04 PROTECTION A. General: Provide final protection and maintain conditions, in a manner acceptable to manufacturer and installer to ensure telescoping gym seats are without damage or deterioration at time of substantial completion. END OF SECTION TELESCOPIC BLEACHERS 12 66 13 - 15 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 12 93 00 - SITE FURNISHINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Seating. 2. Bicycle racks. 3. Trash receptacles. B. Related Requirements: 1. Section 033000 "Cast -in -Place Concrete" for installing pipe sleeves cast, installing anchor bolts cast and formed voids in concrete footings. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. B. Sustainable Submittals: 1. Product Data: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content. Include statement indicating cost for each product having recycled content. C. Samples: For each exposed product and for each color and texture specified. D. Samples for Initial Selection: For units with factory -applied finishes. E. Samples for Verification: For each type of exposed finish, not less than 6 -inch- (152 -mm-) long linear components and 4 -inch- (102 -mm-) square sheet components. F. Product Schedule: For site furnishings. Use same designations indicated on Drawings. 1.4 INFORMATIONAL SUBMITTALS A. Material Certificates: For site furnishings. SITE FURNISHINGS 12 93 00 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Product Data: Submit manufacturer's product data, storage and handling requirements and recommendations, installation methods and available colors, styles, patterns and textures. C. Shop Drawings: Submit manufacturer's shop drawings, including plans and elevations, indicating overall dimensions. D. Samples: Submit manufacturer's samples of materials, finishes, and colors. 1.5 CLOSEOUT SUBMITTALS A. Maintenance Data: For site furnishings to include in maintenance manuals. B. Warranty: Manufacturer's standard warranty. 1.6 MAINTENANCE MATERIAL SUBMITTALS A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Trash Receptacle Inner Containers: Five full-size units for each size indicated, but no fewer than two units. PART 2- PRODUCTS 2.1 SEATING A. Products: Subject to compliance with requirements, available products that may incorporated into the Work include, but are not limited to, the following: Basis of Design: Size: Material: Cast stone Fasteners: Landscape Forms, Inc. Model: "Flor" Bench. Small - 67"w x 75"d x 16-1/2"h (concrete). Surface Mount. Basis of Design: Landscape Forms, Inc. Model: "Lungo Mare" Bench. Size: 158"w X 79"d X 35" h Material: Reinforced Cast stone (concrete). Fasteners: Surface Mount. be Basis of Design: Landscape Forms, Inc. Model: "Abil" Bench. Size: 117" length x 30" depth x 18" height Material: Reinforced Cast stone (concrete). Anchors: concrete pavement mounting with 3/8"x2-1/4" HILTI KB-11-304-SSCF stainless steel expansion bolts W/ 3/8" HTN tamper proof nuts. SITE FURNISHINGS 12 93 00 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Basis of Design: Landscape Forms, Inc. Model: "Sicurta" Chair. Size: 21"w X 26"d X 32"h Material: Reinforced Cast stone (concrete). 2.2 BICYCLE RACK A. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: Basis of Design: Landscape Forms, Inc. Model "Bicilinea" Bicycle Rack". Size: 119 inches Length; 31-3/4 inches overall height. Material: - Horizontal tube: 3-5/16 inch dia x 0.08 inch wall thickness 304 stainless steel. - Curved tube: 2 inch dia x 0.08 inch wall thickness 304 stainless steel. - Vertical post: 3-1/8 inch x 5/8 inch 304 stainless steel flat bar. - Collar for curved tube connection: Nylon - Hardware: stainless steel Finish: Stainless Steel: Polished finish. Fasteners: Embedded: 59-3/4 inches depth 2.3 TRASH RECEPTACLES A. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: Basis of Design: Landscape Forms, Inc. Model "Lakeside" Litter Receptacle. Size: 36 inches height, 21 inches diameter. Side Opening: 20" diameter x 1- 1/4" tall at top of dome. Material: Top: spun 14 gauge spun steel. Liner: Constructed of linear low density polyethylene with 0.100" nominal wall thickness. - Body: Constructed of 10 gauge HRPO steel welded to a 2" tall toe ring. Capacity: Side -Opening Style, 30 Gallons. Pattern: Grass Pattern Fasteners: Surface Mount. Corrosion resistant bolts w/tamper proof nuts. Color: Powder coated silver. SITE FURNISHINGS 12 93 00 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Basis of Design: Landscape Forms, Inc. Model "Select" Litter Receptacle. Size: Triple Unit: Width: 50-3/8 inches, 42 inches height. Material: - Base: Welded carbon steel. Base is bolted to unit body with stainless steel 1/4-20 hex head screws. Unit body: Formed of 14 gauge carbon steel sheet. Door panel: Formed of 14 gauge carbon steel sheet with lock - Liner: Rotomolded low density polyethylene. Door opening trim and sign medallion: Cast 319 or A413 aluminum. Secured to door panel with black nylon cup washers and carbon steel #8- 32 x 1/4" socket button head cap screws with magni-coat. Vinyl graphics factory -applied to medallion. Adjustable glides: Black nylon base, 2-3/16" diameter, with 3/8-16 thread on stainless steel stem. - Hinge: Stainless steel hinges (2) per door, attached to door and unit body with stainless steel screws. - Cross braces, bin dividers: Carbon steel sheet. Bin dividers on double and triple units only. Fasteners: Surface Mount. Corrosion resistant bolts w/tamper proof nuts. Color: Carbon Steel. 2.4 MATERIALS A. Aluminum: Alloy and temper recommended by aluminum producer and finisher for type of use and finish indicated; free of surface blemishes and complying with the following: 1. Rolled or Cold -Finished Bars, Rods, and Wire: ASTM B 211 (ASTM B 211M). 2. Extruded Bars, Rods, Wire, Profiles, and Tubes: ASTM B 221 (ASTM B 221M). 3. Structural Pipe and Tube: ASTM B 429/B 429M. 4. Sheet and Plate: ASTM B 209 (ASTM B 209M). 5. Castings: ASTM B 26/B 26M. B. Steel and Iron: Free of surface blemishes and complying with the following: 1. Plates, Shapes, and Bars: ASTM A 36/A 36M. 2. Steel Pipe: Standard -weight steel pipe complying with ASTM A 53/A 53M, or electric - resistance -welded pipe complying with ASTM A 135/A 135M. 3. Tubing: Cold -formed steel tubing complying with ASTM A 500/A 500M. 4. Mechanical Tubing: Cold -rolled, electric -resistance -welded carbon or alloy steel tubing complying with ASTM A 513, or steel tubing fabricated from steel complying with ASTM A 1011/A 1011M and complying with dimensional tolerances in ASTM A 500/A 500M; zinc coated internally and externally. 5. Sheet. Commercial steel sheet complying with ASTM A 1011/A 1011M. 6. Perforated Metal: From steel sheet not less than 0.090 -inch (2.3 -mm) nominal thickness; manufacturer's standard perforation pattern. 7. Expanded Metal: Carbon -steel sheets, deburred after expansion, and complying with ASTM F 1267. SITE FURNISHINGS 12 93 00 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 8. Malleable -Iron Castings: ASTM A 47/A 47M, grade as recommended by fabricator for type of use intended. 9. Gray -Iron Castings: ASTM A 48/A 48M, Class 200. C. Stainless Steel: Free of surface blemishes and complying with the following: 1. Sheet, Strip, Plate, and Flat Bars: ASTM A 666. 2. Pipe: Schedule 40 steel pipe complying with ASTM A 312/A 312M. 3. Tubing: ASTM A 554. D. Fiberglass: Multiple laminations of glass -fiber -reinforced polyester resin with UV -light stable, colorfast, nonfading, weather- and stain -resistant, colored polyester gel coat, and with manufacturer's standard fmish. E. Plastic: Color impregnated, color and UV -light stabilized, and mold rests 1. Polyethylene: Fabricated from virgin plastic HDPE resin. 2. Recycled Content of Polyethylene: Postconsumer recycled content plus one-half of preconsumer recycled content not less than 25 percent. F. Anchors, Fasteners, Fittings, and Hardware: Stainless steel, commercial quality, tamperproof, vandal and theft resistant. G. Nonshrink, Nonmetallic Grout: Premixed, factory -packaged, nonstaining, noncorrosive, nongaseous grout complying with ASTM C 1107/C 1107M; recommended in writing by manufacturer, for exterior applications. H. Erosion -Resistant Anchoring Cement: Factory -packaged, nonshrink, nonstaining, hydraulic - controlled expansion cement formulation for mixing with potable water at Project site to create pourable anchoring, patching, and grouting compound; resistant to erosion from water exposure without needing protection by a sealer or waterproof coating; recommended in writing by manufacturer, for exterior applications. I. Galvanizing: Where indicated for steel and iron components, provide the following protective zinc coating applied to components after fabrication: 1. Zinc -Coated Tubing: External, zinc with organic overcoat, consisting of a minimum of 0.9 oz./sq. ft. (0.27 kg/sq. m) of zinc after welding, a chromate conversion coating, and a clear, polymer film. Internal, same as external or consisting of 81 percent zinc pigmented coating, not less than 0.3 mil (0.0076 mm) thick. 2. Hot -Dip Galvanizing. According to ASTM A 123/A 123M, ASTM A 153/A 153M, or ASTM A 924/A 924M. J. Cast stone (concrete): Manufacturer's proprietary blend of portland cement, sand, aggregate, and color admixture. 1. Use only one brand, type and source of cement for entire Project. 2. Provide integral colored concrete with lightfast (UV and fade resistant) color pigments. 3. Water: Clean and potable. SITE FURNISHINGS 12 93 00 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.5 GENERAL FINISH REQUIREMENTS A. Appearance of Finished Work: Noticeable variations in same piece are not acceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast. 2.6 ALUMINUM FINISHES A. Baked -Enamel, Powder -Coat Finish: Manufacturer's standard, baked, polyester, powder -coat finish complying with finish manufacturer's written instructions for surface preparation, including pretreatment, application, baking, and minimum dry film thickness. 2.7 STEEL AND GALVANIZED -STEEL FINISHES A. Baked -Enamel, Powder -Coat Finish: Manufacturer's standard, baked, polyester, powder -coat finish complying with fmish manufacturer's written instructions for surface preparation, including pretreatment, application, baking, and minimum dry film thickness. B. PVC Finish: Manufacturer's standard, UV -light stabilized, mold -resistant, slip -resistant, matte - textured, dipped or sprayed -on, PVC-plastisol finish, with flame retardant added; complying with coating manufacturer's written instructions for pretreatment, application, and minimum dry film thickness. 2.8 IRON FINISHES A. Baked -Enamel, Powder -Coat Finish: Manufacturer's standard, baked, polyester, powder -coat fmish complying with finish manufacturer's written instructions for surface preparation, including pretreatment, application, baking, and minimum dry film thickness. 2.9 STAINLESS-STEEL FINISHES A. Surface Preparation: Remove tool and die marks and stretch lines, or blend into fmish. B. Polished Finishes: Grind and polish surfaces to produce uniform finish, free of cross scratches. 1. Run directional finishes with long dimension of each piece. 2. Directional Satin Finish: No 4. 3. Dull Satin Finish: No. 6. 2.10 CAST STONE (CONCRETE) FINISHES A. Formwork: Fabricate forms sufficiently rigid to meet casting tolerances. Coat formwork with form release agent. B. Casting: Fabricate units to required profiles and sizes. Execute work accurately to specified tolerances and free of broken edges. SITE FURNISHINGS 12 93 00 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Curing: Protect units from exposure to weather until concrete strength is adequate for form removal. Cure under identical conditions. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine areas and conditions, with Installer present, for compliance with requirements for correct and level finished grade, mounting surfaces, installation tolerances, and other conditions affecting performance of the Work. B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION, GENERAL A. Comply with manufacturer's written installation instructions unless more stringent requirements are indicated. Complete field assembly of site furnishings where required. B. Unless otherwise indicated, install site furnishings after landscaping and paving have been completed. C. Install site furnishings level, plumb, true, and securely anchored at locations indicated on Drawings. D. Post Setting: Set cast -in support posts in concrete footing with smooth top, shaped to shed water. Protect portion of posts above footing from concrete splatter. Verify that posts are set plumb or at correct angle and are aligned and at correct height and spacing. Hold posts in position during placement and finishing operations until concrete is sufficiently cured. E. Posts Set into Voids in Concrete: Form or core -drill holes for installing posts in concrete to depth recommended in writing by manufacturer of site furnishings and 3/4 inch (19 mm) larger than OD of post. Clean holes of loose material, insert posts, and fill annular space between post and concrete with nonshrink, nonmetallic grout, mixed and placed to comply with anchoring material manufacturer's written instructions, with top smoothed and shaped to shed water. F. Pipe Sleeves: Use steel pipe sleeves preset and anchored into concrete for installing posts. After posts have been inserted into sleeves, fill annular space between post and sleeve with nonshrink, nonmetallic grout, mixed and placed to comply with anchoring material manufacturer's written instructions, with top smoothed and shaped to shed water. 3.3 ADJUSTING A. Finish Damage: Contact manufacturer for assistance to repair minor damages to fmish as approved by Architect. SITE FURNISHINGS 12 93 00 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.4 CLEANING A. Clean benches promptly after installation in accordance with manufacturer's instructions. B. Do not use harsh cleaning materials or methods that could damage finish. 3.5 PROTECTION A. Protect installed site furniture to ensure that, except for normal weathering, they will be without damage or deterioration at time of Substantial Completion. END OF SECTION 12 93 00 SITE FURNISHINGS 12 93 00 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 210500 - COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Piping materials and installation instructions common to most piping systems. 2. Mechanical sleeve seals. 3. Sleeves. 4. Escutcheons. 5. Grout. 6. Painting and finishing. 7. Supports and anchorages. 1.3 DEFINITIONS A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe chases, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels. B. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms. C. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations. D. Concealed, Interior Installations: Concealed from view and protected from physical contact by building occupants. Examples include above ceilings and in chases. E. Concealed, Exterior Installations: Concealed from view and protected from weather conditions and physical contact by building occupants but subject to outdoor ambient temperatures. Examples include installations within unheated shelters. F. The following are industry abbreviations for plastic materials: 1. CPVC: Chlorinated polyvinyl chloride plastic. G. The following are industry abbreviations for rubber materials: 1. EPDM: Ethylene -propylene -diene terpolymer rubber. 2. NBR: Acrylonitrile -butadiene rubber. COMMON WORK RESULTS FOR FIRE SUPPRESSION 210500 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.4 SUBMITTALS A. Product Data. B. Welding certificates. 1.5 QUALITY ASSURANCE A. Steel Support Welding: Qualify processes and operators according to AWS D1.1, "Structural Welding Code --Steel." B. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications." Comply with provisions in ASME B31 Series, "Code for Pressure Piping." Certify that each welder has passed AWS qualification tests for welding processes involved and that certification is current. 1.6 DELIVERY, STORAGE, AND HANDLING A. Deliver pipes and tubes with factory -applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and moisture. B. Store plastic pipes protected from direct sunlight. Support to prevent sagging and bending. 1.7 COORDINATION Arrange for pipe spaces, chases, slots, and openings in building structure during progress of construction, to allow for fire -suppression installations. B. Coordinate installation of required supporting devices and set sleeves in poured -in-place concrete and other structural components as they are constructed. C. Coordinate requirements for access panels and doors for fire -suppression items requiring access that are concealed behind finished surfaces. Access panels and doors are specified in Division 08 Section "Access Doors and Frames." PART 2 - PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where subparagraph titles below introduce lists, the following requirements apply for product selection: 1. Manufacturers: Subject to compliance with requirements, provide products by the manufacturers specified. COMMON WORK RESULTS FOR FIRE SUPPRESSION 210500 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.2 PIPE, TUBE, AND FITTINGS A. Refer to individual Division 21 piping Sections for pipe, tube, and fitting materials and joining methods. B. Pipe Threads: ASME B1.20.1 for factory -threaded pipe and pipe fittings. 2.3 JOINING MATERIALS A. Refer to individual Division 21 piping Sections for special joining materials not listed below. B. Pipe -Flange Gasket Materials: Suitable for chemical and thermal conditions of piping system contents. 1. ASME B16.21, nonmetallic, flat, asbestos -free, 1/8 -inch maximum thickness unless thickness or specific material is indicated. a. Full -Face Type: For flat -face, Class 125, cast-iron and cast -bronze flanges. b. Narrow -Face Type: For raised -face, Class 250, cast-iron and steel flanges. 2. AWWA C110, rubber, flat face, 1/8 inch thick, unless otherwise indicated; and full -face or ring type, unless otherwise indicated. C. Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless otherwise indicated. D. Welding Filler Metals: Comply with AWS D10.12 for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded. 2.4 MECHANICAL SLEEVE SEALS A. Description: Modular sealing element unit, designed for field assembly, to fill annular space between pipe and sleeve. Manufacturers: a. Advance Products & Systems, Inc. b. Calpico, Inc. c. Metraflex Co. d. Pipeline Seal and Insulator, Inc 2. Sealing Elements: EPDM interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe. 3. Pressure Plates: Carbon steel or Stainless steel. Include two for each sealing element. 4. Connecting Bolts and Nuts: Carbon steel with corrosion -resistant coating or Stainless steel of length required to secure pressure plates to sealing elements. Include one for each sealing element. 2.5 SLEEVES A. Steel Pipe: ASTM A 53, Type E, Grade B, Schedule 40, galvanized, plain ends. COMMON WORK RESULTS FOR FIRE SUPPRESSION 210500 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Cast Iron: Cast or fabricated "wall pipe" equivalent to ductile -iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated. C. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange. Include clamping ring and bolts and nuts for membrane flashing. Underdeck Clamp: Clamping ring with set screws. 2.6 PIPING ESCUTCHEONS Description: Manufactured wall and ceiling escutcheons and floor plates, with an ID to closely fit around pipe, tube, and insulation of insulated piping and an OD that completely covers opening. B. One -Piece, Cast -Brass Type: With set screw. 1. Finish: Polished chrome -plated. C. Split -Casting, Cast -Brass Type: With concealed hinge and set screw. 1. Finish: Polished chrome -plated. 2.7 GROUT A. Description: ASTM C 1107, Grade B, nonshrink and nonmetallic, dry hydraulic -cement grout. 1. Characteristics: Post -hardening, volume -adjusting, nonstaining, noncorrosive, nongaseous, and recommended for interior and exterior applications. 2. Design Mix: 5000 -psi, 28 -day compressive strength. 3. Packaging: Premixed and factory packaged. PART 3 - EXECUTION 3.1 PIPING SYSTEMS - COMMON REQUIREMENTS A. Install piping according to the following requirements and Division 21 Sections specifying piping systems. B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, pump sizing, and other design considerations. Install piping as indicated unless deviations to layout are approved on Coordination Drawings. C. Install piping in concealed locations, unless otherwise indicated and except in equipment rooms and service areas. D. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise. COMMON WORK RESULTS FOR FIRE SUPPRESSION 210500 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS E. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal. F. Install piping to permit valve servicing. G. Install piping at indicated slopes. I -I. Install piping free of sags and bends. I. Install fittings for changes in direction and branch connections. J. Install piping to allow application of insulation. K. Select system components with pressure rating equal to or greater than system operating pressure. L. Install escutcheons for penetrations of walls, ceilings, and floors according to the following: 1. New Piping: a. Bare Piping at Wall Ceiling and Floor Penetrations in Finished Spaces: One-piece, cast -brass type with polished chrome -plated finish. M. Permanent sleeves are not required for holes formed by removable PE sleeves. N. Install sleeves for pipes passing through concrete and masonry walls, gypsum -board partitions, and concrete floor and roof slabs. 1. Cut sleeves to length for mounting flush with both surfaces. a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches above finished floor level. Extend cast-iron sleeve fittings below floor slab as required to secure clamping ring if ring is specified. 2. Install sleeves in new walls and slabs as new walls and slabs are constructed. 3. Install sleeves that are large enough to provide 1/4 -inch annular clear space between sleeve and pipe or pipe insulation. Use the following sleeve materials: a. Steel Pipe Sleeves. b. Stack Sleeve Fittings: For pipes penetrating floors with membrane waterproofing. Secure flashing between clamping flanges. Install section of cast-iron soil pipe to extend sleeve to 2 inches above finished floor level. Refer to Division 07 Section "Sheet Metal Flashing and Trim" for flashing. 1) Seal space outside of sleeve fittings with grout. 4. Except for underground wall penetrations, seal annular space between sleeve and pipe or pipe insulation, using joint sealants appropriate for size, depth, and location of joint. Refer to Division 07 Section "Joint Sealants" for materials and installation. O. Aboveground, Exterior -Wall Pipe Penetrations: Seal penetrations using sleeves and mechanical sleeve seals. Select sleeve size to allow for 1 -inch annular clear space between pipe and sleeve for installing mechanical sleeve seals. COMMON WORK RESULTS FOR FIRE SUPPRESSION 210500 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Install steel pipe for sleeves smaller than 6 inches in diameter. 2. Install cast-iron "wall pipes" for sleeves 6 inches and larger in diameter. 3. Mechanical Sleeve Seal Installation: Select type and number of sealing elements required for pipe material and size. Position pipe in center of sleeve. Assemble mechanical sleeve seals and install in annular space between pipe and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal. P. Fire -Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Refer to Division 07 Section "Penetration Firestopping" for materials. Q. Verify final equipment locations for roughing -in. R. Refer to equipment specifications in other Sections of these Specifications for roughing -in requirements. 3.2 PIPING JOINT CONSTRUCTION A. Join pipe and fittings according to the following requirements and Division 21 Sections specifying piping systems. B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe. C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly. D. Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to tube end. Construct joints according to ASTM B 828 or CDA's "Copper Tube Handbook," using lead- free solder alloy complying with ASTM B 32. E. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows: 1. Apply appropriate tape or thread compound to external pipe threads unless dry seal threading is specified. 2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds. F. Welded Joints: Construct joints according to AWS D10.12, using qualified processes and welding operators according to Part 1 "Quality Assurance" Article. G. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service application. Install gasket concentrically positioned. Use suitable lubricants on bolt threads. 3.3 PAINTING A. Painting of fire -suppression systems, equipment, and components is specified in Division 09 Sections "Interior Painting" and "Exterior Painting." B. Damage and Touchup: Repair marred and damaged factory -painted finishes with materials and procedures to match original factory finish. COMMON WORK RESULTS FOR FIRE SUPPRESSION 210500 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.4 ERECTION OF METAL SUPPORTS AND ANCHORAGES A. Refer to Division 05 Section "Metal Fabrications" for structural steel. B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor fire -suppression materials and equipment. C. Field Welding: Comply with AWS D1.1. 3.5 GROUTING A. Mix and install grout for fire -suppression equipment base bearing surfaces, pump and other equipment base plates, and anchors. B. Clean surfaces that will come into contact with grout. C. Provide forms as required for placement of grout. D. Avoid air entrapment during placement of grout. E. Place grout, completely filling equipment bases. F. Place grout on concrete bases and provide smooth bearing surface for equipment. G. Place grout around anchors. H. Cure placed grout. END OF SECTION 210500 COMMON WORK RESULTS FOR FIRE SUPPRESSION 210500 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 211313 - WET -PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire -protection valves. 3. Fire -department connections. 4. Sprinklers. 1.3 DEFINITIONS Standard -Pressure Sprinkler Piping: Wet -pipe sprinkler system piping designed to operate at working pressure of 175 psig maximum. 1.4 SYSTEM DESCRIPTIONS A. Wet -Pipe Sprinkler System: Automatic sprinklers are attached to piping containing water and that is connected to water supply through alarm valve. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device. Hose connections are included if indicated. 1.5 PERFORMANCE REQUIREMENTS A. Standard -Pressure Piping System Component: Listed for 175-psig minimum working pressure. B. Sprinkler system shall be approved by authorities having jurisdiction. 1. Margin of Safety for Available Water Flow and Pressure: 10 P.S.I. 2. Sprinkler Occupancy Hazard Classifications refer to drawings. 1.6 SUBMITTALS A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories. B. Shop Drawings: For wet -pipe sprinkler systems. Include plans, elevations, sections, details, and attachments to other work. WET -PIPE SPRINKLER SYSTEMS 211313 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Hydraulic Calculations. 1.7 QUALITY ASSURANCE A. Installer Qualifications: 1. Installer's responsibilities include fabricating, and installing sprinkler systems and providing working plans per NFPA 13. Base calculations on results of fire -hydrant flow test. B. Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code. C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. D. NFPA Standards: Sprinkler system equipment, specialties, accessories, installation, and testing shall comply with the following: 1. NFPA 13, "Installation of Sprinkler Systems." 2. NFPA 24, "Installation of Private Fire Service Mains and Their Appurtenances." 1.8 COORDINATION A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including light fixtures, HVAC equipment, and partition assemblies. PART 2 - PRODUCTS 2.1 STEEL PIPE AND FITTINGS A. Standard Weight, Black -Steel Pipe: ASTM A 53/A 53M or ASTM A 135. B. Piping Schedule shall be: All piping with threaded fittings shall be schedule 40 and all piping with grooved fittings shall be schedule 10. C. Galvanized- and Black -Steel Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M, standard -weight, seamless steel pipe with threaded ends. D. Galvanized and Uncoated, Steel Couplings: ASTM A 865, threaded. E. Galvanized and Uncoated, Gray -Iron Threaded Fittings: ASME B16.4, Class 125, standard pattern. F. Grooved -Joint, Steel -Pipe Appurtenances: Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Tyco Fire & Building Products LP. WET -PIPE SPRINKLER SYSTEMS 211313 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS b. Victaulic Company. c. Anvil Star Piping Inc. 2. Pressure Rating: 175 psig unless otherwise noted. 3. Galvanized and Uncoated, Grooved -End Fittings for Steel Piping: ASTM A 47/A 47M, malleable -iron casting or ASTM A 536, ductile -iron casting; with dimensions matching steel pipe. 4. Grooved -End -Pipe Couplings for Steel Piping: AWWA C606 and UL 213, rigid pattern, unless otherwise indicated, for steel -pipe dimensions. Include ferrous housing sections, EPDM-rubber gasket, and bolts and nuts. 2.2 PIPING JOINING MATERIALS A. Pipe -Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch thick or ASME B16.21, nonmetallic and asbestos free. 1. Class 125, Cast -Iron Flanges and Class 150, Bronze Flat -Face Flanges: Full -face gaskets. 2. Class 250, Cast -Iron Flanges and Class 300, Steel Raised -Face Flanges: Ring -type gaskets. Metal, Pipe -Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise indicated. C. Brazing Filler Metals: AWS A5.8/A5.8M, BCuP Series, copper -phosphorus alloys for general - duty brazing unless otherwise indicated. D. Welding Filler Metals: Comply with AWS D10.12M/D10.12 for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded. 2.3 LISTED FIRE -PROTECTION VALVES A. General Requirements: 1. Valves shall be UL listed or FM approved. 2. Minimum Pressure Rating for Standard -Pressure Piping: 175 psig. 3. Minimum Pressure Rating for High -Pressure Piping: 300 psig. B. Ball Valves: 1. Standard: UL 1091 except with ball instead of disc. 2. Valves NPS 1-1/2 and Smaller: Bronze body with threaded ends. 3. Valves NPS 2 and NPS 2-1/2: Bronze body with threaded ends or ductile -iron body with grooved ends. 4. Valves NPS 3: Ductile -iron body with grooved ends. C. Check Valves: 1. Standard: UL 312. 2. Pressure Rating: 300 psig. 3. Type: Swing check. 4. Body Material: Cast iron. 5. End Connections: Flanged or grooved. WET -PIPE SPRINKLER SYSTEMS 211313 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D, Iron Butterfly Valves: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Anvil International, Inc. b. Tyco Fire & Building Products LP. c. Victaulic Company. 2. Standard: UL 1091. 3. Pressure Rating: 175 psig. 4. Body Material: Cast or ductile iron. 5. Style: Lug or wafer. 6. End Connections: Grooved. 2.4 FIRE -DEPARTMENT CONNECTIONS A. Fire -Department Connection: Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Fire -End & Croker Corporation. b. Tyco Fire & Building Products LP c. Potter Roemer d. Elkhart Brass 2. Standard: UL 405. 3. Type: As indicated on drawings. 4. Pressure Rating: 175 psig minimum. 5. Body Material: Corrosion -resistant metal. 6. Inlets: Threads according to NFPA 1963 and matching local fire -department sizes and threads. Include extension pipe nipples, lugged swivel connections, and check devices or clappers. 7. Caps: Lugged type, with gasket and chain. 2.5 SPRINKLERS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the work include, but are not limited to, the following: 1. Reliable Automatic Sprinkler Co., Inc. 2. Tyco Fire & Building Products LP. 3. Victaulic Company. 4. Viking Corporation. B. General Requirements: 1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing. 2. Pressure Rating for Automatic Sprinklers: 175 psig minimum. 3. Refer to drawings for sprinkler types and applicable locations. WET -PIPE SPRINKLER SYSTEMS 211313 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.6 GROUT A. Standard: ASTM C 1107, Grade B, posthardening and volume adjusting, dry, hydraulic -cement grout. B. Characteristics: Nonshrink, and recommended for interior and exterior applications. C. Design Mix: 5000 -psi, 28 -day compressive strength. D. Packaging: Premixed and factory packaged. PART 3 - EXECUTION 3.1 PREPARATION Perform fire -hydrant flow test according to NFPA 13 and NFPA 291. Use results for system design calculations required in "Quality Assurance" Article. B. Report test results promptly and in writing. 3.2 SERVICE -ENTRANCE PIPING A. Connect sprinkler piping to water -service piping for service entrance to building. B. Install shutoff valve, backflow preventer, pressure gage, drain, and other accessories indicated at connection to water -service piping. 3.3 PIPING INSTALLATION A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and arrangement of piping. Install piping as indicated, as far as practical. 1. Deviations from approved working plans for piping require written approval from authorities having jurisdiction. File written approval with Architect before deviating from approved working plans. Piping Standard: Comply with requirements for installation of sprinkler piping in NFPA 13. C. Use listed fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes. D. Install unions adjacent to each valve in pipes NPS 2 and smaller. E. Install flanges, flange adapters, or couplings for grooved -end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections. F. Install "Inspector's Test Connections" in sprinkler system piping, complete with shutoff valve, and sized and located according to NFPA 13. G. Install sprinkler piping with drains for complete system drainage. WET -PIPE SPRINKLER SYSTEMS 211313 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS H. Install sprinkler control valves, test assemblies, and drain risers adjacent to standpipes when sprinkler piping is connected to standpipes. I. Install automatic (ball drip) drain valve at each check valve for fire -department connection, to drain piping between fire -department connection and check valve. Install drain piping to and spill over floor drain or to outside building. J. Install alarm devices in piping systems. K. Install hangers and supports for sprinkler system piping according to NFPA 13. Comply with requirements for hanger materials in NFPA 13. Powder driven inserts are not allowed. L. Install pressure gages on riser or feed main, at each sprinkler test connection, and at top of each standpipe. Include pressure gages with connection not less than NPS 1/4 and with soft metal seated globe valve, arranged for draining pipe between gage and valve. Install gages to permit removal, and install where they will not be subject to freezing. M. Pressurize and check preaction sprinkler system piping and air -pressure maintenance devices. N. Fill sprinkler system piping with water. 3.4 JOINT CONSTRUCTION A. Install couplings, flanges, flanged fittings, unions, nipples, and transition and special fittings that have finish and pressure ratings same as or higher than system's pressure rating for aboveground applications unless otherwise indicated. B. Install unions adjacent to each valve in pipes NPS 2 and smaller. C. Install flanges, flange adapters, or couplings for grooved -end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections. D. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe. E. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and fittings before assembly. F. Flanged Joints: Select appropriate gasket material in size, type, and thickness suitable for water service. Join flanges with gasket and bolts according to ASME B31.9. G. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows: 1. Apply appropriate tape or thread compound to external pipe threads. 2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. H. Welded Joints: Construct joints according to AWS D10.12M/D10.12, using qualified processes and welding operators according to "Quality Assurance" Article. Shop weld pipe joints where welded piping is indicated. Do not use welded joints for galvanized -steel pipe. WET -PIPE SPRINKLER SYSTEMS 211313 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS I. Steel -Piping, Roll -Grooved Joints: Roll rounded -edge groove in end of pipe according to AWWA C606. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved -end fittings according to AWWA C606 for steel -pipe grooved joints. J. Dissimilar -Material Piping Joints: Make joints using adapters compatible with materials of both piping systems. 3.5 VALVE AND SPECIALTIES INSTALLATION A. Install listed fire -protection valves, trim and drain valves, specialty valves and trim, controls, and specialties according to NFPA 13 and authorities having jurisdiction. B. Install listed fire -protection shutoff valves supervised open, located to control sources of water supply except from fire -department connections. Install permanent identification signs indicating portion of system controlled by each valve. C. Install check valve in each water -supply connection. Install backflow preventers instead of check valves in potable -water -supply sources. D. Specialty Valves: 1. General Requirements: Install in vertical position for proper direction of flow, in main supply to system. 2. Alarm Valves: Include bypass check valve and retarding chamber drain -line connection. 3.6 SPRINKLER INSTALLATION A. Install sprinklers in suspended ceilings in center of acoustical ceiling panels. Sprinklers may be centered in tile either by hard pipe or with flexible connectors. Connectors shall be UL 2443 listed, Flex Heads Industries or equal. B. Sprinkler Head Location: Sprinkler heads shall be installed no closer than 4 inches to any Ceiling grid or wall. C. Install dry -type sprinklers with water supply from heated space. Do not install pendent or sidewall, wet -type sprinklers in areas subject to freezing. 3.7 ESCUTCHEON INSTALLATION A. Install escutcheons for penetrations of walls, ceilings, and floors. B. Escutcheons for Piping: 1. Piping with Fitting or Sleeve Protruding from Wall: deep pattern. 2. Bare Piping at Wall and Floor Penetrations in Finished Spaces: cast brass with polished chrome -plated finish. 3. Bare Piping at Ceiling Penetrations in Finished Spaces cast brass with polished chrome - plated finish. WET -PIPE SPRINKLER SYSTEMS 211313 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.8 SLEEVE INSTALLATION A. General Requirements: Install sleeves for pipes and tubes passing through penetrations in floors, partitions, roofs, and walls. B. Sleeves are not required for core -drilled holes. C. Permanent sleeves are not required for holes formed by removable PE sleeves. D. Cut sleeves to length for mounting flush with both surfaces unless otherwise indicated. E. Install sleeves in new partitions, slabs, and walls as they are built. F. For interior wall penetrations, seal annular space between sleeve and pipe or pipe insulation using joint sealants appropriate for size, depth, and location of joint. Comply with requirements for joint sealants in Division 07 Section "Joint Sealants." G. For exterior wall penetrations above grade, seal annular space between sleeve and pipe using joint sealants appropriate for size, depth, and location of joint. Comply with requirements for joint sealants in Division 07 Section "Joint Sealants." H. For exterior wall penetrations below grade, seal annular space between sleeve and pipe using sleeve seals. I. Seal space outside of sleeves in concrete slabs and walls with grout. J. Install sleeves that are large enough to provide 1/4 -inch annular clear space between sleeve and pipe or pipe insulation unless otherwise indicated. K. Install sleeve materials according to the following applications: Sleeves for Piping Passing through Concrete Floor Slabs of Mechanical Equipment Areas or Other Wet Areas: Stack sleeve fittings. a. Extend sleeves 2 inches above finished floor level. b. For pipes penetrating floors with membrane waterproofing, extend cast-iron sleeve fittings below floor slab as required to secure clamping ring if ring is specified. Secure flashing between clamping flanges. Install section of cast-iron soil pipe to extend sleeve to 2 inches above finished floor level. Comply with requirements for flashing in Division 07 Section "Sheet Metal Flashing and Trim." 2. Sleeves for Piping Passing through Gypsum -Board Partitions: a. Galvanized -steel -sheet sleeves for pipes NPS 6 and larger. b. Exception: Sleeves are not required for water -supply tubes and waste pipes for individual plumbing fixtures if escutcheons will cover openings. 3. Sleeves for Piping Passing through Concrete Roof Slabs: Molded PVC. 4. Sleeves for Piping Passing through Exterior Concrete Walls: a. Galvanized -steel -pipe sleeves for pipes smaller than NPS 6. b. Cast-iron wall pipe sleeves for pipes NPS 6 and larger. WET -PIPE SPRINKLER SYSTEMS 211313 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS c. Install sleeves that are large enough to provide 1 -inch annular clear space between sleeve and pipe or pipe insulation when sleeve seals are used. d. All exterior sleeves shall be sealed water tight. 5. Sleeves for Piping Passing through Interior Concrete Walls: a. PVC -pipe sleeves for pipes smaller than NPS 6. b. Galvanized -steel -sheet sleeves for pipes NPS 6 and larger. L. Fire -Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for firestop materials and installations in Division 07 Section 'Penetration Firestopping." 3.9 IDENTIFICATION A. Install labeling and pipe markers on equipment and piping according to requirements in NFPA 13. B. Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Division 26 Section "Identification for Electrical Systems." 3.10 FIELD QUALITY CONTROL A. Perform tests and inspections. B. Tests and Inspections: 1. Leak Test: After installation, charge systems and test for leaks. Repair leaks and retest until no leaks exist. 2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. 3. Flush, test, and inspect sprinkler systems according to NFPA 13, "Systems Acceptance" Chapter. 4. Energize circuits to electrical equipment and devices. 5. Coordinate with fire -alarm tests. Operate as required. 6. Verify that equipment hose threads are same as local fire -department equipment. C. Sprinkler piping system will be considered defective if it does not pass tests and inspections. D. Prepare test and inspection reports. END OF SECTION 211313 WET -PIPE SPRINKLER SYSTEMS 211313 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 220500 - COMMON WORK RESULTS FOR PLUMBING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Piping materials and installation instructions common to most piping systems. 2. Transition fittings. 3. Dielectric fittings. 4. Sleeves. 5. Escutcheons. 6. Grout. 7. Equipment installation requirements common to equipment sections. 8. Painting and finishing. 9. Concrete bases. 10. Supports and anchorages. 1.3 DEFINITIONS Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe chases, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels. B. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms. C. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations. D. Concealed, Interior Installations: Concealed from view and protected from physical contact by building occupants. Examples include above ceilings and in chases. E. The following are industry abbreviations for plastic materials: 1. CPVC: Chlorinated polyvinyl chloride plastic. 2. PE: Polyethylene plastic. 3. PVC: Polyvinyl chloride plastic. 1.4 SUBMITTALS A. Product Data: For the following: COMMON WORK RESULTS FOR PLUMBING 220500 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Transition fittings. 2. Dielectric fittings. 3. Escutcheons. 1.5 QUALITY ASSURANCE A. Steel Support Welding: Qualify processes and operators according to AWS D1.1, "Structural Welding Code --Steel." B. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications." 1. Comply with provisions in ASME B31 Series, "Code for Pressure Piping." 2. Certify that each welder has passed AWS qualification tests for welding processes involved and that certification is current. C. Electrical Characteristics for Plumbing Equipment: Equipment of higher electrical characteristics may be furnished provided such proposed equipment is approved in writing and connecting electrical services, circuit breakers, and conduit sizes are appropriately modified. If minimum energy ratings or efficiencies are specified, equipment shall comply with requirements. 1.6 DELIVERY, STORAGE, AND HANDLING A. Deliver pipes and tubes with factory -applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and moisture. Store plastic pipes protected from direct sunlight. Support to prevent sagging and bending. 1.7 COORDINATION A. Arrange for pipe spaces, chases, slots, and openings in building structure during progress of construction, to allow for plumbing installations. B. Coordinate installation of required supporting devices and set sleeves in poured -in-place concrete and other structural components as they are constructed. C. Coordinate requirements for access panels and doors for plumbing items requiring access that are concealed behind finished surfaces. Access panels and doors are specified in Division 08 Section "Access Doors and Frames." PART 2 - PRODUCTS 2.1 PIPE, TUBE, AND FITTINGS A. Refer to individual Division 22 piping Sections for pipe, tube, and fitting materials and joining methods. B. Pipe Threads: ASME B1.20.1 for factory -threaded pipe and pipe fittings. COMMON WORK RESULTS FOR PLUMBING 220500 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.2 JOINING MATERIALS A. Refer to individual Division 22 piping Sections for special joining materials not listed below. B. Pipe -Flange Gasket Materials: Suitable for chemical and thermal conditions of piping system contents. 1. ASME B16.21, nonmetallic, flat, asbestos -free, 1/8 -inch maximum thickness unless thickness or specific material is indicated. a. Full -Face Type: For flat -face, Class 125, cast-iron and cast -bronze flanges. b. Narrow -Face Type: For raised -face, Class 250, cast-iron and steel flanges. 2. AWWA C110, rubber, flat face, 1/8 inch thick, unless otherwise indicated; and full -face or ring type, unless otherwise indicated. C. Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless otherwise indicated. D. Solder Filler Metals: ASTM B 32, lead-free alloys. Include water-flushable flux according to ASTM B 813. E. Solvent Cements for Joining Plastic Piping: 1. CPVC Piping: ASTM F 493. 2. PVC Piping: ASTM D 2564. Include primer according to ASTM F 656. 2.3 TRANSITION FITTINGS AWWA Transition Couplings: Same size as, and with pressure rating at least equal to and with ends compatible with, piping to be joined. 1. Underground Piping NPS 2 and Larger AWWA C219, metal sleeve -type coupling. B. Flexible Transition Couplings for Underground Nonpressure Drainage Piping: ASTM C 1173 with elastomeric sleeve, ends same size as piping to be joined, and corrosion -resistant metal band on each end. 2.4 DIELECTRIC FITTINGS A. Description: Combination fitting of copper alloy and ferrous materials with threaded, solder - joint, plain, or weld -neck end connections that match piping system materials. B. Insulating Material: Suitable for system fluid, pressure, and temperature. C. Dielectric Unions: Factory -fabricated, union assembly, for 250-psig minimum working pressure at 180 deg F. D. Dielectric -Flange Kits: Companion -flange assembly for field assembly. Include flanges, full- face- or ring -type neoprene or phenolic gasket, phenolic or polyethylene bolt sleeves, phenolic washers, and steel backing washers. Separate companion flanges and steel bolts and nuts shall have 150- or 300-psig minimum working pressure where required to suit system pressures. COMMON WORK RESULTS FOR PLUMBING 220500 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS E. Dielectric Couplings: Galvanized -steel coupling with inert and noncorrosive, thermoplastic lining; threaded ends; and 300-psig minimum working pressure at 225 deg F. 2.5 SLEEVES A. Steel Pipe: ASTM A 53, Type E, Grade B, Schedule 40, galvanized, plain ends. 2.6 ESCUTCHEONS A. Description: Manufactured wall and ceiling escutcheons and floor plates, with an ID to closely fit around pipe, tube, and insulation of insulated piping and an OD that completely covers opening. B. One -Piece, Deep -Pattern Type: Deep -drawn, box -shaped brass with polished chrome -plated finish. C. One -Piece, Cast -Brass Type: With set screw. 1. Finish: Polished chrome -plated and rough brass. 2.7 GROUT A. Description: ASTM C 1107, Grade B, nonshrink and nonmetallic, dry hydraulic -cement grout. 1. Characteristics: Post -hardening, volume -adjusting, nonstaining, noncorrosive, nongaseous, and recommended for interior and exterior applications. 2. Design Mix: 5000 -psi, 28 -day compressive strength. 3. Packaging: Premixed and factory packaged. PART 3 - EXECUTION 3.1 PIPING SYSTEMS - COMMON REQUIREMENTS A. Install piping according to the following requirements and Division 22 Sections specifying piping systems. B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, pump sizing, and other design considerations. Install piping as indicated unless deviations to layout are approved on Coordination Drawings. C. Install piping in concealed locations, unless otherwise indicated and except in equipment rooms and service areas. D. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise. E. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal. COMMON WORK RESULTS FOR PLUMBING 220500 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS F. Install piping to permit valve servicing. Valves located above ceilings shall be positioned no further than arms length away from accessible ceiling opening. G. Install piping at indicated slopes. H. Install piping free of sags and bends. I. Install fittings for changes in direction and branch connections. J. Install piping to allow application of insulation. K. Select system components with pressure rating equal to or greater than system operating pressure. L. Install escutcheons for penetrations of walls, ceilings, and floors according to the following: New Piping: a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep -pattern type. b. Chrome -Plated Piping: One-piece, cast -brass type with polished chrome -plated finish. c. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece, cast - brass type with polished chrome -plated finish. d. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece, cast -brass type with polished chrome -plated finish. M. Install sleeves for pipes passing through concrete and masonry walls and concrete floor and roof slabs. Install sleeves for pipes passing through concrete and masonry walls, gypsum -board partitions, and concrete floor and roof slabs. Cut sleeves to length for mounting flush with both surfaces. a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches above finished floor level. Extend cast-iron sleeve fittings below floor slab as required to secure clamping ring if ring is specified. 2. Install sleeves in new walls and slabs as new walls and slabs are constructed. 3. Install sleeves that are large enough to provide 1/4 -inch annular clear space between sleeve and pipe or pipe insulation. Use the following sleeve materials: a. Steel Pipe Sleeves: For pipes smaller than NPS 6. b. Steel Sheet Sleeves: For pipes NPS 6 and larger, penetrating gypsum -board partitions. 4. Except for underground wall penetrations, seal annular space between sleeve and pipe or pipe insulation, using joint sealants appropriate for size, depth, and location of joint. Refer to Division 07 Section "Joint Sealants" for materials and installation. O. Fire -Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Refer to Division 07 Section "Penetration Firestopping" for materials. P. Verify final equipment locations for roughing -in. COMMON WORK RESULTS FOR PLUMBING 220500 - 5 INDIAN RIVER COUNTY INTERGENERATIONAL RECREATION CENTER Q. Refer to equipment specifications in requirements. JULY 25, 2014 100% CONSTRUCTION DOCUMENTS other Sections of these Specifications for roughing -in 3.2 PIPING JOINT CONSTRUCTION A. Join pipe and fittings according to the following requirements and Division 22 Sections specifying piping systems. B. Ream ends of pipes and tubes and remove burrs. C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly. D. Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to tube end. Construct joints according to ASTM B 828 or CDA's "Copper Tube Handbook," using lead- free solder alloy complying with ASTM B 32. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows: 1. Apply appropriate tape or thread compound to external pipe threads unless dry seal threading is specified. 2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds. F. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service application. Install gasket concentrically positioned. Use suitable lubricants on bolt threads. G. Plastic Piping Solvent -Cement Joints: Clean and dry joining surfaces. Join pipe and fittings according to the following: Comply with ASTM F 402 for safe -handling practice of cleaners, primers, and solvent cements. PVC Nonpressure Piping: Join according to ASTM D 2855. 3.3 PIPING CONNECTIONS A. Make connections according to the following, unless otherwise indicated: 1. Install unions, in piping NPS 2 and smaller, adjacent to each valve and at final connection to each piece of equipment. - 2. Wet Piping Systems: Install dielectric coupling and nipple fittings to connect piping materials of dissimilar metals. 3.4 EQUIPMENT INSTALLATION - COMMON REQUIREMENTS A. Install equipment to allow maximum possible headroom unless specific mounting heights are not indicated. B. Install equipment level and plumb, parallel and perpendicular to other building systems and components in exposed interior spaces, unless otherwise indicated. COMMON WORK RESULTS FOR PLUMBING 220500 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Install plumbing equipment to facilitate service, maintenance, and repair or replacement of components. Connect equipment for ease of disconnecting, with minimum interference to other installations. Extend grease fittings to accessible locations. D. Install equipment to allow right of way for piping installed at required slope. 3.5 PAINTING A. Painting of plumbing systems, equipment, and components is specified in Division 09 Sections "Interior Painting" and "Exterior Painting." B. Damage and Touchup: Repair marred and damaged factory -painted finishes with materials and procedures to match original factory finish. 3.6 CONCRETE BASES A. Concrete Bases: Anchor equipment to concrete base according to equipment manufacturer's written instructions and according to seismic codes at Project. 1. Construct concrete bases of dimensions indicated, but not less than 4 inches larger in both directions than supported unit. 2. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18 -inch centers around the full perimeter of the base. 3. Install epoxy -coated anchor bolts for supported equipment that extend through concrete base, and anchor into structural concrete floor. 4. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. 5. Install anchor bolts to elevations required for proper attachment to supported equipment. 6. Install anchor bolts according to anchor -bolt manufacturer's written instructions. 7. As specified in Division 03 Section. 3.7 GROUTING A. Mix and install grout for plumbing equipment base bearing surfaces, pump and other equipment base plates, and anchors. B. Clean surfaces that will come into contact with grout. C. Provide forms as required for placement of grout. D. Avoid air entrapment during placement of grout. E. Place grout, completely filling equipment bases. F. Place grout on concrete bases and provide smooth bearing surface for equipment. G. Place grout around anchors. COMMON WORK RESULTS FOR PLUMBING 220500 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS H. Cure placed grout. END OF SECTION 220500 COMMON WORK RESULTS FOR PLUMBING 220500 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 220519 - METERS AND GAGES FOR PLUMBING PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Liquid -in -glass thermometers. 2. Thermowells. 3. Dial -type pressure gages. 4. Gage attachments. 5. Test plugs. 6. Test -plug kits. B. Related Sections: 1. Section 22 "Domestic Water Piping" for water meters inside the building. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. 1.4 INFORMATIONAL SUBMITTALS A. Product Certificates: For each type of meter and gage, from manufacturer. 1.5 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For meters and gages to include in operation and maintenance manuals. PART 2 - PRODUCTS 2.1 LIQUID -IN -GLASS THERMOMETERS A. Metal -Case, Compact -Style, Liquid -in -Glass Thermometers: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: METERS AND GAGES FOR PLUMBING PIPING 220519 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Trerice, H. O. Co. b. REOTEMP Instrument Corporation. c. Weiss Instruments, Inc. 2. Standard: ASME B40.200. 3. Case: Cast aluminum; 6 -inch nominal size. 4. Case Form: Back angle or Straight unless otherwise indicated. 5. Tube: Glass with magnifying lens and blue or red organic liquid. 6. Tube Background: Nonreflective aluminum with permanently etched scale markings graduated in deg F and deg C. 7. Window: Glass. 8. Stem: Aluminum or brass and of length to suit installation. a. Design for Thermowell Installation: Bare stem. 9. Connector: 3/4 inch, with ASME B1.1 screw threads. 10. Accuracy: Plus or minus 1 percent of scale range or one scale division, to a maximum of 1.5 percent of scale range. 2.2 THERMOWELLS A. Thermowells: 1. Standard: ASME B40.200. 2. Description: Pressure -tight, socket -type fitting made for insertion into piping tee fitting. 3. Material for Use with Copper Tubing: CNR. 4. Material for Use with Steel Piping: ORES. 5. Type: Stepped shank unless straight or tapered shank is indicated. 6. External Threads: NPS 1/2, NPS 3/4, or NPS 1 ASME B1.20.1 pipe threads. 7. Internal Threads: 1/2, 3/4, and 1 inch, with ASME B1.1 screw threads. 8. Bore: Diameter required to match thermometer bulb or stem. 9. Insertion Length: Length required to match thermometer bulb or stem. 10. Lagging Extension: Include on thermowells for insulated piping and tubing. 11. Bushings: For converting size of thermowell's internal screw thread to size of thermometer connection. Heat -Transfer Medium: Mixture of graphite and glycerin. 2.3 PRESSURE GAGES A. Direct -Mounted, Metal -Case, Dial -Type Pressure Gages: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Trerice, H. O. Co. b. Weiss Instruments, Inc. C. Winters Instruments - U.S. 2. Standard: ASME B40.100. 3. Case: Liquid -filled type(s); cast aluminum or drawn steel4-1/2-inch nominal diameter. 4. Pressure -Element Assembly: Bourdon tube unless otherwise indicated. METERS AND GAGES FOR PLUMBING PIPING 220519 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 5. Pressure Connection: Brass, with NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe threads and bottom -outlet type unless back -outlet type is indicated. 6. Movement: Mechanical, with link to pressure element and connection to pointer. 7. Dial: Nonreflective aluminum with permanently etched scale markings graduated in psi. 8. Pointer: Dark -colored metal. 9. Window: Glass. 10. Ring: Brass or Stainless steel. 11. Accuracy: Grade A, plus or minus 1 percent of middle half of scale range. 2.4 GAGE ATTACHMENTS A. Snubbers: ASME 640.100, brass; NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe threads and piston -type surge -dampening device. Include extension for use on insulated piping. B. Valves: Brass or stainless-steel needle], with NPS 1/4 or NPS 1/2, ASME 81.20.1 pipe threads. 2.5 TEST PLUGS A. Manufacturers: Subject to compliance with requirements, [provide products by one of the following: 1. Trerice, H. O. Co. 2. Watts Regulator Co.; a div. of Watts Water Technologies, Inc. 3. Weiss Instruments, Inc. B. Description: Test -station fitting made for insertion into piping tee fitting. C. Body: Brass or stainless steel with core inserts and gasketed and threaded cap. Include extended stem on units to be installed in insulated piping. D. Thread Size: NPS 1/4 or NPS 1/2, ASME B1.20.1 pipe thread. E. Minimum Pressure and Temperature Rating: 500 psig at 200 deg F. F. Core Inserts: Chlorosulfonated polyethylene synthetic self-sealing rubber. 2.6 TEST -PLUG KITS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Trerice, H. O. Co. 2. Watts Regulator Co.; a div. of Watts Water Technologies, Inc. 3. Weiss Instruments, Inc. B. Furnish one test -plug kit(s) containing one thermometer(s), one pressure gage and adapter, and carrying case. Thermometer sensing elements, pressure gage, and adapter probes shall be of diameter to fit test plugs and of length to project into piping. High -Range Thermometer: Small, bimetallic insertion type with 1- to 2 -inch- diameter dial and tapered -end sensing element. Dial range shall be at least 0 to 220 deg F. METERS AND GAGES FOR PLUMBING PIPING 220519 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Pressure Gage: Small, Bourdon -tube insertion type with 2- to 3 -inch- (diameter dial and probe. Dial range shall be at least 0 to 200 psig. E. Carrying Case: Metal or plastic, with formed instrument padding. PART 3 - EXECUTION 3.1 INSTALLATION A. Install thermowells with socket extending to center of pipe and in vertical position in piping tees. B. Install thermowells of sizes required to match thermometer connectors. Include bushings if required to match sizes. C. Install thermowells with extension on insulated piping. D. Fill thermowells with heat -transfer medium. E. Install direct -mounted pressure gages in piping tees with pressure gage located on pipe at the most readable position. F. Install valve and snubber in piping for each pressure gage for fluids. G. Install test plugs in piping tees. H. Install thermometers in the following locations (May not be shown on drawings): 1. Inlet and outlet of each water heater. 2. Outlet of all master mixing valves. 3.2 CONNECTIONS A. Install meters and gages adjacent to machines and equipment to allow service and maintenance of meters, gages, machines, and equipment. 3.3 ADJUSTING A. Adjust faces of meters and gages to proper angle for best visibility. 3.4 THERMOMETER SCALE -RANGE SCHEDULE A. Scale Range for Domestic Hot -Water Piping: 0 to 250 deg F. 3.5 PRESSURE -GAGE SCALE -RANGE SCHEDULE A. Scale Range for Water Service Piping: 0 to 160 psi. METERS AND GAGES FOR PLUMBING PIPING 220519 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Scale Range for Domestic Water Piping: 0 to 200 psi. END OF SECTION 220519 METERS AND GAGES FOR PLUMBING PIPING 220519 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 220523 GENERAL -DUTY VALVES FOR PLUMBING PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Bronze angle valves. 2. Brass ball valves. 3. Bronze ball valves. 4. Bronze lift check valves. 5. Bronze swing check valves. 6. Bronze gate valves. B. Related Sections: 1. Section 22 "Identification for Plumbing Piping and Equipment" for valve tags and schedules. 2. Section 22 "Domestic Water Piping" for valves applicable only to this piping. 3. Section 22 "Storm Drainage Piping Specialties" for valves applicable only to this piping. 1.3 DEFINITIONS A. CWP: Cold working pressure. B. EPDM: Ethylene propylene copolymer rubber. C. NBR: Acrylonitrile -butadiene, Buna-N, or nitrile rubber. D. NRS: Non rising stem. E. OS&Y: Outside screw and yoke. F. RS: Rising stem. G. SWP: Steam working pressure. GENERAL -DUTY VALVES FOR PLUMBING PIPING 220523 • INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.4 ACTION SUBMITTALS A. Product Data: For each type of valve indicated. 1.5 QUALITY ASSURANCE A. Source Limitations for Valves: Obtain each type of valve from single source from single manufacturer. B. ASME Compliance: 1. ASME B16.10 and ASME B 16.34 for ferrous valve dimensions and design criteria. C. NSF Compliance: NSF 61 for valve materials for potable -water service. 1.6 DELIVERY, STORAGE, AND HANDLING A. Use the following precautions during storage: 1. Maintain valve end protection. 2. Store valves indoors and maintain at higher than ambient dew point temperature. If outdoor storage is necessary, store valves off the ground in watertight enclosures. B. Use sling to handle large valves; rig sling to avoid damage to exposed parts. Do not use hand wheels or stems as lifting or rigging points. PART 2- PRODUCTS 2.1 GENERAL REQUIREMENTS FOR VALVES A. Refer to valve schedule articles for applications of valves. B. Valve Pressure and Temperature Ratings: Not less than indicated and as required for system pressures and temperatures. C. Valve Sizes: Same as upstream piping unless otherwise indicated. D. Valve Actuator Types: 1. Handwheel: For valves other than quarter -turn types. 2. Handlever: For quarter -turn valves NPS 6 and smaller except plug valves. 3. Wrench: For plug valves with square heads. Furnish Owner with 1 wrench for every 10 plug valves, for each size square plug -valve head. E. Valves in Insulated Piping: With 2 -inch stem extensions and the following features: 1. Gate Valves: With rising stem. GENERAL -DUTY VALVES FOR PLUMBING PIPING 220523 • INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Ball Valves: With extended operating handle of non -thermal -conductive material, and protective sleeve that allows operation of valve without breaking the vapor seal or disturbing insulation. F. Valve -End Connections: 1. Flanged: With flanges according to ASME B16.1 for iron valves. 2. Grooved: With grooves according to AWWA C606. 3. Solder Joint: With sockets according to ASME B16.18. 4. Threaded: With threads according to ASME B1.20.1. G. Valve Bypass and Drain Connections: MSS SP -45. 2.2 BRONZE BALL VALVES A. Two -Piece, Full -Port, Bronze Ball Valves with Bronze Trim: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Conbraco Industries, Inc.; Apollo Valves. b. Milwaukee Valve Company. c. NIBCO INC. 2. Description: a. Standard: MSS SP -110. b. SWP Rating: 150 psig. c. CWP Rating: 600 psig. d. Body Design: Two piece. e. Body Material: Bronze. f. Ends: Threaded. g. Seats: PTFE or TFE. h. Stem: Bronze. i. Ball: Chrome -plated brass. j. Port: Full. 2.3 BRONZE LIFT CHECK VALVES A. Class 125, Lift Check Valves with Nonmetallic Disc: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Kitz Corporation. b. Milwaukee Valve Company. c. NIBCO INC. 2. Description: GENERAL -DUTY VALVES FOR PLUMBING PIPING 220523 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Standard: MSS SP -80, Type 2. b. CWP Rating: 200 psig. c. Body Design: Vertical flow. d. Body Material: ASTM B 61 or ASTM B 62, bronze. e. Ends: Threaded. f. Disc: NBR, PTFE, or TFE. 2.4 BRONZE SWING CHECK VALVES A. Class 250, Iron Swing Check Valves with Metal Seats: 1. Manufacturers: Subject to compliance with requirements,provide products by one of the following: a. Crane Co.; Crane Valve Group; Stockham Division. b. Milwaukee Valve Company. c. NIBCO INC. 2. Description: a. Standard: MSS SP -71, Type I. b. CWP Rating: 500 psig. c. Body Design: Clear or full waterway. d. Body Material: ASTM A 126, gray iron with bolted bonnet. e. Ends: Flanged. f. Trim: Bronze. g. Gasket: Asbestos free. B. Class 150, NRS Bronze Gate Valves: 1. Manufacturers: Subject to compliance with requirements,provide products by one of the following. a. Kitz Corporation. b. Milwaukee Valve Company. c. NIBCO INC. 2. Description: a. Standard: MSS SP -80, Type 1. b. CWP Rating: 300 psig. c. Body Material: ASTM B 62, bronze with integral seat and union -ring bonnet. d. Ends: Threaded. e. Stem: Bronze. f. Disc: Solid wedge; bronze. g. Packing: Asbestos free. h. Handwheel: Malleable iron, bronze, or aluminum. GENERAL -DUTY VALVES FOR PLUMBING PIPING 220523 • INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION 3.1 EXAMINATION A. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove special packing materials, such as blocks, used to prevent disc movement during shipping and handling. B. Operate valves in positions from fully open to fully closed. Examine guides and seats made accessible by such operations. C. Examine threads on valve and mating pipe for form and cleanliness. D. Examine mating flange faces for conditions that might cause leakage. Check bolting for proper size, length, and material. Verify that gasket is of proper size, that its material composition is suitable for service, and that it is free from defects and damage. E. Do not attempt to repair defective valves; replace with new valves. 3.2 VALVE INSTALLATION A. Install valves with unions or flanges at each piece of equipment arranged to allow service, maintenance, and equipment removal without system shutdown. B. Locate valves for easy access and provide separate support where necessary. C. Install valves in horizontal piping with stem at or above center of pipe. D. Install valves in position to allow full stem movement. E. Install check valves for proper direction of flow and as follows: 1. Swing Check Valves: In horizontal position with hinge pin level. 2. Lift Check Valves: With stem upright and plumb. 3.3 ADJUSTING A. Adjust or replace valve packing after piping systems have been tested and put into service but before final adjusting and balancing. Replace valves if persistent leaking occurs. 3.4 GENERAL REQUIREMENTS FOR VALVE APPLICATIONS A. If valve applications are not indicated, use the following: 1. Shutoff Service: Ball or gate valves. 2. Pump -Discharge Check Valves: a. NPS 2 and Smaller: Bronze swing check valves with bronze or nonmetallic disc. GENERAL -DUTY VALVES FOR PLUMBING PIPING 220523 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. If valves with specified SWP classes or CWP ratings are not available, the same types of valves with higher SWP classes or CWP ratings may be substituted. C. Select valves, except wafer types, with the following end connections: 1. For Copper Tubing, NPS 2 and Smaller: Threaded ends except where solder joint valve - end option is indicated in valve schedules below. 2. For Copper Tubing, NPS 2-1/2 to NPS 4: Flanged ends except where threaded valve -end option is indicated in valve schedules below. 3. For Grooved -End Copper Tubing and Steel Piping: Valve ends may be grooved. 3.5 DOMESTIC, HOT- AND COLD -WATER VALVE SCHEDULE A. Pipe NPS 4 and Smaller: 1. Bronze and Brass Valves: May be provided with solder -joint ends instead of threaded ends. 2. Ball Valves: Two piece, full port, brass or bronze with brass or bronze trim. 3. Bronze Swing Check Valves: Class 150, bronze disc. 4. Bronze Gate Valves: Class 150, NRS. 3.6 STORM -DRAINAGE VALVE SCHEDULE A. Pipe NPS 2 and Smaller: 1. Bronze Swing Check Valves: Class 125nonmetallic disc. B. Pipe NPS 2-1/2 and Larger: 1. Iron Swing Check Valves: Class 125, nonmetallic -to -metal seats. END OF SECTION GENERAL -DUTY VALVES FOR PLUMBING PIPING 220523 • INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Metal pipe hangers and supports. 2. Trapeze pipe hangers. 3. Metal framing systems. 4. Thermal -hanger shield inserts. 5. Fastener systems. 6. Pipe positioning systems. 7. Equipment supports. B. Related Sections: Section 05 "Metal Fabrications" for structural -steel shapes and plates for trapeze hangers for pipe and equipment supports. 1.3 DEFINITIONS A. MSS: Manufacturers Standardization Society of the Valve and Fittings Industry Inc. 1.4 PERFORMANCE REQUIREMENTS A. Structural Performance: Hangers and supports for plumbing piping and equipment shall withstand the effects of gravity loads and stresses within limits and under conditions indicated according to ASCE/SEI 7. 1. Design supports for multiple pipes, including pipe stands, capable of supporting combined weight of supported systems, system contents, and test water. 2. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components. 1.5 ACTION SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: Show fabrication and installation details and include calculations for the following; include Product Data for components: HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Trapeze pipe hangers. 1.6 INFORMATIONAL SUBMITTALS A. Welding certificates. 1.7 QUALITY ASSURANCE A. Structural Steel Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel." B. Pipe Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code. PART 2 - PRODUCTS 2.1 METAL PIPE HANGERS AND SUPPORTS A. Carbon -Steel Pipe Hangers and Supports: 1. Description: MSS SP -58, Types 1 through 58, factory -fabricated components. 2. Galvanized Metallic Coatings: Pre -galvanized or hot dipped. 3. Nonmetallic Coatings: Plastic coating, jacket, or liner. 4. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of piping. 5. Hanger Rods: Continuous -thread rod, nuts, and washer made of carbon steel. 2.2 TRAPEZE PIPE HANGERS A. Description: MSS SP -69, Type 59, shop- or field -fabricated pipe -support assembly made from structural carbon -steel shapes with MSS SP -58 carbon -steel hanger rods, nuts, saddles, and U - bolts. 2.3 THERMAL -HANGER SHIELD INSERTS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. ERICO International Corporation. 2. PHS Industries, Inc. 3. Pipe Shields, Inc.; a subsidiary of Piping Technology & Products, Inc. B. Insulation -Insert Material for Hot Piping: Water-repellent treated, ASTM C 533, Type I calcium silicate with 100-psig ASTM C 552, Type II cellular glass with 100-psig or ASTM C 591, Type VI, Grade 1 polyisocyanurate with 125-psig minimum compressive strength. C. For Trapeze or Clamped Systems: Insert and shield shall cover entire circumference of pipe. HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. For Clevis or Band Hangers: Insert and shield shall cover lower 180 degrees of pipe. E. Insert Length: Extend 2 inches beyond sheet metal shield for piping operating below ambient air temperature. 2.4 FASTENER SYSTEMS A. Powder -actuated fasteners are not acceptable. B. Mechanical -Expansion Anchors: Insert -wedge -type, stainless-steel anchors, for use in hardened portland cement concrete; with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used. 2.5 PIPE POSITIONING SYSTEMS A. Description: IAPMO PS 42, positioning system of metal brackets, clips, and straps for positioning piping in pipe spaces; for plumbing fixtures in commercial applications. 2.6 MISCELLANEOUS MATERIALS A. Structural Steel: ASTM A 36/A 36M, carbon -steel plates, shapes, and bars; black and galvanized. B. Grout: ASTM C 1107, factory -mixed and -packaged, dry, hydraulic -cement, nonshrink and nonmetallic grout; suitable for interior and exterior applications. 1. Properties: Nonstaining, noncorrosive, and nongaseous. 2. Design Mix: 5000 -psi, 28 -day compressive strength. PART3-EXECUTION 3.1 HANGER AND SUPPORT INSTALLATION A. Metal Pipe -Hanger Installation: Comply with MSS SP -69 and MSS SP -89. Install hangers, supports, clamps, and attachments as required to properly support piping from the building structure. B. Metal Trapeze Pipe -Hanger Installation: Comply with MSS SP -69 and MSS SP -89. Arrange for grouping of parallel runs of horizontal piping, and support together on field -fabricated trapeze pipe hangers. 1. Pipes of Various Sizes: Support together and space trapezes for smallest pipe size or install intermediate supports for smaller diameter pipes as specified for individual pipe hangers. 2. Field fabricate from ASTM A 36/A 36M, carbon -steel shapes selected for loads being supported. Weld steel according to AWS D1.1/D1.1M. C. Thermal -Hanger Shield Installation: Install in pipe hanger or shield for insulated piping. HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Pipe Positioning -System Installation: Install support devices to make rigid supply and waste piping connections to each plumbing fixture. E. Install hangers and supports complete with necessary attachments, inserts, bolts, rods, nuts, washers, and other accessories. F. Equipment Support Installation: Fabricate from welded -structural -steel shapes. G. Install hangers and supports to allow controlled thermal movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units. H. Install lateral bracing with pipe hangers and supports to prevent swaying. Install building attachments within concrete slabs or attach to structural steel. Install additional attachments at concentrated loads, including valves, flanges, and strainers, NPS 2-1/2 and larger and at changes in direction of piping. Install concrete inserts before concrete is placed; fasten inserts to forms and install reinforcing bars through openings at top of inserts. J. Load Distribution: Install hangers and supports so that piping live and dead loads and stresses from movement will not be transmitted to connected equipment. K. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and to not exceed maximum pipe deflections allowed by ASME B31.9 for building services piping. L. Insulated Piping: 1. Attach clamps and spacers to piping. a. Piping Operating above Ambient Air Temperature: Clamp may project through insulation. b. Piping Operating below Ambient Air Temperature: Use thermal -hanger shield insert with clamp sized to match OD of insert. c. Do not exceed pipe stress limits allowed by ASME B31.9 for building services piping. 2. Install MSS SP -58, Type 39, protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation. a. Option: Thermal -hanger shield inserts may be used. Include steel weight - distribution plate for pipe NPS 4 and larger if pipe is installed on rollers. 3. Install MSS SP -58, Type 40, protective shields on cold piping with vapor barrier. Shields shall span an arc of 180 degrees. a. Option: Thermal -hanger shield inserts may be used. Include steel weight - distribution plate for pipe NPS 4 and larger if pipe is installed on rollers. 4. Shield Dimensions for Pipe: Not less than the following: a. NPS 1/4 to NPS 3-1/2 : 12 inches long and 0.048 inch thick. b. NPS 4 : 12 inches long and 0.06 inch thick. c. NPS 5 and NPS 6 : 18 inches long and 0.06 inch thick. d. NPS 8 to NPS 14 : 24 inches long and 0.075 inch thick. HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 5. Pipes NPS 8 and Larger: Include wood or reinforced calcium -silicate -insulation inserts of length at least as long as protective shield. 6. Thermal -Hanger Shields: Install with insulation same thickness as piping insulation. M. Grouting: Place grout under supports for equipment and make bearing surface smooth. N. Provide lateral bracing, to prevent swaying, for equipment supports. 3.2 METAL FABRICATIONS A. Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers. B. Fit exposed connections together to form hairline joints. Field weld connections that cannot be shop welded because of shipping size limitations. C. Field Welding: Comply with AWS D1.1/D1.1M procedures for shielded, metal arc welding; appearance and quality of welds; and methods used in correcting welding work; and with the following: 1. Use materials and methods that minimize distortion and develop strength and corrosion resistance of base metals. 2. Obtain fusion without undercut or overlap. 3. Remove welding flux immediately. 4. Finish welds at exposed connections so no roughness shows after finishing and so contours of welded surfaces match adjacent contours. 3.3 ADJUSTING A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe. B. Trim excess length of continuous -thread hanger and support rods to 1-1/2 inches. 3.4 PAINTING A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field -painted surfaces. 1. Apply paint by brush or spray to provide a minimum dry film thickness of 2.0 mils. B. Touchup: Cleaning and touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal are specified in Section 099113 "Exterior Painting." C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing -repair paint to comply with ASTM A 780. 3.5 HANGER AND SUPPORT SCHEDULE A. Specific hanger and support requirements are in Sections specifying piping systems and equipment. HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Comply with MSS SP -69 for pipe -hanger selections and applications that are not specified in piping system Sections. C. Use hangers and supports with galvanized metallic coatings for piping and equipment that will not have field -applied finish. D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing. E. Use carbon -steel pipe hangers and supports metal trapeze pipe hangers and metal framing systems and attachments for general service applications. F. Use copper -plated pipe hangers and copper attachments for copper piping and tubing. G. Use padded hangers for piping that is subject to scratching. H. Use thermal -hanger shield inserts for insulated piping and tubing. I. Horizontal -Piping Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of non -insulated or insulated, stationary pipes. 2. Steel Pipe Clamps (MSS Type 4): For suspension of cold and hot pipes if little or no insulation is required. 3. Adjustable, Swivel -Ring Band Hangers (MSS Type 10): For suspension of non -insulated, stationary pipes NPS 1/2 to NPS 8. 4. Pipe Saddle Supports (MSS Type 36): For support of pipes NPS 4 and up, with steel - pipe base stanchion support and cast-iron floor flange or carbon -steel plate. J. Vertical -Piping Clamps: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers NPS 3/4 and up. K. Hanger -Rod Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches for heavy loads. 2. Swivel Turnbuckles (MSS Type 15): For use with MSS Type 11, split pipe rings. L. Building Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. Steel or Malleable Concrete Inserts (MSS Type 18): For upper attachment to suspend pipe hangers from concrete ceiling. 2. Top -Beam C -Clamps (MSS Type 19): For use under roof installations with bar -joist construction, to attach to top flange of structural shape. 3. Side -Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange of beams, channels, or angles. 4. Center -Beam Clamps (MSS Type 21): For attaching to center of bottom Flange of beams. 5. Welded Beam Attachments (MSS Type 22): For attaching to bottom of beams if loads are considerable and rod sizes are large. HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 6. Top -Beam Clamps (MSS Type 25): For top of beams if hanger rod is required tangent to flange edge. 7. Welded -Steel Brackets: For support of pipes from below or for suspending from above by using clip and rod. Use one of the following for indicated loads: a. Light (MSS Type 31): 750 Ib. b. Medium (MSS Type 32): 1500 Ib. c. Heavy (MSS Type 33): 3000 Ib. M. Comply with MSS SP -69 for trapeze pipe -hanger selections and applications that are not specified in piping system Sections. N. Comply with MFMA-103 for metal framing system selections and applications that are not specified in piping system Sections. O. Use mechanical -expansion anchors instead of building attachments where required in concrete construction. P. Use pipe positioning systems in pipe spaces behind plumbing fixtures to support supply and waste piping for plumbing fixtures. END OF SECTION 220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 220529 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Equipment labels. 2. Pipe labels. 3. Valve tags. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. 1.4 COORDINATION A. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied. B. Coordinate installation of identifying devices with locations of access panels and doors. C. Install identifying devices before installing acoustical ceilings and similar concealment. PART 2 - PRODUCTS 2.1 EQUIPMENT LABELS A. Plastic Labels for Equipment: 1. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8 inch thick, and having predrilled holes for attachment hardware. 2. Letter Color: White. 3. Background Color: Black. 4. Maximum Temperature: Able to withstand temperatures up to 160 deg F. 5. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch. 6. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering. IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT 220553 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 7. Fasteners: Stainless-steel rivets or self -tapping screws. 8. Adhesive: Contact -type permanent adhesive, compatible with label and with substrate. B. Label Content: Include equipment's Drawing designation or unique equipment number, Drawing numbers where equipment is indicated (plans, details, and schedules), plus the Specification Section number and title where equipment is specified. C. Equipment Label Schedule: For each item of equipment to be labeled, on 8 -1/2 -by -11 -inch bond paper. Tabulate equipment identification number and identify Drawing numbers where equipment is indicated (plans, details, and schedules), plus the Specification Section number and title where equipment is specified. Equipment schedule shall be included in operation and maintenance data. 2.2 PIPE LABELS A. General Requirements for Manufactured Pipe Labels: Preprinted, color -coded, with lettering indicating service, and showing flow direction. B. Pretensioned Pipe Labels: Precoiled, semi-rigid plastic formed to partially cover circumference of pipe and to attach to pipe without fasteners or adhesive. C. Pipe Label Contents: Include identification of piping service using same designations or abbreviations as used on Drawings and an arrow indicating flow direction. Flow -Direction Arrows: Integral with piping system service lettering to accommodate both directions, or as separate unit on each pipe label to indicate flow direction. Lettering Size: At least 1-1/2 inches high. 2.3 VALVE TAGS A. Valve Tags: Stamped or engraved with 1/4 -inch letters for piping system abbreviation and 1/2 - inch numbers. 1. Tag Material: Brass, 0.032 -inch or Stainless steel, 0.025 -inch minimum thickness, and having predrilled or stamped holes for attachment hardware. 2. Fasteners: Brass wire -link or beaded chain or S -hook. B. Valve Schedules: For each piping system, on 8 -1/2 -by -11 -inch bond paper. Tabulate valve number, piping system, system abbreviation (as shown on valve tag), location of valve (room or space), normal -operating position (open, closed, or modulating), and variations for identification. Mark valves for emergency shutoff and similar special uses. 1. Valve -tag schedule shall be included in operation and maintenance data. PART 3 - EXECUTION 3.1 PREPARATION Clean piping and equipment surfaces of substances that could impair bond of identification devices, including dirt, oil, grease, release agents, and incompatible primers, paints, and encapsulants. IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT 220553 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.2 EQUIPMENT LABEL INSTALLATION A. Install or permanently fasten labels on each major item of mechanical equipment. B. Locate equipment labels where accessible and visible. 3.3 PIPE LABEL INSTALLATION A. Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior exposed locations as follows: 1. Near each valve and control device. 2. Near each branch connection, excluding short takeoffs for fixtures and terminal units. Where flow pattern is not obvious, mark each pipe at branch. 3. Near penetrations through walls, floors, ceilings, and inaccessible enclosures. 4. At access doors, manholes, and similar access points that permit view of concealed piping. 5. Near major equipment items and other points of origination and termination. 6. Spaced at maximum intervals of 25 feet along each run. Reduce intervals to 10 feet in areas of congested piping and equipment. 7. Identification of potable and non -potable wate a. In all buildings where two or more water distribution system, one potable water and the other non -potable water, ate installed, each system shall be identified either by color marking or metal tags as required by ASME A13.1. Reclaimed water systems shall be identified using color coded Pantone Purple 522C and marked with the statement "NONPOTABLE WATER - NOT FOR HUMAN CONSUMPTION. B. Pipe Label Color Refer to ASME(ANSI) Standard A13.1-2007. 3.4 VALVE -TAG INSTALLATION Install tags on valves and control devices in piping systems, except check valves; valves within factory -fabricated equipment units; shutoff valves; faucets; convenience and lawn -watering hose connections; and similar roughing -in connections of end-use fixtures and units. List tagged valves in a valve schedule. Valve -Tag Application Schedule: Tag valves according to size, shape, and color scheme and with captions similar to those indicated in the following subparagraphs: 1. Valve -Tag Size and Shape: a. Cold Water: 2 inches, round. b. Hot Water: 2 inches, round. END OF SECTION 220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT 220553 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 220700 PLUMBING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Insulation Materials: a. Flexible elastomeric. b. Mineral fiber. 2. Insulating cements. 3. Adhesives. 4. Mastics. 5. Lagging adhesives. 6. Sealants. 7. Factory -applied jackets. 8. Tapes. 9. Corner angles. 1.3 SUBMITTALS A. Product Data: For each type of product indicated. Include thermal conductivity, thickness, and jackets (both factory and field applied, if any). B. Submittal: For adhesives and sealants, including printed statement of VOC content compliant with South Coast Air Quality Management District (SCAQMD) Rule #1168. 1.4 QUALITY ASSURANCE A. Installer Qualifications: Skilled mechanics who have successfully completed an apprenticeship program or another craft training program certified by the Department of Labor, Bureau of Apprenticeship and Training. B. Fire -Test -Response Characteristics: Insulation and related materials shall have fire -test - response characteristics indicated, as determined by testing identical products per ASTM E 84, by a testing and inspecting agency acceptable to authorities having jurisdiction. Factory label PLUMBING INSULATION 220700 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS insulation and jacket materials and adhesive, mastic, tapes, and cement material containers, with appropriate markings of applicable testing and inspecting agency. 1. Insulation Installed Indoors: Flame -spread index of 25 or less, and smoke -developed index of 50 or less. 1.5 DELIVERY, STORAGE, AND HANDLING A. Packaging: Insulation material containers shall be marked by manufacturer with appropriate ASTM standard designation, type and grade, and maximum use temperature. 1.6 COORDINATION A. Coordinate size and location of supports, hangers, and insulation shields specified in Division 22 Section "Hangers and Supports for Plumbing Piping and Equipment." B. Coordinate clearance requirements with piping Installer for piping insulation application and equipment Installer for equipment insulation application. Before preparing piping Shop Drawings, establish and maintain clearance requirements for installation of insulation and field- appliedjackets and finishes and for space required for maintenance. C. Coordinate installation and testing of heat tracing. 1.7 SCHEDULING A. Schedule insulation application after pressure testing systems and, where required, after installing and testing heat tracing. Insulation application may begin on segments that have satisfactory test results. B. Complete installation and concealment of plastic materials as rapidly as possible in each area of construction. PART 2 - PRODUCTS 2.1 INSULATION MATERIALS A. Comply with requirements in Part 3 schedule articles for where insulating materials shall be applied. B. Products shall not contain asbestos, lead, mercury, or mercury compounds. C. Flexible Elastomeric: Closed -cell, sponge- or expanded -rubber materials. Comply with ASTM C 534, Type 1 for tubular materials and Type II for sheet materials. Products: Subject to compliance with requirements, provide one of the following: a. Aeroflex USA Inc.; Aerocel. b. Armacell LLC; AP Armaflex. c. RBX Corporation; Insul-Sheet 1800 and Insul-Tube 180. PLUMBING INSULATION 220700 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Mineral -Fiber, Preformed Pipe Insulation: 1. Products: Subject to compliance with requirements, provide one of the following: a. Johns Manville; Micro -Lok, b. Knauf Insulation; 1000(Pipe Insulation. c. Owens Corning; Fiberglas Pipe Insulation. 2. Type I, 850 deg F Materials: Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 547, Type I, Grade A, with factory -applied ASJ-SSL. Factory - applied jacket requirements are specified in "Factory -Applied Jackets" Article. 2.2 INSULATING CEMENTS A. Mineral -Fiber Insulating Cement: Comply with ASTM C 195. 1. Products: Subject to compliance with requirements, provide one of the following: a. Insulco, Division of MFS, Inc.; Triple I. b. P. K. Insulation Mfg. Co., Inc.; Super-Stik. 2.3 ADHESIVES A. Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated, unless otherwise indicated. B. Flexible Elastomeric Adhesive: Comply with MIL -A -24179A, Type II, Class I. 1. Products: Subject to compliance with requirements, provide one of the following: a. Aeroflex USA Inc.; Aeroseal. b. Armacell LCC; 520 Adhesive. c. RBX Corporation; Rubatex Contact Adhesive. C. Mineral -Fiber Adhesive: Comply with MIL -A -3316C, Class 2, Grade A. 1. Products: Subject to compliance with requirements, provide one of the following: a. Childers Products, Division of ITW; CP -82. b. Foster Products Corporation, H. B. Fuller Company; 85-20. c. ITW TACC, Division of Illinois Tool Works; S-90/80. D. ASJ Adhesive, and FSK and PVDC Jacket Adhesive: Comply with MIL -A -3316C, Class 2, Grade A for bonding insulation jacket lap seams and joints. 1. Products: Subject to compliance with requirements, provide one of the following: a. Childers Products, Division of ITW; CP -82. b. Foster Products Corporation, H. B. Fuller Company; 85-20. c. ITW TACC, Division of Illinois Tool Works; S-90/80. PLUMBING INSULATION 220700 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.4 MASTICS A. Materials shall be compatible with insulation materials, jackets, and substrates; comply with MIL -C -19565C, Type II. B. Vapor -Barrier Mastic: Water based; suitable for indoor and outdoor use on below ambient services. 1. Products: Subject to compliance with requirements, provide one of the following: a. Childers Products, Division of ITW; CP -35. b. Foster Products Corporation, H. B. Fuller Company; 30-90. c. ITW TACC, Division of Illinois Tool Works; CB -50. 2. Water -Vapor Permeance: ASTM E 96, Procedure B, 0.013 perm at 43 -mil dry film thickness. 3. Service Temperature Range: Minus 20 to plus 180 deg F. 4. Solids Content: ASTM D 1644, 59 percent by volume and 71 percent by weight. 5. Color: White. 2.5 LAGGING ADHESIVES A. Description: Comply with MIL -A -3316C Class I, Grade A and shall be compatible with insulation materials, jackets, and substrates. 1. Products: Subject to compliance with requirements, provide one of the following: a. Childers Products, Division of ITW; CP -52. b. Foster Products Corporation, H. B. Fuller Company; 81-42. c. Marathon Industries, Inc.; 130. 2. Fire-resistant, water-based lagging adhesive and coating for use indoors to adhere fire- resistant lagging cloths over equipment and pipe insulation. 3. Service Temperature Range: Minus 50 to plus 180 deg F. 4. Color: White. 2.6 SEALANTS A. Joint Sealants: 1. Materials shall be compatible with insulation materials, jackets, and substrates. 2. Permanently flexible, elastomeric sealant. 3. Service Temperature Range: Minus 100 to plus 300 deg F. 4. Color: White or gray. B. ASJ Flashing Sealants, and Vinyl, PVDC, and PVC Jacket Flashing Sealants: 1. Products: Subject to compliance with requirements, provide one of the following: a. Childers Products, Division of ITW; CP -76. 2. Materials shall be compatible with insulation materials, jackets, and substrates. PLUMBING INSULATION 220700 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3. Fire- and water-resistant, flexible, elastomeric sealant. 4. Service Temperature Range: Minus 40 to plus 250 deg F. 5. Color: White. 2.7 FACTORY -APPLIED JACKETS A. Insulation system schedules indicate factory -applied jackets on various applications. When factory -applied jackets are indicated, comply with the following: 1. ASJ: White, kraft -paper, fiberglass -reinforced scrim with aluminum -foil backing; complying with ASTM C 1136, Type I. 2.8 TAPES ASJ Tape: White vapor -retarder tape matching factory -applied jacket with acrylic adhesive, complying with ASTM C 1136. 1. Products: Subject to compliance with requirements, provide one of the following: a. Avery Dennison Corporation, Specialty Tapes Division; Fasson 0835. b. Compac Corp.; 104 and 105. c. Ideal Tape Co., Inc., an American Biltrite Company; 428 AWF ASJ. 2. Width: 3 inches. 3. Thickness: 11.5 mils. 4. Adhesion: 90 ounces force/inch in width. 5. Elongation: 2 percent. 6. Tensile Strength: 40 Ibf/inch in width. 7. ASJ Tape Disks and Squares: Precut disks or squares of ASJ tape. 2.9 CORNER ANGLES A. PVC Corner Angles: 30 mils thick, minimum 1 by 1 inch, PVC according to ASTM D 1784, Class 16354-C. White or color -coded to match adjacent surface. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions for compliance with requirements for installation and other conditions affecting performance of insulation application. Verify that systems and equipment to be insulated have been tested and are free of defects. Verify that surfaces to be insulated are clean and dry. Proceed with installation only after unsatisfactory conditions have been corrected. PLUMBING INSULATION 220700 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.2 PREPARATION A. Surface Preparation: Clean and dry surfaces to receive insulation. adversely affect insulation application. B. Surface Preparation: Clean and prepare surfaces to be insulated. corrosion coating to insulated surfaces as follows: Remove materials that will Before insulating, apply a Carbon Steel: Coat carbon steel operating at a service temperature between 32 and 300 deg F with an epoxy coating. Consult coating manufacturer for appropriate coating materials and application methods for operating temperature range. C. Mix insulating cements with clean potable water; if insulating cements are to be in contact with stainless-steel surfaces, use demineralized water. 3.3 A. GENERAL INSTALLATION REQUIREMENTS Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces; free of voids throughout the length of equipment and piping including fittings, valves, and specialties. B. Install insulation materials, forms, vapor barriers or retarders, jackets, and thicknesses required for each item of equipment and pipe system as specified in insulation system schedules. C. Install accessories compatible with insulation materials and suitable for the service. Install accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or dry state. D. Install insulation with longitudinal seams at top and bottom of horizontal runs. E. Install multiple layers of insulation with longitudinal and end seams staggered. F. Do not weld brackets, clips, or other attachment devices to piping, fittings, and specialties. G. Keep insulation materials dry during application and finishing. H. Install insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive recommended by insulation material manufacturer. I. Install insulation with least number of joints practical. J. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at hangers, supports, anchors, and other projections with vapor -barrier mastic. 1. Install insulation continuously through hangers and around anchor attachments. 2. For insulation application where vapor barriers are indicated, extend insulation on anchor legs from point of attachment to supported item to point of attachment to structure. Taper and seal ends at attachment to structure -with vapor -barrier mastic. 3. Install insert materials and install insulation to tightly join the insert. Seal insulation to insulation inserts with adhesive or sealing compound recommended by insulation material manufacturer. 4. Cover inserts with jacket material matching adjacent pipe insulation. Install shields over jacket, arranged to protect jacket from tear or puncture by hanger, support, and shield. PLUMBING INSULATION 220700 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS K. Apply adhesives, mastics, and sealants at manufacturer's recommended coverage rate and wet and dry film thicknesses. L. Install insulation with factory -applied jackets as follows: 1. Draw jacket tight and smooth. 2. Cover joints and seams with tape as recommended by insulation material manufacturer to maintain vapor seal. 3. Where vapor barriers are indicated, apply vapor -barrier mastic on seams and joints and at ends adjacent to pipe flanges and fittings. M. Cut insulation in a manner to avoid compressing insulation more than 75 percent of its nominal thickness. N. Finish installation with systems at operating conditions. Repair joint separations and cracking due to thermal movement. O. Repair damaged insulation facings by applying same facing material over damaged areas. Extend patches at least 4 inches beyond damaged areas. Adhere and seal patches similar to butt joints. P. For above ambient services, do not install insulation to the following: 1. Vibration -control devices. 2. Testing agency labels and stamps. 3. Nameplates and data plates. 4. Manholes. 5. Handholes. 6. Cleanouts. 3.4 PENETRATIONS A. Insulation Installation at Aboveground Exterior Wall Penetrations: Install insulation continuously through wall penetrations. 1. Seal penetrations with flashing sealant. 2. For applications requiring only indoor insulation, terminate insulation inside wall surface and seal with joint sealant. 3. Seal jacket to wall flashing with flashing sealant. B. Insulation Installation at Interior Wall and Partition Penetrations (That Are Not Fire Rated): Install insulation continuously through walls and partitions. C. Insulation Installation at Fire -Rated Wall and Partition Penetrations: Install insulation continuously through penetrations of fire -rated walls and partitions. 1. Comply with requirements in Division 07 Section "Penetration Firestopping" for firestopping and fire -resistive joint sealers. PLUMBING INSULATION 220700 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.5 GENERAL PIPE INSULATION INSTALLATION A. Requirements in this article generally apply to all insulation materials except where more specific requirements are specified in various pipe insulation material installation articles. Insulation Installation on Fittings, Valves, Strainers, Flanges, and Unions: 1. Install insulation over fittings, valves, strainers, flanges, unions, and other specialties with continuous thermal and vapor -retarder integrity, unless otherwise indicated. 2. Insulate pipe elbows using preformed fitting insulation or mitered fittings made from same material and density as adjacent pipe insulation. Each piece shall be butted tightly against adjoining piece and bonded with adhesive. Fill joints, seams, voids, and irregular surfaces with insulating cement finished to a smooth, hard, and uniform contour that is uniform with adjoining pipe insulation. 3. Insulate tee fittings with preformed fitting insulation or sectional pipe insulation of same material and thickness as used for adjacent pipe. Cut sectional pipe insulation to fit. Butt each section closely to the next and hold in place with tie wire. Bond pieces with adhesive. 4. Insulate valves using preformed fitting insulation or sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. For valves, insulate up to and including the bonnets, valve stuffing -box studs, bolts, and nuts. Fill joints, seams, and irregular surfaces with insulating cement. 5. Insulate strainers using preformed fitting insulation or sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. Fill joints, seams, and irregular surfaces with insulating cement. Insulate strainers so strainer basket flange or plug can be easily removed and replaced without damaging the insulation and jacket. Provide a removable reusable insulation cover. For below ambient services, provide a design that maintains vapor barrier. 6. Insulate flanges and unions using a section of oversized preformed pipe insulation. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. 7. Cover segmented insulated surfaces with a layer of finishing cement and coat with a mastic. Install vapor -barrier mastic for below ambient services and a breather mastic for above ambient services. Reinforce the mastic with fabric -reinforcing mesh. Trowel the mastic to a smooth and well -shaped contour. 8. For services not specified to receive a field -applied jacket except for flexible elastomeric install fitted PVC cover over elbows, tees, strainers, valves, flanges, and unions. Terminate ends with PVC end caps. Tape PVC covers to adjoining insulation facing using PVC tape. 9. Stencil or label the outside insulation jacket of each union with the word "UNION." Match size and color of pipe labels. C. Insulate instrument connections for thermometers, pressure gages, pressure temperature taps, test connections, flow meters, sensors, switches, and transmitters on insulated pipes, vessels, and equipment. Shape insulation at these connections by tapering it to and around the connection with insulating cement and finish with finishing cement, mastic, and flashing sealant. 3.6 FLEXIBLE ELASTOMERIC INSULATION INSTALLATION A. Seal longitudinal seams and end joints with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. PLUMBING INSULATION 220700 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Insulation Installation on Pipe Flanges: 1. Install pipe insulation to outer diameter of pipe flange. 2. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness of pipe insulation. 3. Fill voids between inner circumference of flange insulation and outer circumference of adjacent straight pipe segments with cut sections of sheet insulation of same thickness as pipe insulation. 4. Secure insulation to flanges and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. C. Insulation Installation on Pipe Fittings and Elbows: 1. Install mitered sections of pipe insulation. 2. Secure insulation materials and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. D. Insulation Installation on Valves and Pipe Specialties: 1. Install preformed valve covers manufactured of same material as pipe insulation when available. 2. When preformed valve covers are not available, install cut sections of pipe and sheet insulation to valve body. Arrange insulation to permit access to packing and to allow valve operation without disturbing insulation. 3. Install insulation to flanges as specified for flange insulation application. 4. Secure insulation to valves and specialties and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. 3.7 MINERAL -FIBER INSULATION INSTALLATION A. Insulation Installation on Straight Pipes and Tubes: 1. Secure each layer of preformed pipe insulation to pipe with wire or bands and tighten bands without deforming insulation materials. 2. Where vapor barriers are indicated, seal longitudinal seams, end joints, and protrusions with vapor -barrier mastic and joint sealant. 3. For insulation with factory -applied jackets on above ambient surfaces, secure laps with outward clinched staples at 6 inches o.c. 4. For insulation with factory -applied jackets on below ambient surfaces, do not staple longitudinal tabs but secure tabs with additional adhesive as recommended by insulation material manufacturer and seal with vapor -barrier mastic and flashing sealant. B. Insulation Installation on Pipe Flanges: 1. Install preformed pipe insulation to outer diameter of pipe flange. 2. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness of pipe insulation. 3. Fill voids between inner circumference of flange insulation and outer circumference of adjacent straight pipe segments with mineral -fiber blanket insulation. 4. Install jacket material with manufacturer's recommended adhesive, overlap seams at least 1 inch, and seal joints with flashing sealant. C. Insulation Installation on Pipe Fittings and Elbows: PLUMBING INSULATION 220700 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Install preformed sections of same material as straight segments of pipe insulation when available. 2. When preformed insulation elbows and fittings are not available, install mitered sections of pipe insulation, to a thickness equal to adjoining pipe insulation. Secure insulation materials with wire or bands. D. Insulation Installation on Valves and Pipe Specialties: 1. Install preformed sections of same material as straight segments of pipe insulation when available. 2. When preformed sections are not available, install mitered sections of pipe insulation to valve body. 3. Arrange insulation to permit access to packing and to allow valve operation without disturbing insulation. 4. Install insulation to flanges as specified for flange insulation application. 3.8 FINISHES A. Equipment and Pipe Insulation with ASJ, Glass -Cloth, or Other Paintable Jacket Material: Paint jacket with paint system identified below and as specified in Division 09 painting Sections. 1. Flat Acrylic Finish: Two finish coats over a primer that is compatible with jacket material and finish coat paint. Add fungicidal agent to render fabric mildew proof. a. Finish Coat Material: Interior, flat, latex -emulsion size. B. Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats of insulation manufacturer's recommended protective coating. C. Color: Final color as selected by Architect. Vary first and second coats to allow visual inspection of the completed Work. D. Do not field paint aluminum or stainless-steel jackets. 3.9 PIPING INSULATION SCHEDULE, GENERAL A. Acceptable preformed pipe and tubular insulation materials and thicknesses are identified for each piping system and pipe size range. If more than one material is listed for a piping system, selection from materials listed is Contractor's option. 3.10 INDOOR PIPING INSULATION SCHEDULE A. Domestic Hot and Recirculated Hot Water: 1. Insulation shall be one of the following: a. Mineral -Fiber, Preformed Pipe Insulation, Type I: 1 inch thick. B. Stormwater and Overflow: 1. All Pipe Sizes: Insulation shall be one of the following: PLUMBING INSULATION 220700 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Mineral -Fiber, Preformed Pipe Insulation, Type I: minimum %" thick. C. Roof Drain and Overflow Drain Bodies: 1. All Pipe Sizes: Insulation shall be one of the following: a. Mineral -Fiber, Preformed Pipe Insulation, Type I: minimum''/2" thick. D. Condensate and Equipment Drain Water: 1. All Pipe Sizes: Insulation shall be one of the following: a. Flexible Elastomeric: 3/4 inch thick. END OF SECTION 220700 PLUMBING INSULATION 220700 - 11 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 221116 - DOMESTIC WATER PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Under -building -slab and aboveground domestic water pipes, tubes, and fittings inside buildings. 2. Encasement for piping. 1.3 ACTION SUBMITTALS A. Product Data: For transition fittings and dielectric fittings. 1.4 INFORMATIONAL SUBMITTALS A. System purging and disinfecting activities report. B. Field quality -control reports. PART 2 - PRODUCTS 2.1 PIPING MATERIALS Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, fitting materials, and joining methods for specific services, service locations, and pipe sizes. B. Potable -water piping and components shall comply with NSF 14 and NSF 61. Plastic piping components shall be marked with "NSF-pw." 2.2 COPPER TUBE AND FITTINGS A. Hard Copper Tube: ASTM B 88, Type L water tube, drawn temper. B. Soft Copper Tube: ASTM B 88, Type K and ASTM B 88, Type L water tube, annealed temper. C. Wrought -Copper, Solder -Joint Fittings: ASME B16.22, wrought -copper pressure fittings. D. Bronze Flanges: ASME B16.24, Class 150, with solder -joint ends. DOMESTIC WATER PIPING 221116 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS E. Copper Unions: 1. MSS SP -123. 2. Cast -copper -alloy, hexagonal -stock body. 3. Ball-and-socket, metal -to -metal seating surfaces. 4. Solder -joint or threaded ends. F. Copper Pressure -Seal -Joint Fittings: 1. Basis -of -Design Product: Subject to compliance with requirements, provide products by one of the following: a. Elkhart Products Corporation. b. NIBCO Inc. c. Viega. 2. Fittings for NPS 2 and Smaller: Wrought -copper fitting with EPDM-rubber, 0 -ring seal in each end. 3. Fittings for NPS 2-1/2 to NPS 4: Cast -bronze or wrought -copper fitting with EPDM- rubber, 0 -ring seal in each end. 2.3 PIPING JOINING MATERIALS A. Pipe -Flange Gasket Materials: 1. AWWA C110/A21.10, rubber, flat face, 1/8 inch thick or ASME 616.21, nonmetallic and asbestos free unless otherwise indicated. 2. Full -face or ring type unless otherwise indicated. B. Metal, Pipe -Flange Bolts and Nuts: ASME 618.2.1, carbon steel unless otherwise indicated. C. Solder Filler Metals: ASTM B 32, lead-free alloys. D. Flux: ASTM B 813, water flushable. 2.4 ENCASEMENT FOR PIPING A. Standard: ASTM A 674 or AWWA C105/A21.5. B. Form: Sheet or tube. C. Color Black or natural. 2.5 TRANSITION FITTINGS A. General Requirements: 1. Same size as pipes to be joined. 2. Pressure rating at least equal to pipes to be joined. 3. End connections compatible with pipes to be joined. DOMESTIC WATER PIPING 221116 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Fitting -Type Transition Couplings: Manufactured piping coupling or specified piping system fitting. C. Sleeve -Type Transition Coupling: AWWA C219. 1. Basis -of -Design Product: Subject to compliance with requirements, provide products by one of the following: a. Cascade Waterworks Manufacturing. b. Dresser, Inc.; Piping Specialties Products. c. Ford Meter Box Company, Inc. (The). D. Plastic -to -Metal Transition Fittings: 1. Basis -of -Design Product: Subject to compliance with requirements, provide products by one of the following: a. Charlotte Pipe and Foundry Company. b. Harvel Plastics, Inc. c. Spears Manufacturing Company. 2. Description: a. CPVC or PVC one-piece fitting with manufacturer's Schedule 80 equivalent dimensions. b. One end with threaded brass insert and one solvent -cement -socket or threaded end. E. Plastic -to -Metal Transition Unions: 1. Basis -of -Design Product: Subject to compliance with requirements, provide products by one of the following: a. Colonial Engineering, Inc. b. NIBCO Inc. c. Spears Manufacturing Company. Description: a. CPVC or PVC four-part union. b. Brass or stainless-steel threaded end. c. Solvent -cement -joint or threaded plastic end. d. Rubber 0 -ring. e. Union nut. 2.6 DIELECTRIC FITTINGS A. General Requirements: Assembly of copper alloy and ferrous materials with separating nonconductive insulating material. Include end connections compatible with pipes to be joined. DOMESTIC WATER PIPING 221116 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Dielectric Unions: 1. Basis -of -Design Product: Subject to compliance with requirements, products by one of the following: a. Capitol Manufacturing Company; member of the Phoenix Forge Group. b. Central Plastics Company. c. Watts; a division of Watts Water Technologies, Inc. 2. Standard: ASSE 1079. 3. Pressure Rating: 150 psig. 4. End Connections: Solder -joint copper alloy and threaded ferrous. C. Dielectric Flanges: 1. Basis -of -Design Product: Subject to compliance with requirements, provide products by one of the following: a. Capitol Manufacturing Company; member of the Phoenix Forge Group. b. Matco-Norca. c. Watts; a division of Watts Water Technologies, Inc. 2. Standard: ASSE 1079. 3. Factory -fabricated, bolted, companion -flange assembly. 4. Pressure Rating150 psig. 5. End Connections: Solder -joint copper alloy and threaded ferrous; threaded solder -joint copper alloy and threaded ferrous. D. Dielectric -Flange Insulating Kits: 1. Basis -of -Design Product: Subject to compliance with requirements, provide products by one of the following: a. Advance Products & Systems, Inc. b. Calpico, Inc. c. Pipeline Seal and Insulator, Inc. 2. Nonconducting materials for field assembly of companion flanges. 3. Pressure Rating: 150 psig 4. Gasket: Neoprene or phenolic. 5. Bolt Sleeves: Phenolic or polyethylene. 6. Washers: Phenolic with steel backing washers. E. Dielectric Nipples: 1. Basis -of -Design Product: Subject to compliance with requirements, provide products by one of the following: a. Elster Perfection Corporation. b. Precision Plumbing Products, Inc. c. Victaulic Company. 2. Standard: IAPMO PS 66. 3. Electroplated steel nipple complying with ASTM F 1545. 4. Pressure Rating and Temperature: 300 psig at 225 deg F DOMESTIC WATER PIPING 221116 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 5. End Connections: Male threaded or grooved. 6. Lining: Inert and noncorrosive, propylene. PART 3 - EXECUTION 3.1 EARTHWORK A. Comply with requirements in Section 312000 "Earth Moving" for excavating, trenching, and backfilling. 3.2 PIPING INSTALLATION A. Drawing plans, schematics, and diagrams indicate general location and arrangement of domestic water piping. Indicated locations and arrangements are used to size pipe and calculate friction loss, expansion, and other design considerations. Install piping as indicated unless deviations to layout are approved on coordination drawings. B. Install copper tubing under building slab according to CDA's "Copper Tube Handbook." C. Install underground copper tube in PE encasement according to ASTM A 674 or AWWA C105/A21.5. D. Install shutoff valve, hose -end drain valve, strainer, pressure gage, and test tee with valve inside the building at each domestic water -service entrance. Comply with requirements for pressure gages in Section 220519 "Meters and Gages for Plumbing Piping" and with requirements for drain valves and strainers in Section 221119 "Domestic Water Piping Specialties." E. Install shutoff valve immediately upstream of each dielectric fitting. F. Install water -pressure -reducing valves downstream from shutoff valves. Comply with requirements for pressure -reducing valves in Section 221119 "Domestic Water Piping Specialties." G. Install domestic water piping without pitch and plumb H. Rough -in domestic water piping for water -meter installation according to utility company's requirements. Install piping concealed from view and protected from physical contact by building occupants unless otherwise indicated and except in equipment rooms and service areas. J. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise. K. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal, and coordinate with other services occupying that space. L. Install piping to permit valve servicing. DOMESTIC WATER PIPING 221116 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS M. N. O. P. Q. R. S. T. Install nipples, unions, special fittings, and valves with pressure ratings the same as or higher than the system pressure rating used in applications below unless otherwise indicated. Install piping free of sags and bends. Install fittings for changes in direction and branch connections. Install unions in copper tubing at final connection to each piece of equipment, machine, and specialty. Install thermostats in hot-water circulation piping. Comply with requirements for thermostats in Section 221123 "Domestic Water Pumps." Install thermometers on outlet piping from each water heater. Comply with requirements for thermometers in Section 220519 "Meters and Gages for Plumbing Piping." Install sleeves for piping penetrations of walls, ceilings, and floors. Comply with requirements for sleeves specified in Section 220500 "Common Work Results for Plumbing." Install sleeve seals for piping requirements for sleeve seals Plumbing." U. Install escutcheons for piping requirements for escutcheons Plumbing." 3.3 JOINT CONSTRUCTION penetrations specified in penetrations specified in of concrete walls and slabs. Comply with Section 220500 "Common Work Results for of walls, ceilings, and floors. Comply with Section 220500 "Common Work Results for A. Ream ends of pipes and tubes and remove burrs. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and fittings before assembly. C. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows: 1. Apply appropriate tape or thread compound to external pipe threads. 2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. D. Soldered Joints for Copper Tubing: Apply ASTM B 813, water-flushable flux to end of tube. Join copper tube and fittings according to ASTM B 828 or CDA's "Copper Tube Handbook." E. Pressure -Sealed Joints for Copper Tubing: Join copper tube and pressure -seal fittings with tools recommended by fitting manufacturer. F. Joints for Dissimilar -Material Piping: Make joints using adapters compatible with materials of both piping systems. DOMESTIC WATER PIPING 221116 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.4 TRANSITION FITTING INSTALLATION A. Install transition couplings at joints of dissimilar piping. B. Transition Fittings in Underground Domestic Water Piping: 1. Fittings for NPS 1-1/2 and Smaller: Fitting -type coupling. 2. Fittings for NPS 2 and Larger: Sleeve -type coupling. C. Transition Fittings in Aboveground Domestic Water Piping NPS 2 and Smaller: Plastic -to -metal transition fittings or unions. 3.5 DIELECTRIC FITTING INSTALLATION A. Install dielectric fittings in piping at connections of dissimilar metal piping and tubing. B. Dielectric Fittings for NPS 2 and Smaller: Use dielectric couplings or nipples. C. Dielectric Fittings for NPS 2-1/2 to NPS 4: Use dielectric flanges, flange kits or nipples. 3.6 HANGER AND SUPPORT INSTALLATION A. Comply with requirements for pipe hanger, support products, and installation in Section 220529 "Hangers and Supports for Plumbing Piping and Equipment." 1. Vertical Piping: MSS Type 8 or 42, clamps. 2. Individual, Straight, Horizontal Piping Runs: a. 100 Feet and Less: MSS Type 1, adjustable, steel clevis hangers. b. Longer Than 100 Feet: MSS Type 43, adjustable roller hangers. c. Longer Than 100 Feet if Indicated: MSS Type 49, spring cushion rolls. 3. Multiple, Straight, Horizontal Piping Runs 100 Feet or Longer: MSS Type 44, pipe rolls. Support pipe rolls on trapeze. 4. Base of Vertical Piping: MSS Type 52, spring hangers. B. Support vertical piping and tubing at base and at each floor. C. Rod diameter may be reduced one size for double -rod hangers, to a minimum of 3/8 inch D. Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters: 1. NPS 3/4 and Smaller: 60 inches with 3/8 -inch rod. 2. NPS 1 and NPS 1-1/4: 72 inches with 3/8 -inch rod. 3. NPS 1-1/2 and NPS 2: 96 inches with 3/8 -inch rod. 4. NPS 2-1/2: 108 inches with 1/2 -inch rod. 5. NPS 3 to NPS 5: 10 feet with 1/2 -inch rod. E. Install supports for vertical copper tubing every 10 feet F. Support piping and tubing not listed in this article according to MSS SP -69 and manufacturer's written instructions. DOMESTIC WATER PIPING 221116 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.7 CONNECTIONS A. Drawings indicate general arrangement of piping, fittings, and specialties. B. When installing piping adjacent to equipment and machines, allow space for service and maintenance. C. Connect domestic water piping to exterior water -service piping. Use transition fitting to join dissimilar piping materials. D. Connect domestic water piping to water -service piping with shutoff valve; extend and connect to the following: 1. Water Heaters: Cold -water inlet and hot-water outlet piping in sizes indicated, but not smaller than sizes of water heater connections. 2. Plumbing Fixtures: Cold- and hot -water -supply piping in sizes indicated, but not smaller than that required by plumbing code. 3. Equipment: Cold- and hot -water -supply piping as indicated, but not smaller than equipment connections. Provide shutoff valve and union for each connection. Use flanges instead of unions for NPS 2-1/2 and larger. 3.8 IDENTIFICATION A. Identify system components. Comply with requirements for identification materials and installation in Section 220553 "Identification for Plumbing Piping and Equipment." B. Label pressure piping with system operating pressure. 3.9 FIELD QUALITY CONTROL A. Perform the following tests and inspections: 1. Piping Inspections: a. Do not enclose, cover, or put piping into operation until it has been inspected and approved by authorities having jurisdiction. b. During installation, notify authorities having jurisdiction at least one day before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction: 1) Roughing -in Inspection: Arrange for inspection of piping before concealing or closing in after roughing in and before setting fixtures. 2) Final Inspection: Arrange for authorities having jurisdiction to observe tests specified in 'Piping Tests" Subparagraph below and to ensure compliance with requirements. c. Reinspection: If authorities having jurisdiction find that piping will not pass tests or inspections, make required corrections and arrange for reinspection. d. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction. 2. Piping Tests: DOMESTIC WATER PIPING 221116 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Fill domestic water piping. Check components to determine that they are not air bound and that piping is full of water. b. Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit a separate report for each test, complete with diagram of portion of piping tested. c. Leave new, altered, extended, or replaced domestic water piping uncovered and unconcealed until it has been tested and approved. Expose work that was covered or concealed before it was tested. d. Cap and subject piping to static water pressure of 50 psig above operating pressure, without exceeding pressure rating of piping system materials. Isolate test source and allow it to stand for four hours. Leaks and loss in test pressure constitute defects that must be repaired. e. Repair leaks and defects with new materials, and retest piping or portion thereof until satisfactory results are obtained. f. Prepare reports for tests and for corrective action required. B. Domestic water piping will be considered defective if it does not pass tests and inspections. C. Prepare test and inspection reports. 3.10 ADJUSTING A. Perform the following adjustments before operation: 1. Close drain valves, hydrants, and hose bibbs. 2. Open shutoff valves to fully open position. 3. Open throttling valves to proper setting. 4. Adjust balancing valves in hot -water -circulation return piping to provide adequate flow. a. Manually adjust ball -type balancing valves in hot -water -circulation return piping to provide hot-water flow in each branch. b. Adjust calibrated balancing valves to flows indicated. 5. Remove plugs used during testing of piping and for temporary sealing of piping during installation. 6. Remove and clean strainer screens. Close drain valves and replace drain plugs. 7. Remove filter cartridges from housings and verify that cartridges are as specified for application where used and are clean and ready for use. 8. Check plumbing specialties and verify proper settings, adjustments, and operation. 3.11 CLEANING A. Clean and disinfect potable domestic water piping as follows: 1. Purge new piping before using. 2. Use purging and disinfecting procedures prescribed by authorities having jurisdiction; if methods are not prescribed, use procedures described in either AWWA C651 or AWWA C652 or follow procedures described below: a. Flush piping system with clean, potable water until dirty water does not appear at outlets. DOMESTIC WATER PIPING 221116 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS b. Fill and isolate system according to either of the following: 1) Fill system or part thereof with water/chlorine solution with at least 50 ppm of chlorine. Isolate with valves and allow to stand for 24 hours. 2) Fill system or part thereof with water/chlorine solution with at least 200 ppm of chlorine. Isolate and allow to stand for three hours. c. Flush system with clean, potable water until no chlorine is in water coming from system after the standing time. d. Repeat procedures if biological examination shows contamination. e. Submit water samples in sterile bottles to authorities having jurisdiction. B. Prepare and submit reports of purging and disinfecting activities. Include copies of water - sample approvals from authorities having jurisdiction. C. Clean interior of domestic water piping system. Remove dirt and debris as work progresses. 3.12 PIPING SCHEDULE A. Transition and special fittings with pressure ratings at least equal to piping rating may be used in applications below unless otherwise indicated. B. Under -building -slab, domestic water, building -service piping, NPS 3 and smaller shall be the following: 1. Soft copper tube, ASTM B 88, Type K wrought -copper, solder -joint fittings. C. Aboveground domestic water piping, NPS 2 and smaller, shall be one of the following: 1. Hard copper tube, ASTM B 88, Type L wrought -copper, solder -joint fittings; and soldered joints. 2. Hard copper tube, ASTM B 88, Type L; copper pressure -seal -joint fittings; and pressure - sealed joints. D. Aboveground domestic water piping, NPS 2-1/2 to NPS 4, shall be one of the following: 1. Hard copper tube, ASTM B 88, Type L wrought -copper, solder -joint fittings; and soldered joints. 2. Hard copper tube, ASTM B 88, Type L copper pressure -seal -joint fittings; and pressure - sealed joints. 3.13 VALVE SCHEDULE A. Drawings indicate valve types to be used. Where specific valve types are not indicated, the following requirements apply: 1. Shutoff Duty: Use ball or gate valves for piping NPS 2 and smaller. Use ball or gate valves with flanged ends for piping NPS 2-1/2 and larger. 2. Throttling Duty: Use ball or globe valves for piping NPS 2 and smaller. Use ball valves with flanged ends for piping NPS 2-1/2 and larger. 3. Hot -Water Circulation Piping, Balancing Duty: Calibrated balancing valves. 4. Drain Duty: Hose -end drain valves. DOMESTIC WATER PIPING 221116 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Use check valves to maintain correct direction of domestic water flow to and from equipment. END OF SECTION 221116 DOMESTIC WATER PIPING 221116 - 11 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 221119 - DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Backflow preventers. 2. Water pressure -reducing valves. 3. Balancing valves. 4. Temperature -actuated, water mixing valves. 5. Strainers. 6. Outlet boxes. 7. Hose bibbs. 8. Wall hydrants. 9. Drain valves. 10. Water -hammer arresters. 11. Trap -seal primer valves. B. Related Requirements: 1. Section 220519 "Meters and Gages for Plumbing Piping" for thermometers, pressure gages, and flow meters in domestic water piping. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. 1.4 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For domestic water piping specialties to include in emergency, operation, and maintenance manuals. PART 2 - PRODUCTS 2.1 GENERAL REQUIREMENTS FOR PIPING SPECIALTIES A. Potable -water piping and components shall comply with NSF 61 and NSF 14. DOMESTIC WATER PIPING SPECIALTIES 221119 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.2 PERFORMANCE REQUIREMENTS A. Minimum Working Pressure for Domestic Water Piping Specialties: 125 psig unless otherwise indicated. 2.3 BACKFLOW PREVENTERS A. Reduced -Pressure -Principle Backflow Preventers: 1. Basis -of -Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following: a. Ames Fire & Waterworks; a division of Watts Water Technologies, Inc. b. Conbraco Industries, Inc. c. FEBCO; a division of Watts Water Technologies, Inc. 2. Standard: ASSE 1013. 3. Operation: Continuous -pressure applications. 4. Pressure Loss: 12 psig maximum, through middle third of flow range. 5. End Connections: Threaded for NPS 2 and smaller; flanged for NPS 2-1/2 and larger. 6. Configuration: Refer to drawings: a. Valves NPS 2 and Smaller: Ball type with threaded ends on inlet and outlet. 2.4 WATER PRESSURE -REDUCING VALVES A. Water Regulators: 1. Basis -of -Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following: a. Cash Acme; a division of Reliance Worldwide Corporation. b. Conbraco Industries, Inc. c. Watts; a division of Watts Water Technologies, Inc.; Watts Regulator Company. 2. Standard: ASSE 1003. 3. Pressure Rating: Initial working pressure of 150 psig. 2.5 BALANCING VALVES A. Copper -Alloy Calibrated Balancing Valves: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following : a. ITT Corporation; Bell & Gossett Div. b. TACO Incorporated. c. Watts; a division of Watts Water Technologies, Inc.; Watts Regulator Company. 2. Type: Ball valve with two readout ports and memory -setting indicator. DOMESTIC WATER PIPING SPECIALTIES 221119 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3. Body: Brass or bronze. 4. Size: Same as connected piping, but not larger than NPS 2. B. Accessories: Meter hoses, fittings, valves, differential pressure meter, and carrying case. 2.6 TEMPERATURE -ACTUATED, WATER MIXING VALVES A. Primary, Thermostatic, Water Mixing Valves: 1. Basis -of -Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following: a. Armstrong International, Inc. b. Leonard Valve Company. c. Powers; a division of Watts Water Technologies, Inc. 2. Standard: ASSE 1017. 3. Pressure Rating: 125 psig minimum unless otherwise indicated. 4. Type: Exposed -mounted, thermostatically controlled, water mixing valve. 5. Material: Bronze body with corrosion -resistant interior components. 6. Connections: Threaded union inlets and outlet. 7. Accessories: Manual temperature control, check stops on hot- and cold -water supplies, and adjustable, temperature -control handle. B. Individual -Fixture, Water Tempering: 1. Basis -of -Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following: a. Leonard Valve Company. b. Powers; a division of Watts Water Technologies, Inc. c. Watts; a division of Watts Water Technologies, Inc.; Watts Regulator Company. 2. Standard: ASSE 1016, thermostatically controlled, water tempering valve. 3. Pressure Rating: 125 psig minimum unless otherwise indicated. 4. Body: Bronze body with corrosion -resistant interior components. 5. Temperature Control: Adjustable. 6. Inlets and Outlet: Threaded. 7. Finish: Rough or chrome -plated bronze. 2.7 STRAINERS FOR DOMESTIC WATER PIPING A. Y -Pattern Strainers: 1. Pressure Rating: 125 psig minimum unless otherwise indicated. 2. Body: Bronze for NPS 2 and smaller; cast iron with interior lining that complies with AWWA C550 or that is FDA approved, epoxy coated and for NPS 2-1/2 and larger. 3. End Connections: Threaded for NPS 2 and smaller; flanged for NPS 2-1/2 and larger. 4. Screen: Stainless steel with round perforations unless otherwise indicated. 5. Perforation Size: a. Strainers NPS 2-1/2 to NPS 4: 0.045 inch DOMESTIC WATER PIPING SPECIALTIES 221119 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 6. Drain: Factory -installed, hose -end drain valve. 2.8 OUTLET BOXES A. Icemaker Outlet Boxes: 1. Basis -of -Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following: a. Acorn Engineering Company. b. IPS Corporation. c. Oatey. 2. Mounting: Recessed. 3. Faucet: Valved fitting complying with ASME A112.18.1. Include NPS 1/2 or smaller copper tube outlet. 4. Supply Shutoff Fitting: NPS 1/2 gate, globe, or ball valve and NPS 1/2 copper, water tubing. 2.9 HOSE BIBBS A. Hose Bibbs: 1. Standard: ASME A112.18.1 for sediment faucets. 2. Body Material: Bronze. 3. Seat: Bronze, replaceable. 4. Supply Connections: NPS 3/4 threaded or solder -joint inlet. 5. Outlet Connection: Garden -hose thread complying with ASME B1.20.7. 6. Pressure Rating: 125 psig. 7. Vacuum Breaker: Integral nonremovable, drainable, hose -connection vacuum breaker complying with ASSE 1011. 8. Finish for Equipment Rooms: Rough bronze, or chrome or nickel plated. 9. Finish for Service Areas: Rough bronze or Chrome or nickel plated. 10. Finish for Finished Rooms: Chrome or nickel plated. 11. Operation for Equipment Rooms: Wheel handle. 12. Operation for Service Areas: Operating key. 13. Operation for Finished Rooms: Operating key. 14. Include operating key with each operating -key hose bibb. 15. Include wall flange with each chrome- or nickel -plated hose bibb. 2.10 WALL HYDRANTS A. Moderate -Climate Wall Hydrants: 1. Basis -of -Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following: a. MIFAB, Inc. b. Watts Drainage Products. c. Woodford Manufacturing Company; a division of WCM Industries, Inc 2. Standard: ASME A112.21.3M for concealed -outlet, self -draining wall hydrants. DOMESTIC WATER PIPING SPECIALTIES 221119 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3. Pressure Rating: 125 psig 4. Operation: Loose key. 5. Inlet: NPS 3/4. 6. Box and Cover Finish: Chrome plated . 7. Operating Keys(s): One with each wall hydrant. 2.11 DRAIN VALVES A. Ball -Valve -Type, Hose -End Drain Valves: 1. Standard: MSS SP -110 for standard -port, two-piece ball valves. 2. Pressure Rating: 400-psig minimum CWP. 3. Size: NPS 3/4. 4. Body: Copper alloy. 5. Ball: Chrome -plated brass. 6. Seats and Seals: Replaceable. 7. Handle: Vinyl -covered steel. 8. Inlet: Threaded or solder joint. 9. Outlet: Threaded, short nipple with garden -hose thread complying with ASME B1.20.7 and cap with brass chain. 2.12 WATER -HAMMER ARRESTERS A. Water -Hammer Arresters: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Josam Company. b. Sioux Chief Manufacturing Company, Inc. c. Smith, Jay R. Mfg. Co.; Division of Smith Industries, Inc. 2. Standard: ASSE 1010 or PDI -WH 201. 3. Type: Copper tube with piston. 4. Size: ASSE 1010, Sizes AA and A through F, or PDI -WH 201, Sizes A through F. 2.13 TRAP -SEAL PRIMER DEVICE A. Supply -Type, Trap -Seal Primer Device: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. MIFAB, Inc. b. Precision Plumbing Products, Inc. c. Sioux Chief Manufacturing Company, Inc. 2. Standard: ASSE 1018. 3. Pressure Rating: 125 psig minimum. 4. Body: Bronze. 5. Inlet and Outlet Connections: NPS 1/2 threaded, union, or solder joint. DOMESTIC WATER PIPING SPECIALTIES 221119 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 6. Gravity Drain Outlet Connection: NPS 1/2 threaded or solder joint. 7. Finish: Chrome plated, or rough bronze for units used with pipe or tube that is not chrome finished. PART 3 - EXECUTION 3.1 INSTALLATION A. Install backflow preventers in each water supply to mechanical equipment and systems and to other equipment and water systems that may be sources of contamination. Comply with authorities having jurisdiction. 1. Locate backflow preventers in same room as connected equipment or system. 2. Install drain for backflow preventers with atmospheric -vent drain connection with air -gap fitting, fixed air -gap fitting, or equivalent positive pipe separation of at least two pipe diameters in drain piping and pipe -to -floor drain. Locate air -gap device attached to or under backflow preventer. Simple air breaks are unacceptable for this application. 3. Do not install bypass piping around backflow preventers. Install water regulators with inlet and outlet shutoff valves. Install pressure gages on inlet and outlet. C. Install balancing valves in locations where they can easily be adjusted. D. Install temperature -actuated, water mixing valves with check stops or shutoff valves on inlets and with shutoff valve on outlet. E. Install Y -pattern strainers for water on supply side of each water pressure -reducing valve solenoid valve and pump. F. Install outlet boxes recessed in wall. Install 2 -by -4 -inch fire -retardant -treated -wood blocking, wall reinforcement between studs. Comply with requirements for fire -retardant -treated -wood blocking in Section 061000 "Rough Carpentry." G. Install water -hammer arresters in water piping according to PDI -WH 201. H. Install supply -type, trap -seal primer valves with outlet piping pitched down toward drain trap a minimum of 1 percent, and connect to floor -drain body, trap, or inlet fitting. Adjust valve for proper flow. 3.2 CONNECTIONS A. Comply with requirements for ground equipment in Section 260526 "Grounding and Bonding for Electrical Systems." B. Fire -retardant -treated -wood blocking is specified in Section 260519 "Low -Voltage Electrical Power Conductors and Cables" for electrical connections. DOMESTIC WATER PIPING SPECIALTIES 221119 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.3 LABELING AND IDENTIFYING A. Equipment Nameplates and Signs: Install engraved plastic -laminate equipment nameplate or sign on or near each of the following: 1. Reduced -pressure -principle backflow preventers. 2. Double-check, backflow -prevention assemblies. 3. Double-check, detector -assembly backflow preventers. 4. Water pressure -reducing valves. 5. Calibrated balancing valves. 6. Primary, thermostatic, water mixing valves. B. Distinguish among multiple units, inform operator of operational requirements, indicate safety and emergency precautions, and warn of hazards and improper operations, in addition to identifying unit. Nameplates and signs are specified in Section 220553 "Identification for Plumbing Piping and Equipment." 3.4 FIELD QUALITY CONTROL A. Perform the following tests and inspections: 1. Test each pressure vacuum breaker reduced -pressure -principle backflow preventer and double-check, detector -assembly backflow preventer according to authorities having jurisdiction and the device's reference standard. B. Domestic water piping specialties will be considered defective if they do not pass tests and inspections. C. Prepare test and inspection reports. 3.5 ADJUSTING A. Set field -adjustable pressure set points of water pressure -reducing valves. B. Set field -adjustable flow set points of balancing valves. C. Set field -adjustable temperature set points of temperature -actuated, water mixing valves. END OF SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES 221119 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 221123 - DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. In-line, sealless centrifugal pumps. 1.3 DEFINITIONS A. Low Voltage: As defined in NFPA 70 for circuits and equipment operating at less than 50 V or for remote -control, signaling power -limited circuits. 1.4 ACTION SUBMITTALS A. Product Data: For each type of product indicated. Include materials of construction, rated capacities, certified performance curves with operating points plotted on curves, operating characteristics, electrical characteristics, and furnished specialties and accessories. 1.5 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For domestic water pumps to include in operation and maintenance manuals. 1.6 QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. UL Compliance: Comply with UL 778 for motor -operated water pumps. 1.7 DELIVERY, STORAGE, AND HANDLING A. Retain shipping flange protective covers and protective coatings during storage. B. Protect bearings and couplings against damage. C. Comply with pump manufacturer's written handling instructions. DOMESTIC WATER PUMPS 221123 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART2-PRODUCTS 2.1 IN-LINE, SEALLESS CENTRIFUGAL PUMPS A. Basis -of -Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following: 1. Bell & Gossett Domestic Pump; ITT Corporation. 2. Grundfos Pumps Corp. 3. TACO Incorporated. B. Description: Factory -assembled and -tested, in-line, close -coupled, canned -motor, sealless, overhung -impeller centrifugal pumps. C. Pump Construction: 1. Pump and Motor Assembly: Hermetically sealed, replaceable -cartridge type with motor and impeller on common shaft and designed for installation with pump and motor shaft horizontal. 2. Casing: Bronze, with threaded or companion -flange connections. 3. Impeller: Plastic. 4. Motor: Single speed, unless otherwise indicated. D. Capacities and Characteristics: 1. Refer to plumbing drawings. 2.2 MOTORS A. Comply with NEMA designation, temperature rating, service factor, enclosure type, and efficiency requirements for motors specified in Section 220513 "Common Motor Requirements for Plumbing Equipment." 1. Motor Sizes: Minimum size as indicated. If not indicated, large enough so driven load will not require motor to operate in service factor range above 1.0. 2.3 CONTROLS A. Thermostats: Electric; adjustable for control of hot-water circulation pump. 1. Type: Water -immersion temperature sensor, for installation in piping. 2. Range: 65 to 200 deg F. 3. Operation of Pump: On or off. 4. Transformer: Provide if required. 5. Power Requirement: 120 V, ac. 6. Settings: Start pump at 105 deg F and stop pump at 120 deg F. B. Timers: Electric, for control of hot-water circulation pump. 1. Type: Programmable, seven-day clock with manual override on-off switch. 2. Operation of Pump: On or off. 3. Transformer: Provide if required. DOMESTIC WATER PUMPS 221123 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 4. Power Requirement: 24-V ac 5. Programmable Sequence of Operation: Up to two on-off cycles each day for seven days. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine roughing -in of domestic -water -piping system to verify actual locations of connections before pump installation. 3.2 PUMP INSTALLATION A. Comply with HI 1.4. B. Install in-line, sealless centrifugal pumps with shaft horizontal unless otherwise indicated. C. Install horizontally mounted, in-line, close -coupled centrifugal pumps with shaft(s) horizontal. D. Install vertically mounted, in-line, close -coupled centrifugal pumps with shaft vertical. E. Install continuous -thread hanger rods and spring hangers of size required to support pump weight. 1. Comply with requirements for hangers and supports specified in Section 220529 "Hangers and Supports for Plumbing Piping and Equipment." F. Install thermostats in hot-water return piping. G. Install timers on wall in engineer's office. 3.3 CONNECTIONS A. Comply with requirements for piping specified in Section 221116 "Domestic Water Piping." Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to pumps to allow service and maintenance. C. Connect domestic water piping to pumps. Install suction and discharge piping equal to or greater than size of pump nozzles. Install flexible connectors adjacent to pumps in suction and discharge piping of the following pumps: a. Horizontally mounted, in-line, close -coupled centrifugal pumps. b. Vertically mounted, in-line, close -coupled centrifugal pumps. c. Comply with requirements for flexible connectors specified in Section 221116 "Domestic Water Piping." 2. Install shutoff valve and strainer on suction side of each pump, and check, shutoff, and throttling valves on discharge side of each pump. Install valves same size as connected piping. Comply with requirements for valves specified in Section 220523 "General -Duty DOMESTIC WATER PUMPS 221123 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Valves for Plumbing Piping" and comply with requirements for strainers specified in Section 221119 "Domestic Water Piping Specialties." D. Connect thermostats and timers to pumps that they control. 3.4 IDENTIFICATION A. Comply with requirements for identification specified in Section 220553 "Identification for Plumbing Piping and Equipment" for identification of pumps. 3.5 STARTUP SERVICE A. Perform startup service. 1. Complete installation and startup checks according to manufacturer's written instructions. 2. Check piping connections for tightness. 3. Clean strainers on suction piping. 4. Set thermostats and timers, for automatic starting and stopping operation of pumps. 5. Perform the following startup checks for each pump before starting: a. Verify bearing lubrication. b. Verify that pump is free to rotate by hand and that pump for handling hot liquid is free to rotate with pump hot and cold. If pump is bound or drags, do not operate until cause of trouble is determined and corrected. c. Verify that pump is rotating in the correct direction. 6. Prime pump by opening suction valves and closing drains, and prepare pump for operation. 7. Start motor. 8. Open discharge valve slowly. 9. Adjust temperature settings on thermostats. 10. Adjust timer settings. 3.6 ADJUSTING A. Adjust domestic water pumps to function smoothly, and lubricate as recommended by manufacturer. B. Adjust initial temperature set points. C. Set field -adjustable switches and circuit -breaker trip ranges as indicated. END OF SECTION 221123 DOMESTIC WATER PUMPS 221123 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 221316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Pipe, tube, and fittings. 1.3 PERFORMANCE REQUIREMENTS A. Components and installation shall be capable of withstanding the following minimum working pressure unless otherwise indicated: 1. Soil, Waste, and Vent Piping: 10 -foot head of water. 1.4 SUBMITTALS A. Product Data: For each type of product indicated. 1.5 INFORMATIONAL SUBMITTALS A. Field quality -control reports. 1.6 QUALITY ASSURANCE A. Piping materials shall bear label, stamp, or other markings of specified testing agency B. Comply with NSF/ANSI 14, "Plastics Piping Systems Components and Related Materials," for plastic piping components. Include marking with "NSF-dwv" for plastic drain, waste, and vent piping and "NSF -sewer" for plastic sewer piping. PART 2 - PRODUCTS 2.1 PIPING MATERIALS A. Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, fitting materials, and joining methods for specific services, service locations, and pipe sizes. SANITARY WASTE AND VENT PIPING 221316 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.2 COPPER TUBE AND FITTINGS A. Copper DWV Tube: ASTM B 306, drainage tube, drawn temper. B. Copper Drainage Fittings: ASME B16.23, cast copper or ASME B16.29, wrought copper, solder -joint fittings. C. Hard Copper Tube: ASTM B 88, Type L and Type M, water tube, drawn temper. D. Solder: ASTM B 32, lead free with ASTM B 813, water-flushable flux. 2.3 PVC PIPE AND FITTINGS A. Solid -Wall PVC Pipe: ASTM D 2665, drain, waste, and vent. B. PVC Socket Fittings: ASTM D 2665, made to ASTM D 3311, drain, waste, and vent patterns and to fit Schedule 40 pipe. C. Adhesive Primer: ASTM F 656. 1. Adhesive primer shall have a VOC content of 550 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 2. Adhesive primer shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small -Scale Environmental Chambers." Solvent Cement: ASTM D 2564 1. PVC solvent cement shall have a VOC content of 510 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 2. Solvent cement shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small -Scale Environmental Chambers." PART 3 - EXECUTION 3.1 EARTH MOVING A. Comply with requirements for excavating, trenching, and backfilling specified in Section 312000 "Earth Moving." 3.2 PIPING INSTALLATION A. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, pump sizing, and other design considerations. Install piping as indicated unless deviations to layout are approved on coordination drawings. B. Install piping in concealed locations unless otherwise indicated and except in equipment rooms and service areas. SANITARY WASTE AND VENT PIPING 221316 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise. D. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal. E. Install piping at indicated slopes. F. Install piping free of sags and bends. G. Install fittings for changes in direction and branch connections. H. Install piping to allow application of insulation. Make changes in direction for soil and waste drainage and vent piping using appropriate branches, bends, and long -sweep bends. Sanitary tees and short -sweep 1/4 bends may be used on vertical stacks if change in direction of flow is from horizontal to vertical. Use long -turn, double Y -branch and 1/8 -bend fittings if two fixtures are installed back to back or side by side with common drain pipe. Straight tees, elbows, and crosses may be used on vent lines. Do not change direction of flow more than 90 degrees. Use proper size of standard increasers and reducers if pipes of different sizes are connected. Reducing size of drainage piping in direction of flow is prohibited. J. Lay buried building drainage piping beginning at low point of each system. Install true to grades and alignment indicated, with unbroken continuity of invert. Place hub ends of piping upstream. Install required gaskets according to manufacturer's written instructions for use of lubricants, cements, and other installation requirements. Maintain swab in piping and pull past each joint as completed. K. Install soil and waste drainage and vent piping at the following minimum slopes unless otherwise indicated: 1. Building Sanitary Drain: 1 percent downward in direction of flow for piping NPS 2 and smaller; 1 percent downward in direction of flow for piping NPS 3 and larger. 2. Horizontal Sanitary Drainage Piping: 2 percent downward in direction of flow. 3. Vent Piping: 1 percent down toward vertical fixture vent or toward vent stack. L. Install aboveground copper tubing according to CDA's "Copper Tube Handbook." M. Install aboveground PVC piping according to ASTM D 2665. N. Install underground PVC piping according to ASTM D 2321. O. Install engineered soil and waste drainage and vent piping systems as follows: 1. Combination Waste and Vent: Comply with standards of authorities having jurisdiction. P. Plumbing Specialties: 1. Install cleanouts at grade and extend to where building sanitary drains connect to building sanitary sewers in sanitary drainage gravity -flow piping. Comply with requirements for cleanouts specified in Section 221319 "Sanitary Waste Piping Specialties." Q. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction. SANITARY WASTE AND VENT PIPING 221316 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS R. Install sleeves for piping penetrations of walls, ceilings, and floors. Comply with requirements for sleeves specified in Section 220500 "Common Work Results for Plumbing." S. Install sleeve seals for piping penetrations of concrete walls and slabs. Comply with requirements for sleeve seals specified in Section 220500 "Common Work Results for Plumbing." T. Install escutcheons for piping penetrations of walls, ceilings, and floors. Comply with requirements for escutcheons specified in Section 220500 "Common Work Results for Plumbing." 3.3 JOINT CONSTRUCTION A. Join copper tube and fittings with soldered joints according to ASTM B 828. Use ASTM B 813, water-flushable, lead-free flux and ASTM B 32, lead -free -alloy solder. B. Plastic, Nonpressure -Piping, Solvent -Cement Joints: Clean and dry joining surfaces. Join pipe and fittings according to the following: 1. Comply with ASTM F 402 for safe -handling practice of cleaners, primers, and solvent cements. 2. PVC Piping: Join according to ASTM D 2855 and ASTM D 2665 Appendixes. 3.4 HANGER AND SUPPORT INSTALLATION A. Comply with requirements for pipe hanger and support devices and installation specified in Section 220529 "Hangers and Supports for Plumbing Piping and Equipment." Support vertical piping and tubing at base and at each floor. C. Rod diameter may be reduced one size for double -rod hangers, with 3/8 -inch (10 -mm) minimum rods. D. Install hangers for PVC piping with the following maximum horizontal spacing and minimum rod diameters: 1. NPS 1-1/2 and NPS 2: 48 inches with 3/8 -inch rod. 2. NPS 3: 48 inches with 1/2 -inch rod. 3. NPS 4: with 5/8 -inch rod. 4. NPS 6 and NPS 8: 48 inches with 3/4 -inch rod. E. Install supports for vertical PVC piping every 48 inches. Support piping and tubing not listed above according to MSS SP -69 and manufacturer's written instructions. 3.5 CONNECTIONS A. Drawings indicate general arrangement of piping, fittings, and specialties. B. Connect drainage and vent piping to the following: SANITARY WASTE AND VENT PIPING 221316 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Plumbing Fixtures: Connect drainage piping in sizes indicated, but not smaller than required by plumbing code. 2. Plumbing Fixtures and Equipment: Connect atmospheric vent piping in sizes indicated, but not smaller than required by authorities having jurisdiction. 3. Plumbing Specialties: Connect drainage and vent piping in sizes indicated, but not smaller than required by plumbing code. 4. Install test tees (wall cleanouts) in conductors near floor and floor cleanouts with cover flush with floor. 5. Equipment: Connect drainage piping as indicated. Provide shutoff valve if indicated and union for each connection. Use flanges instead of unions for connections NPS 2-1/2 (DN 65) and larger. 3.6 IDENTIFICATION A. Identify exposed sanitary waste and vent piping. Comply with requirements for identification specified in Section 220553 "Identification for Plumbing Piping and Equipment." 3.7 FIELD QUALITY CONTROL A. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction. 1. Roughing -in Inspection: Arrange for inspection of piping before concealing or closing -in after roughing -in and before setting fixtures. 2. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements. B. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make required corrections and arrange for reinspection. C. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction. D. Test sanitary drainage and vent piping according to procedures of authorities having jurisdiction or, in absence of published procedures, as follows: 1. Leave uncovered and unconcealed new, altered, extended, or replaced drainage and vent piping until it has been tested and approved. Expose work that was covered or concealed before it was tested. 2. Roughing -in Plumbing Test Procedure: Test drainage and vent piping except outside leaders on completion of roughing -in. Close openings in piping system and fill with water to point of overflow, but not less than 10 -foot head of water. From 15 minutes before inspection starts to completion of inspection, water level must not drop. Inspect joints for leaks. 3. Finished Plumbing Test Procedure: After plumbing fixtures have been set and traps filled with water, test connections and prove they are gastight and watertight. Plug vent -stack openings on roof and building drains where they leave building. Introduce air into piping system equal to pressure of 1 -inch wg. Use U-tube or manometer inserted in trap of water closet to measure this pressure. Air pressure must remain constant without introducing additional air throughout period of inspection. Inspect plumbing fixture connections for gas and water leaks. 4. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are obtained. 5. Prepare reports for tests and required corrective action. SANITARY WASTE AND VENT PIPING 221316 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.8 CLEANING AND PROTECTION A. Clean interior of piping. Remove dirt and debris as work progresses. B. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work. C. Place plugs in ends of uncompleted piping at end of day and when work stops. D. Exposed PVC Piping: Protect plumbing vents exposed to sunlight with two coats of water- based latex paint. 3.9 PIPING SCHEDULE A. Aboveground, soil and waste piping shall be the following: 1. Copper DWV tube, copper drainage fittings, and soldered joints. 2. Solid -wall PVC pipe, PVC socket fittings, and solvent -cemented joints. B. Aboveground, vent piping shall be the following: 1. Hubless, cast-iron soil pipe and fittings; heavy-duty hubless-piping couplings; and coupled joints. 2. Copper DWV tube, copper drainage fittings, and soldered joints. a. Option for Vent Piping, NPS 2-1/2 and NPS 3: Hard copper tube, Type M; copper pressure fittings; and soldered joints. 3. Solid -wall PVC pipe, PVC socket fittings, and solvent -cemented joints. C. Underground, soil, waste, and vent piping shall be the following: 1. Solid wall PVC pipe, PVC sockets fittings, and solvent -cemented joints. END OF SECTION 221316 SANITARY WASTE AND VENT PIPING 221316 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 221319 - SANITARY WASTE PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Cleanouts. 2. Floor drains. 3. Miscellaneous sanitary drainage piping specialties. B. Related Requirements: 1. Section 221423 "Storm Drainage Piping Specialties" for storm drainage piping inside the building, drainage piping specialties, and drains. 1.3 DEFINITIONS A. ABS: Acrylonitrile -butadiene -styrene plastic. B. FRP: Fiberglass -reinforced plastic. C. HDPE: High-density polyethylene plastic. D. PE: Polyethylene plastic. E. PP: Polypropylene plastic. F. PVC: Polyvinyl chloride plastic. 1.4 ACTION SUBMITTALS A. Product Data: For each type of product indicated. 1.5 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For drainage piping specialties to include in emergency, operation, and maintenance manuals. SANITARY WASTE PIPING SPECIALTIES 221319 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.6 QUALITY ASSURANCE A. Drainage piping specialties shall bear label, stamp, or other markings of specified testing agency. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. C. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic sanitary piping specialty components. 1.7 COORDINATION A. Coordinate size and location of concrete bases. Cast anchor -bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in Section 033000 "Cast -in -Place Concrete." B. Coordinate size and location of roof penetrations. PART 2 - PRODUCTS 2.1 CLEANOUTS A. Metal Cleanouts: 1. ASME A112.36.2M, Cast -Iron Cleanouts: a. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1) MIFAB, Inc. 2) Smith, Jay R. Mfg. Co. 3) Watts Drainage Products. 4) Zurn Plumbing Products Group. 2.2 FLOOR DRAINS A. Cast -Iron Floor Drains : 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. MIFAB, Inc. b. Watts Drainage Products. c. Zurn Plumbing Products Group; Light Commercial Operation. 2.3 MISCELLANEOUS SANITARY DRAINAGE PIPING SPECIALTIES A. Deep -Seal Traps: SANITARY WASTE PIPING SPECIALTIES 221319 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Description: Cast-iron or bronze casting, with inlet and outlet matching connected piping and cleanout trap -seal primer valve connection. B. Floor -Drain, Trap -Seal Primer Fittings : 1. Description: Cast iron, with threaded inlet and threaded or spigot outlet, and trap -seal primer valve connection. 2. Size: Same as floor drain outlet with NPS 1/2 (DN 15) side inlet. C. Air -Gap Fittings : 1. Standard: ASME A112.1.2, for fitting designed to ensure fixed, positive air gap between installed inlet and outlet piping. PART 3 - EXECUTION 3.1 INSTALLATION A. Refer to Section 220500 "Common Work Results for Plumbing" for piping joining materials, joint construction, and basic installation requirements. B. Install backwater valves in building drain piping. For interior installation, provide cleanout deck plate flush with floor and centered over backwater valve cover, and of adequate size to remove valve cover for servicing. C. Install cleanouts in aboveground piping and building drain piping according to the following, unless otherwise indicated: 1. Size same as drainage piping up to NPS 4. Use NPS 4 for larger drainage piping unless larger cleanout is indicated. 2. Locate at each change in direction of piping greater than 45 degrees. 3. Locate at minimum intervals of 50 feet for piping NPS 4 and smaller and 100 feet for larger piping. 4. Locate at base of each vertical soil and waste stack. D. For floor cleanouts for piping below floors, install cleanout deck plates with top flush with finished floor. E. For cleanouts located in concealed piping, install cleanout wall access covers, of types indicated, with frame and cover flush with finished wall. F. Install floor drains at low points of surface areas to be drained. Set grates of drains flush with finished floor, unless otherwise indicated. Position floor drains for easy access and maintenance. Set floor drains below elevation of surrounding finished floor to allow floor drainage. Set with grates depressed according to the following drainage area radii: a. Radius, 30 Inches or Less: Equivalent to 1 percent slope, but not less than 1/4 - inch total depression. b. Radius, 30 to 60 Inches: Equivalent to 1 percent slope. SANITARY WASTE PIPING SPECIALTIES 221319 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS c. Radius, 60 Inches or Larger: Equivalent to 1 percent slope, but not greater than 1 - inch total depression. 3. Install floor -drain flashing collar or flange so no leakage occurs between drain and adjoining flooring. Maintain integrity of waterproof membranes where penetrated. 4. Install individual traps for floor drains connected to sanitary building drain, unless otherwise indicated. G. Install deep -seal traps on floor drains and other waste outlets, if indicated. I -I. Install floor -drain, trap -seal primer fittings on inlet to floor drains that require trap -seal primer connection. 1. Exception:. Fitting may be omitted if trap has trap -seal primer connection. 2. Size: Same as floor drain inlet. I. Install air -gap fittings on draining -type backflow preventers and on indirect -waste piping discharge into sanitary drainage system. J. K. L. 3.2 A. B. C. D. 1. Above -Floor Installation: Set unit with bottom resting on floor, unless otherwise indicated. 2. Flush with Floor Installation: Set unit and extension, if required, with cover flush with finished floor. 3. Recessed Floor Installation: Set unit in receiver housing having bottom or cradle supports, with receiver housing cover flush with finished floor. 4. Install cleanout immediately downstream from interceptors not having integral cleanout on outlet. Install wood -blocking reinforcement for wall -mounting -type specialties. Install traps on plumbing specialty drain outlets. Omit traps on indirect wastes unless trap is indicated. Install escutcheons at wall, floor, and ceiling penetrations in exposed finished locations and within cabinets and millwork. Use deep -pattern escutcheons if required to conceal protruding pipe fittings. CONNECTIONS Comply with requirements in Section 221316 "Sanitary Waste and Vent Piping" for piping installation requirements. Drawings indicate general arrangement of piping, fittings, and specialties. Install piping adjacent to equipment to allow service and maintenance. Ground equipment according to Section 260526 "Grounding and Systems." Connect wiring according to Section 260519 "Low -Voltage Electrical Cables." Bonding for Electrical Power Conductors and SANITARY WASTE PIPING SPECIALTIES 221319 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.3 PROTECTION A. Protect drains during remainder of construction period to avoid clogging with dirt or debris and to prevent damage from traffic or construction work. B. Place plugs in ends of uncompleted piping at end of each day or when work stops. END OF SECTION 221319 SANITARY WASTE PIPING SPECIALTIES 221319 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 221413 - STORM DRAINAGE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following storm drainage piping inside the building: 1. Pipe, tube, and fittings. B. Related Sections include the following: 1. Division 22 Section "Sump Pumps." 1.3 DEFINITIONS A. PVC: Polyvinyl chloride plastic. B. TPE: Thermoplastic elastomer. 1.4 PERFORMANCE REQUIREMENTS A. Components and installation shall be capable of withstanding the following minimum working - pressure, unless otherwise indicated: 1. Storm Drainage Piping: 10 foot head of water. 2. Force Main Piping: 150 psig. 1.5 SUBMITTALS A. Product Data: For pipe, tube, fittings, and couplings. 1.6 QUALITY ASSURANCE A. Piping materials shall bear label, stamp, or other markings of specified testing agency. Comply with NSF 14, "Plastics Piping Systems Components and Related Materials," for plastic piping components. Include marking with "NSF -drain" for plastic drain piping and "NSF -sewer" for plastic sewer piping. STORM DRAINAGE PIPING 221413 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 2 - PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. 2.2 PIPING MATERIALS A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materials. 2.3 PVC PIPE AND FITTINGS A. Solid -Wall PVC Pipe: ASTM D 2665, drain, waste, and vent. B. Solvent Cement and Adhesive Primer: 1. Use PVC solvent cement that has a VOC content of 510 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 2. Use adhesive primer that has a VOC content of 550 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). PART 3 - EXECUTION 3.1 EXCAVATION A. Refer to Division 31 Section "Earth Moving" for excavating, trenching, and backfilling. 3.2 PIPING APPLICATIONS A. Aboveground storm drainage piping shall be one of the following: Solid -wall PVC pipe, PVC socket fittings, and solvent -cemented joints. B. Underground storm drainagepiping shall be one of the following: 1. Solid -wall PVC pipe, PVC socket fittings, and solvent -cemented joints. 3.3 PIPING INSTALLATION A. Storm sewer and drainage piping outside the building are specified in Civil Specifications "Storm Utility Drainage Piping." STORM DRAINAGE PIPING 221413 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Basic piping installation requirements are specified in Division 22 Section "Common Work Results for Plumbing." C. Install cleanouts at grade and extend to where building storm drains connect to building storm sewers. Cleanouts are specified in Division 22 Section "Storm Drainage Piping Specialties." D. Install cast-iron sleeve with water stop and mechanical sleeve seal at each service pipe penetration through foundation wall. Select number of interlocking rubber links required to make installation watertight. Sleeves and mechanical sleeve seals are specified in Division 22 Section "Common Work Results for Plumbing." E. Make changes in direction for storm drainage piping using appropriate branches, bends, and long -sweep bends. Do not change direction of flow more than 90 degrees. Use proper size of standard increasers and reducers if pipes of different sizes are connected. Reducing size of drainage piping in direction of flow is prohibited. F. Lay buried building storm drainage piping beginning at low point of each system. Install true to grades and alignment indicated, with unbroken continuity of invert. Place hub ends of piping upstream. Install required gaskets according to manufacturer's written instructions for use of lubricants, cements, and other installation requirements. Maintain swab in piping and pull past each joint as completed. G. Install storm drainage piping at the following minimum slopes, unless otherwise indicated: 1. Storm Drain: Slope piping per Local Building Code or as shown on drawings. H. Install PVC storm drainage piping according to ASTM D 2665. 1. Install underground PVC storm drainage piping according to ASTM D 2321. J. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction. 3.4 JOINT CONSTRUCTION A. Basic piping joint construction requirements are specified in Division 22 Section "Common Work Results Plumbing." B. PVC Nonpressure Piping Joints: Join piping according to ASTM D 2665. 3.5 VALVE INSTALLATION A. General valve installation requirements are specified in Division 22 Section "General -Duty Valves for Plumbing Piping. B. Backwater Valves: Install backwater valves in piping subject to backflow. 1. Horizontal Piping: Horizontal backwater valves. Use normally closed type, unless otherwise indicated. 2. Install backwater valves in accessible locations. 3. Backwater valve are specified in Division 22 Section "Storm Drainage Piping Specialties." STORM DRAINAGE PIPING 221413 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.6 HANGER AND SUPPORT INSTALLATION A. Pipe hangers and supports are specified in Division 22 Section "Hangers and Supports for Plumbing Piping and Equipment." Install the following: 1. Vertical Piping: MSS Type 8 or Type 42, damps. 2. Individual, Straight, Horizontal Piping Runs: According to the following: a. 100 Feet and Less: MSS Type 1, adjustable, steel clevis hangers. b. Longer Than 100 Feet: MSS Type 43, adjustable roller hangers. c. Longer Than 100 Feet, if Indicated: MSS Type 49, spring cushion rolls. 3. Multiple, Straight, Horizontal Piping Runs 100 Feet or Longer: MSS Type 44, pipe rolls. Support pipe rolls on trapeze. 4. Base of Vertical Piping: MSS Type 52, spring hangers. B. Install supports according to Division 22 Section "Hangers and Supports for Plumbing Piping and Equipment." C. Support vertical piping and tubing at base and at each floor. D. Rod diameter may be reduced 1 size for double -rod hangers, with 3/8 -inch minimum rods. E. Install hangers for PVC piping with the following maximum horizontal spacing and minimum rod diameters: 1. NPS 1-1/2 and NPS 2: 48 inches with 3/8 -inch rod. 2. NPS 3: 48 inches with 1/2 -inch rod. 3. NPS 4 and NPS 5: 48 inches with 5/8 -inch rod. 4. NPS 6: 48 inches with 3/4 -inch rod. 5. NPS 8 to NPS 12: 48 inches with 7/8 -inch rod. F. Install supports for vertical PVC piping every 48 inches. G. Support piping and tubing not listed above according to MSS SP -69 and manufacturer's written instructions. 3.7 CONNECTIONS A. Drawings indicate general arrangement of piping, fittings, and specialties. B. Connect interior storm drainage piping to exterior storm drainage piping. Use transition fitting to join dissimilar piping materials. C. Connect storm drainage piping to roof drains and storm drainage specialties. 3.8 CLEANING A. Clean interior of piping. Remove dirt and debris as work progresses. B. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work. STORM DRAINAGE PIPING 221413 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Place plugs in ends of uncompleted piping at end of day and when work stops. END OF SECTION 221413 STORM DRAINAGE PIPING 221413 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 221423 - STORM DRAINAGE PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Roof drains. 2. Cleanouts. 3. Backwater valves. 1.3 SUBMITTALS A. Product Data: For each type of product indicated. 1.4 QUALITY ASSURANCE A. Drainage piping specialties shall bear label, stamp, or other markings of specified testing agency. PART 2 - PRODUCTS 2.1 STORM DRAINS A. Cast -Iron Storm Drains. 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. MIFAB, Inc. b. Zurn Plumbing Products Group; Specification Drainage Operation. c. Tyler Pipe; Wade Div 2. Standard: ASME A112.6.4, for general-purpose roof drains. 2.2 CLEANOUTS A. Metal Cleanouts: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Josam Company; Josam Div. b. Watts Drainage Products Inc. c. Zurn Plumbing Products Group; Specification Drainage Operation. STORM DRAINAGE PIPING SPECIALTIES 221423 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.3 BACKWATER VALVES A. Horizontal Backwater Valves: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. MIFAB, Inc. b. Spears. c. Clean Check. PART 3 - EXECUTION 3.1 INSTALLATION A. Install roof drains at low points of roof areas according to roof membrane manufacturer's written installation instructions. Roofing materials are specified in Division 07 Sections. 1. Install flashing collar or flange of roof drain to prevent leakage between drain and adjoining roofing. Maintain integrity of waterproof membranes where penetrated. 2. Install expansion joints, if indicated, in roof drain outlets. 3. Position roof drains for easy access and maintenance. B. Install cleanouts in aboveground piping and building drain piping according to the following, unless otherwise indicated: 1. Size same as drainage piping up to NPS 4. Use NPS 4 for larger drainage piping unless larger cleanout is indicated. 2. Cleanouts shall be installed per local Plumbing Code. 3. Locate at base of each vertical storm stack. C. For floor cleanouts for piping below floors, install cleanout deck plates with top flush with finished floor. D. For cleanouts located in concealed piping, install cleanout wall access covers, of types indicated, with frame and cover flush with finished wall. E. Install horizontal backwater valves in floor with cover flush with floor. F. Install wall cleanouts in vertical conductors. Install access door in wall if indicated. 3.2 CONNECTIONS A. Comply with requirements for piping specified in Division 22 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. 3.3 PROTECTION A. Protect drains during remainder of construction period to avoid clogging with dirt or debris and to prevent damage from traffic or construction work. STORM DRAINAGE PIPING SPECIALTIES 221423 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Place plugs in ends of uncompleted piping at end of each day or when work stops. END OF SECTION 221423 STORM DRAINAGE PIPING SPECIALTIES 221423 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 223300 - ELECTRIC DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY This Section includes the following electric water heaters: 1. Household, storage electric water heaters. 2. Compression tanks. 3. Water heater accessories. 1.3 SUBMITTALS Product Data: For each type and size of water heater indicated. Include rated capacities, operating characteristics, furnished specialties, and accessories. B. LEED Submittal: Product Data for Prerequisite EA 2: Documentation indicating that units comply with ASHRAE/IESNA 90.1-2004, Section 7 - "Service Water Heating." C. Operation and Maintenance Data: For electric water heaters to include in emergency, operation, and maintenance manuals. D. Warranty: Special warranty specified in this Section. 1.4 QUALITY ASSURANCE Source Limitations: Obtain same type of electric water heaters through one source from a single manufacturer. B. Product Options: Drawings indicate size, profiles, and dimensional requirements of electric water heaters and are based on the specific system indicated. Refer to Division 01 Section "Product Requirements." C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. D. ASHRAE/IESNA 90.1-2004 Compliance: Applicable requirements in ASHRAE/IESNA 90.1- 2004. ELECTRIC DOMESTIC WATER HEATERS 223300 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS E. ASME Compliance: Where indicated, fabricate and label commercial water heater storage tanks to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. F. Comply with NSF 61, "Drinking Water System Components - Health Effects; Sections 1 through 9," for all components that will be in contact with potable water. 1.5 COORDINATION A. Coordinate size and location of concrete bases with Architectural and Structural Drawings. 1.6 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of electric water heaters that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Structural failures including storage tank and supports. b. Faulty operation of controls. c. Deterioration of metals, metal finishes, and other materials beyond normal use. 2. Warranty Period(s): From date of Substantial Completion: a. Household Electric Water Heaters: 1) Storage Tank: Five years. 2) Controls and Other Components: Three years. b. Compression Tanks: One year. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. 2.2 ELECTRIC WATER HEATERS A. Standard, Storage Electric Water Heaters: Comply with UL 174. 1. Manufacturers: a. Lochinvar Corporation. b. Smith, A. O. Water Products Company. c. State Industries, Inc. ELECTRIC DOMESTIC WATER HEATERS 223300 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Storage -Tank Construction: Steel. a. Tappings: ASME B1.20.1 pipe thread. b. Pressure Rating: 150 PSI c. Interior Finish: Comply with NSF 61 barrier materials for potable -water tank linings, including extending lining material into tappings. 3. Factory -Installed Storage -Tank Appurtenances: a. Anode Rod: Replaceable magnesium. b. Dip Tube: Provide unless cold -water inlet is near bottom of tank. c. Drain Valve: ASSE 1005. d. Insulation: Comply with ASHRAE/IESNA 90.1-2004. e. Heat Trap Fittings: Inlet type in cold -water inlet and outlet type in hot-water outlet. f. Temperature Control: Adjustable thermostat for each element. g. Safety Control: High -temperature -limit cutoff device or system. h. Relief Valve: ASME rated and stamped and complying with ASME PTC 25.3 for combination temperature and pressure relief valves. Include relieving capacity at least as great as heat input, and include pressure setting less than water heater working -pressure rating. Select relief valve with sensing element that extends into storage tank. 4. Capacity and Characteristics: (Refer to Drawings). 2.3 COMPRESSION TANKS A. Description: Steel pressure -rated tank constructed with welded joints and factory -installed butyl -rubber diaphragm. Include air precharge to minimum system -operating pressure at tank. 1. Manufacturers: a. AMTROL Inc. b. Taco, Inc. c. Watts Regulator Co. 2. Construction: a. Tappings: Factory -fabricated steel, welded to tank before testing and labeling. Include ASME B1.20.1, pipe thread. b. Interior Finish: Comply with NSF 61 barrier materials for potable -water tank linings, including extending finish into and through tank fittings and outlets. c. Air -Charging Valve: Factory installed. 2.4 WATER HEATER ACCESSORIES A. Combination Temperature and Pressure Relief Valves: ASME rated and stamped and complying with ASME PTC 25.3. Include relieving capacity at least as great as heat input, and include pressure setting less than water heater working -pressure rating. Select relief valves with sensing element that extends into storage tank. B. Drain -Pan Units: Where water heaters or hot water storage tanks are installed in habitable space, the tank or water heater shall be installed in a galvanized steel drain pan of a minimum ELECTRIC DOMESTIC WATER HEATERS 223300 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS thickness of 24 gauge. Electric water heater drain pans may be high impact plastic of at least 0.0625 inch thickness. C. Piping -Type Heat Traps: Field -fabricated piping arrangement according to ASHRAE/IESNA 90.1-2004. 2.5 SOURCE QUALITY CONTROL A. Test and inspect water heater storage tanks, specified to be ASME-code construction, according to ASME Boiler and Pressure Vessel Code. B. Hydrostatically test water heater storage tanks before shipment to minimum of one and one-half times pressure rating. C. Prepare test reports. PART 3 - EXECUTION 3.1 WATER HEATER INSTALLATION A. Install water heaters on concrete bases. 1. Exception: Omit concrete bases for commercial water heaters if installation on stand, bracket, suspended platform, or direct on floor is indicated. 2. Concrete base construction requirements are specified in Division 22 Section "Common Work Results for Plumbing." B. Install water heaters level and plumb, according to layout drawings, original design, and referenced standards. Maintain manufacturer's recommended clearances. Arrange units so controls and devices needing service are accessible. C. Install combination temperature and pressure relief valves in top portion of storage tanks. Use relief valves with sensing elements that extend into tanks. Extend water -heater relief -valve outlet, with drain piping same as domestic water piping in continuous downward pitch, and discharge by positive air gap onto closest floor drain in the same room as water heater. D. Install water -heater drain piping as indirect waste to spill by positive air gap into open drains or over floor drains. Install hose -end drain valves at low points in water piping for water heaters that do not have tank drains. Refer to Division 22 Section "Domestic Water Piping Specialties" for hose -end drain valves. E. Install thermometer on outlet piping of water heaters. Refer to Division 22 Section "Meters and Gages for Plumbing Piping" for thermometers. F. Install piping -type heat traps on inlet and outlet piping of water heater storage tanks without integral or fitting -type heat traps. G. Fill water heaters with water. H. Charge compression tanks with air. ELECTRIC DOMESTIC WATER HEATERS 223300 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.2 CONNECTIONS A. Piping installation requirements are specified in other Division 22 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to water heaters to allow service and maintenance. Arrange piping for easy removal of water heaters. C. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical Systems." D. Connect wiring according to Division 26 Section "Low -Voltage Electrical Power Conductors and Cables." 3.3 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory -authorized service representative to inspect, test, and adjust Feld -assembled components and equipment installation, including connections, and to assist in field testing. Report results in writing. B. Perform the following field tests and inspections and prepare test reports: 1. Leak Test: After installation, test for leaks. Repair- leaks and retest until no leaks exist. 2. Operational Test: After electrical circuitry has been energized, confirm proper operation. 3. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. C. Remove and replace water heaters that do not pass tests and inspections and retest as specified above. 3.4 DEMONSTRATION A. Engage a factory -authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain commercial electric water heaters. Refer to Division 01 Section "Demonstration and Training." END OF SECTION 223300 ELECTRIC DOMESTIC WATER HEATERS 223300 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 224000 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following conventional plumbing fixtures and related components: 1. Faucets. 2. Flushometers. 3. Fixture supports. 4. Protective Shielding Guards. 5. Disposers. 6. Water closets. 7. Urinals. 8. Lavatories. 9. Kitchen sinks. 10. Mop sinks. 11. Drinking fountains. 12. Hose Bibbs and Hydrants 1.3 SUBMITTALS A. Product Data: For each type of plumbing fixture indicated. Include selected fixture and trim, fittings, accessories, appliances, appurtenances, equipment, and supports. Indicate materials and finishes, dimensions, construction details, and flow -control rates. B. Operation and Maintenance Data: For plumbing fixtures to include in emergency, operation, and maintenance manuals. C. Warranty: Special warranty specified in this Section. 1.4 QUALITY ASSURANCE A. Source Limitations: Obtain plumbing fixtures, faucets, and other components of each category through one source from a single manufacturer. 1. Exception: If fixtures, faucets, or other components are not available from a single manufacturer, obtain similar products from other manufacturers specified for that category. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. PLUMBING FIXTURES 224000 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Regulatory Requirements: Comply with requirements in ICC A117.1, "Accessible and Usable Buildings and Facilities"; Public Law 90-480, "Architectural Barriers Act"; and Public Law 101- 336, "Americans with Disabilities Act"; for plumbing fixtures for people with disabilities. D. Regulatory Requirements: Comply with requirements in Public Law 102-486, "Energy Policy Act," about water flow and consumption rates for plumbing fixtures. E. NSF Standard: Comply with NSF 61, "Drinking Water System Components --Health Effects," for fixture materials that will be in contact with potable water. F. ARI Standard: Comply with ARI's "Directory of Certified Drinking Water Coolers" for style classifications. G. ARI Standard: Comply with ARI 1010, "Self -Contained, Mechanically Refrigerated Drinking - Water Coolers," for water coolers and with ARI's "Directory of Certified Drinking Water Coolers" for type and style classifications. H. ASHRAE Standard: Comply with ASHRAE 34, "Designation and Safety Classification of Refrigerants," for water coolers. Provide HFC 134a (tetrafluoroethane) refrigerant, unless otherwise indicated. Select combinations of fixtures and trim, faucets, fittings, and other components that are compatible. J. Comply with the following applicable standards and other requirements specified for plumbing fixtures: 1. Stainless -Steel Residential Sinks: ASME A112.19.3. 2. Vitreous -China Fixtures: ASME A112.19.2M. 3. Water -Closet, Flush Valve, Tank Trim: ASME A112.19.5. 4. Water -Closet, Flushometer Tank Trim: ASSE 1037. 1.5 WARRANTY A. Special Warranties: Manufacturer's standard form in which manufacturer agrees to repair or replace components of whirlpools that fail in materials or workmanship within specified warranty period. Failures include, but are not limited to, the following: a. Structural failures of unit shell. b. Faulty operation of controls, blowers, pumps, heaters, and timers. c. Deterioration of metals, metal finishes, and other materials beyond normal use. 2. 1 year Warranty Period for Commercial Applications. PART 2 - PRODUCTS 2.1 LAVATORY AND SINK FAUCETS A. Lavatory and Sink Faucets: PLUMBING FIXTURES 224000 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Chicago Faucets. b. T & S Brass and Bronze Works, Inc. c. Zurn Plumbing Products Group; Commercial Brass Operation 2.2 FLUSHOMETERS A. Flushometers: 1. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Sloan Valve Company. b. Zurn Plumbing Products Group; Commercial Brass Operation. 2.3 TOILET SEATS A. Toilet Seats: 1. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Bemis Manufacturing Company. b. Centoco Manufacturing Corp. c. Olsonite Corp. 2.4 PROTECTIVE SHIELDING GUARDS A. Protective Shielding Pipe Covers: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. McGuire Manufacturing Co., Inc. b. Plumberex Specialty Products Inc. c. TRUEBRO, Inc. 2.5 FIXTURE SUPPORTS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Josam Company. 2. Tyler Pipe; Wade Div. 3. Zurn Plumbing Products Group; Specification Drainage Operation. PLUMBING FIXTURES 224000 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.6 DISPOSERS A. Disposers: 1. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. In-Sink-Erator; a div. of Emerson Electric Co. b. KitchenAid. WATER CLOSETS B. Water Closets: 1. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Kohler Co. b. TOTO USA, Inc. c. American Standard Companies, Inc. 2.7 URINALS A. Urinals: 1. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Kohler Co. b. TOTO USA, Inc. c. American Standard Companies, Inc. 2.8 LAVATORIES A. Lavatories: 1. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Kohler Co. b. TOTO USA, Inc. c. American Standard Companies, Inc. 2.9 KITCHEN SINKS A. Kitchen Sinks: 1. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Jacuzzi, Inc. PLUMBING FIXTURES 224000 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.10 A. b. c. d. e. f. 9. Kohler Co. American Standard Companies, Inc. Eljer. DuPont, Corian Products. Elkay Manufacturing Co. Just Manufacturing Company. MOP SINKS Mop Sinks: Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. b. c. Crane Plumbing, L.L.C./Fiat Products. Precast Terrazzo Enterprises, Inc. Stern -Williams Co., Inc. 2.11 DRINKING FOUNTAINS AND WATER COOLERS Drinking Fountains: 1. Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. b. c. Elkay Manufacturing Co. Halsey Taylor. Oasis Corporation. 2.12 HOSE BIBB'S AND HYDRANTS A. Hose Bibbs and Hydrants Basis -of -Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Zurn b. Prier c. WoodFord PART 3 - EXECUTION 3.1 EXAMINATION A. Examine roughing -in of water supply and sanitary drainage actual locations of piping connections before plumbing fixture B. Examine cabinets, counters, floors, and walls for suitable installed. and vent piping systems to verify installation. conditions where fixtures will be PLUMBING FIXTURES 224000-5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Assemble plumbing fixtures, trim, fittings, and other components according to manufacturers' written instructions. B. Install off -floor supports, affixed to building substrate, for wall -mounting fixtures. 1. Use carrier supports with waste fitting and seal for back -outlet fixtures. 2. Use carrier supports without waste fitting for fixtures with tubular waste piping. 3. Use chair -type carrier supports with rectangular steel uprights for accessible fixtures. C. Install back -outlet, wall -mounting fixtures onto waste fitting seals and attach to supports. D. Install floor -mounting fixtures on closet flanges or other attachments to piping or building substrate. E. Install wall -mounting fixtures with tubular waste piping attached to supports. F. Install mounting frames affixed to building construction and attach recessed water coolers to mounting frames, unless otherwise indicated. G. Install counter -mounting fixtures in and attached to casework. I -I. Install fixtures level and plumb according to roughing -in drawings. Install water -supply piping with stop on each supply to each fixture to be connected to water distribution piping. Attach supplies to supports or substrate within pipe spaces behind fixtures. Install stops in locations where they can be easily reached for operation. J. Install trap and tubular waste piping on drain outlet of each fixture to be directly connected to sanitary drainage system. K. Install tubular waste piping on drain outlet of each fixture to be indirectly connected to drainage system. L. Install flushometer valves for accessible water closets and urinals with handle mounted on wide side of compartment. Install other actuators in locations that are easy for people with disabilities to reach. M. Install toilet seats on water closets. N. Install faucet -spout fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required. O. Install water -supply flow -control fittings with specified flow rates in fixture supplies at stop valves. P. Install shower flow -control fittings with specified maximum flow rates in shower arms. Q. Install traps on fixture outlets. 1. Exception: Omit trap on fixtures with integral traps. PLUMBING FIXTURES 224000 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Exception: Omit trap on indirect wastes, unless otherwise indicated. R. Install disposer in outlet of each sink indicated to have disposer. Install switch where indicated or in wall adjacent to sink if location is not indicated. S. Install dishwasher air -gap fitting at each sink indicated to have air -gap fitting. Connect inlet hose to dishwasher and outlet hose to disposer. T. Install escutcheons at piping wall ceiling penetrations in exposed, finished locations and within cabinets and millwork. Use deep -pattern escutcheons if required to conceal protruding fittings. Escutcheons are specified in Division 22 Section "Common Work Results for Plumbing." U. Seal joints between fixtures and walls, floors, and countertops using sanitary -type, one -part, mildew -resistant silicone sealant. Match sealant color to fixture color. Sealants are specified in Division 07 Section "Joint Sealants." 3.3 CONNECTIONS A. Piping installation requirements are specified in other Division 22 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. B. Connect fixtures with water supplies, stops, and risers, and with traps, soil, waste, and vent piping. Use size fittings required to match fixtures. C. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical Systems." D. Connect wiring according to Division 26 Section "Low -Voltage Electrical Power Conductors and Cables." 3.4 FIELD QUALITY CONTROL A. Verify that installed plumbing fixtures are categories and types specified for locations where installed. B. Check that plumbing fixtures are complete with trim, faucets, fittings, and other specified components. C. Inspect installed plumbing fixtures for damage. Replace damaged fixtures and components. D. Test installed fixtures after water systems are pressurized for proper operation. Replace malfunctioning fixtures and components, then retest. Repeat procedure until units operate properly. E. Install fresh batteries in sensor -operated mechanisms. F. Water Cooler Testing: After electrical circuitry has been energized, test for compliance with requirements. Test and adjust controls and safeties. 1. Remove and replace malfunctioning units and retest as specified above. 2. Report test results in writing. PLUMBING FIXTURES 224000 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.5 ADJUSTING A. Operate and adjust faucets and controls. fittings, and controls. B. D. E. F. G. Operate and adjust disposers and controls. controls. Replace damaged and malfunctioning fixtures, Replace damaged and malfunctioning units and Adjust water pressure at faucets and flushometer valves to produce proper flow and stream. Replace washers and seals of leaking and dripping faucets and stops. Install fresh batteries in sensor -operated mechanisms. Adjust fixture flow regulators for proper flow and stream height. Adjust water cooler temperature settings. 3.6 CLEANING A. Clean fixtures, faucets, and other fittings with manufacturers' recommended cleaning methods and materials. Do the following: 1. Remove faucet spouts and strainers, remove sediment and debris, and reinstall strainers and spouts. 2. Remove sediment and debris from drains. B. After completing installation of exposed, factory -finished fixtures, faucets, and fittings, inspect exposed finishes and repair damaged finishes. C. After completing fixture installation, inspect unit. Remove paint splatters and other spots, dirt, and debris. Repair damaged finish to match original finish. D. Clean fixtures, on completion of installation, according to manufacturer's written instructions. 3.7 PROTECTION A. Provide protective covering for installed fixtures and fittings. B. Do not allow use of plumbing fixtures for temporary facilities unless approved in writing by Owner. END OF SECTION 224000 PLUMBING FIXTURES 224000 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230513 - COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes general requirements for single-phase and polyphase, general-purpose, horizontal, small and medium, squirrel -cage induction motors for use on ac power systems up to 600 V and installed at equipment manufacturer's factory or shipped separately by equipment manufacturer for field installation. 1.3 COORDINATION A. Coordinate features of motors, installed units, and accessory devices to be compatible with the following: 1. Motor controllers. 2. Torque, speed, and horsepower requirements of the load. 3. Ratings and characteristics of supply circuit and required control sequence. 4. Ambient and environmental conditions of installation location. PART 2 - PRODUCTS 2.1 GENERAL MOTOR REQUIREMENTS A. Comply with NEMA MG 1 unless otherwise indicated. 2.2 MOTOR CHARACTERISTICS A. Duty: Continuous duty at ambient temperature of 40 deg C and at altitude of 3300 feet above sea level. B. Capacity and Torque Characteristics: Sufficient to start, accelerate, and operate connected loads at designated speeds, at installed altitude and environment, with indicated operating sequence, and without exceeding nameplate ratings or considering service factor. 2.3 POLYPHASE MOTORS A. Description: NEMA MG 1, Design B, medium induction motor. B. Efficiency: Energy efficient, as defined in NEMA MG 1. COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT 230513 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Service Factor: 1.15. D. Multispeed Motors: Variable torque. 1. For motors with 2:1 speed ratio, consequent pole, single winding. 2. For motors with other than 2:1 speed ratio, separate winding for each speed. E. Rotor: Random -wound, squirrel cage. F. Bearings: Regreasable, shielded, antifriction ball bearings suitable for radial and thrust loading. G. Temperature Rise: Match insulation rating. H. Insulation: Class F. Code Letter Designation: 1. Motors Smaller than 15 HP: Manufacturer's standard starting characteristic. J. Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled steel for motor frame sizes smaller than 324T. 2.4 POLYPHASE MOTORS WITH ADDITIONAL REQUIREMENTS A. Motors Used with Variable Frequency Controllers: Ratings, characteristics, and features coordinated with and approved by controller manufacturer. 1. Windings: Copper magnet wire with moisture -resistant insulation varnish, designed and tested to resist transient spikes, high frequencies, and short time rise pulses produced by pulse -width modulated inverters. 2. Energy- and Premium -Efficient Motors: Class B temperature rise; Class F insulation. 3. Inverter -Duty Motors: Class F temperature rise; Class H insulation. 4. Thermal Protection: Comply with NEMA MG 1 requirements for thermally protected motors. 2.5 SINGLE-PHASE MOTORS A. Motors larger than 1/20 hp shall be one of the following, to suit starting torque and requirements of specific motor application: 1. Permanent -split capacitor. B. Multispeed Motors: Variable -torque, permanent -split -capacitor type. C. Bearings: Prelubricated, antifriction ball bearings or sleeve bearings suitable for radial and thrust loading. Motors 1/20 HP and Smaller: Shaded -pole type. E. Thermal Protection: Internal protection to automatically open power supply circuit to motor when winding temperature exceeds a safe value calibrated to temperature rating of motor insulation. Thermal -protection device shall automatically reset when motor temperature returns to normal range. COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT 230513 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION (Not Applicable) END OF SECTION 230513 COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT 230513 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230514 - VARIABLE FREQUENCY MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use with a standard NEMA Design B induction motor. B. The drive manufacturer shall supply the drive and all necessary options, specified. The manufacturer shall have been engaged in the production of this type of equipment for a minimum of ten years. All VFDs installed on this project shall be from the same manufacturer. 1.3 SUMMARY A. Related Sections 1. Section 237300 — Custom Indoor Central -Station Air -Handling Units 2. Section 233423 - HVAC Power Ventilators 3. Section 232123 - Hydronic Pumps 4. Section 230900 — Instrumentation and Control For HVAC B. Section includes separately enclosed, pre -assembled, combination VFCs, rated 600 V and less, for speed control of three-phase, squirrel -cage induction motors. 1.4 REFERENCES A. Institute of Electrical and Electronics Engineers 1. IEEE C62.41 — Recommended Practice on Surge Voltages in Low -Voltage AC Power Circuits. B. National Electrical Manufacturers Association 1. NEMA 250 — Enclosures for Electrical Equipment (1000 Volts Maximum). 2. NEMA FU 1 — Low Voltage Cartridge Fuses. 3. NEMA ICS 7 — Industrial Control and Systems: Adjustable Speed Drives. 4. NEMA ICS 7.1 — Safety Standards for Construction and Guide for Selection, Installation, and Operation of Adjustable Speed Drive Systems. C. International Electrical Testing Association 1. NETA ATS — Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems. 1.5 SUBMITTALS A. Shop Drawings: Indicate front and side views of enclosures with overall dimensions and weights shown; conduit entrance locations and requirements; and nameplate legends. B. Product Data: For each type and rating of VFC indicated. Include the following features: 1. Performance VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Electrical Ratings 3. Operating Characteristics 4. Dimensioned outline drawing 5. Schematic diagram 6. Component list 7. Power and control connection diagram(s). 8. Bacnet Interface Controller 9. Compliance to IEEE 519 — harmonic analysis for particular jobsite including total harmonic voltage distortion and total harmonic current distortion (TDD). a. The VFD manufacturer shall provide calculations; specific to this installation, showing total harmonic voltage distortion is less than 5%. Input filters shall be sized and provided as required by the VFD manufacturer to ensure compliance with IEEE standard 519. All VFD's shall include a minimum of 5% impedance reactors. C. LEED Submittals 1. Product Data for Credit EA 5: For continuous metering equipment for energy consumption. D. Test Reports: Indicate field test and inspection procedures and test results. E. Manufacturer's Field Reports: Indicate start-up inspection findings. F. Harmonic Analysis Study and Report: Comply with IEEE 399 and NETA Acceptance Testing Specification; indentify the effects of nonlinear loads and their associated harmonic contributions on the voltages and currents throughout the electrical system. Analyze possible operating scenarios, including recommendations for VFC input filtering to limit TDD and THD (V) at each VFC to specified levels. 1.6 CLOSEOUT SUBMITTALS A. Section 01 - Execution and closeout requirements. B. Provide final equipment submittal information with all noted corrections incorporated. C. Field quality -control reports D. Operation and Maintenance Data: Submit instructions complying with NEMA ICS 7.1. Include procedures for starting and operating controllers, and describe operating limits possibly resulting in hazardous or unsafe conditions. Include routine preventive maintenance schedule. 1. Manufacturer's written instructions for testing and adjusting thermal -magnetic circuit breaker and MCP trip setting. 2. Manufacturer's written instructions for setting field -adjustable overload relays. 3. Manufacturer's written instructions for testing, adjusting, and reprogramming microprocessor control modules. 4. Manufacturer's written instructions for setting field -adjustable timers, controls, and status and alarm points. E. Load Current and List of Settings of Adjustable Overload Relays: Compile after motors have been installed and arrange to demonstrate that switch settings for motor -running overload protection suit actual motor to be protected. 1.7 QUALITY ASSURANCE A. Refer to calculation and additional testing requirements located within Division 26 and Part 3 of this Section. VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. C. QUALITY ASSURANCE Referenced Standards: a. Institute of Electrical and Electronic Engineers (IEEE) 1) Standard 519-1992, IEEE Guide for Harmonic Content and Control. b. Underwriters laboratories 1) UL508C c. National Electrical Manufacturer's Association (NEMA) 1) ICS 7.0, AC Adjustable Speed Drives d. IEC 16800 Parts 1 and 2 e. National Electric Code (NEC) 1) NEC 430.120, Adjustable -Speed Drive Systems 2. Qualifications: a. VFDs and options shall be UL listed as a complete assembly. VFD's that require the customer to supply external fuses for the VFD to be UL listed are not acceptable. VFDs with red label UL stickers, requiring additional branch circuit protection are not acceptable. The base VFD shall be UL listed for 100 KAIC without the need for input fuses. 1.8 DELIVERY, STORAGE AND HANDLING A. Section 01 — Product Requirements: Product storage and handling requirements. B. Store in clean, dry space. Maintain factory wrapping and provide additional plastic cover to protect units from dirt, water, construction debris, and traffic. C. Handle in accordance with manufacturer's written instructions. Lift only with lugs provided. Handle carefully to avoid damage to components, enclosure, and finish. 1.9 PROJECT CONDITIONS Environmental Limitations: Rate equipment for continuous operation, capable of driving full load without derating, under the following conditions: 1. Ambient Temperature: Not less than 14 deg. F. and not exceeding 104 deg. F. 2. Ambient Storage Temperature: Not less than minus 4 deg. F. and not exceeding 140 deg. F. 3. Humidity: Less than 95 percent (noncondensing). 4. Altitude: Not Exceeding 1000 feet. B. Conform to NEMA ICS 7 service conditions during and after installation of variable frequency controllers. 1.10 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace VFCs that fail in materials or workmanship within the specified warranty period. B. Furnish five year manufacturer warranty for variable frequency controller. 1.11 TRAINING A. Contractor shall provide 16 hours of training to university staff divided into 4 sessions. VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Training shall be video taped by a licensed videographer. One DVD copy shall be provided to the owner agent. 1.12 MAINTENANCE SERVICE A. Section 01 — Execution and Closeout Requirements: Maintenance service. B. Furnish service and maintenance of variable frequency controller for one year from Date of Substantial Completion. PART 2 - PRODUCTS 2.1 VARIABLE FREQUENCY CONTROLLER A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. ABB. 2. Danfoss Inc.; Danfoss Drives Division (Labeled Drives Manufactured by Danfoss Inc. also Permitted) 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric. 5. Yaskawa Electric America, Inc; Drives Division 2.2 VARIABLE FREQUENCY CONTROLLER A. The VFD package as specified herein shall be enclosed in a UL Listed Type enclosure, exceeding NEMA enclosure design criteria (enclosures with only NEMA ratings are not acceptable), completely assembled and tested by the manufacturer in an ISO9001 facility. The VFD tolerated voltage window shall allow the VFD to operate from a line of +30% nominal, and - 35% nominal voltage as a minimum. 1. Environmental operating conditions: VFDs shall be capable of continuous operation at 0 to 500 C (32 to 1220 F) ambient temperature as per VFD manufacturers documented/submittal data or VFD must be oversized to meet these temperature requirements. Not acceptable are VFD's that can only operate at 40° C intermittently (average during a 24 hour period) and therefore must be oversized. Altitude 0 to 3300 feet above sea level, less than 95% humidity, non -condensing. All circuit boards shall have conformal coating. B. All VFDs shall have the following standard features: All VFDs shall have the same customer interface, including digital display, and keypad, regardless of horsepower rating. The keypad shall be removable, capable of remote mounting and allow for uploading and downloading of parameter settings as an aid for start-up of multiple VFDs. 2. The keypad shall include Hand -Off -Auto selections and manual speed control. The drive shall incorporate "bumpless transfer" of speed reference when switching between "Hand" and "Auto" modes. There shall be fault reset and "Help" buttons on the keypad. The Help button shall include "on-line" assistance for programming and troubleshooting. 3. There shall be a built-in time clock in the VFD keypad. The clock shall have a battery backup with 10 years minimum life span. The clock shall be used to date and time stamp faults and record operating parameters at the time of fault. If the battery fails, the VFD shall automatically revert to hours of operation since initial power up. Capacitor back-up is not acceptable. The clock shall also be programmable to control start/stop functions, VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS constant speeds, PID parameter sets and output Form -C relays. The VFD shall have a digital input that allows an override to the time clock (when in the off mode) for a programmable time frame. There shall be four (4) separate, independent timer functions that have both weekday and weekend settings. 4. The VFD's shall utilize pre-programmed application macro's specifically designed to facilitate start-up. The Application Macros shall provide one command to reprogram all parameters and customer interfaces for a particular application to reduce programming time. The VFD shall have two user macros to allow the end-user to create and save custom settings. 5. The VFD shall have cooling fans that are designed for easy replacement. The fans shall be designed for replacement without requiring removing the VFD from the wall or removal of circuit boards. The VFD cooling fans shall operate only when required. To extend the fan and bearing operating life, the VFD shall cycle the cooling fans on and off as required. 6. The VFD shall be capable of starting into a coasting load (forward or reverse) up to full speed and accelerate or decelerate to set point without tripping or component damage (flying start). 7. The VFD shall have the ability to automatically restart after an over -current, over -voltage, under -voltage, or loss of input signal protective trip. The number of restart attempts, trial time, and time between attempts shall be programmable. 8. The overload rating of the drive shall be 110% of its normal duty current rating for 1 minute every 10 minutes, 130% overload for 2 seconds. The minimum FLA rating shall meet or exceed the values in the NEC/UL table 430.250 for 4 -pole motors. 9. The VFD shall have internal 5% impedance reactors to reduce the harmonics to the power line and to add protection from AC line transients. The 5% impedance may be from dual (positive and negative DC bus) reactors, or 5% AC line reactors. VFD's with only one DC reactor shall add an AC line reactor. 10. The input current rating of the VFD shall be no more than 3% greater than the output current rating. VFD's with higher input current ratings require the upstream wiring, protection devices, and source transformers to be oversized per NEC 430.120. Input and output current ratings must be shown on the VFD nameplate. 11. The VFD shall include a coordinated AC transient surge protection system consisting of 4-120 joule rated MOV's (phase to phase and phase to ground), a capacitor clamp, and 5% impedance reactors. 12. The VFD shall provide a programmable loss -of -load (broken belt / broken coupling) Form -C relay output. The drive shall be programmable to signal the loss -of -load condition via a keypad warning, Form -C relay output, and / or over the serial communications bus. The loss -of -load condition sensing algorithm shall include a programmable time delay that will allow for motor acceleration from zero speed without signaling a false loss -of -load condition. 13. The VFD shall have user programmable underload and overload curve functions to allow user defined indications of broken belt or mechanical failure / jam condition causing motor overload 14. The VFD shall include multiple "two zone" PID algorithms that allow the VFD to maintain PID control from two separate feedback signals (4-20mA, 0-10V, and / or serial communications). The two zone control PID algorithm will control motor speed based on a minimum, maximum, or average of the two feedback signals. All of the VFD PID controllers shall include the ability for "two zone" control. 15. If the input reference (4-20mA or 2-10V) is lost, the VFD shall give the user the option of either (1) stopping and displaying a fault, (2) running at a programmable preset speed, (3) hold the VFD speed based on the last good reference received, or (4) cause a warning to be issued, as selected by the user. The drive shall be programmable to signal this condition via a keypad warning, Form -C relay output and / or over the serial communication bus. 16. The VFD shall have programmable "Sleep" and "Wake up" functions to allow the drive to be started and stopped from the level of a process feedback signal. VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. All VFDs to have the following adjustments: Three (3) programmable critical frequency lockout ranges to prevent the VFD from operating the load continuously at an unstable speed. The lockout range must be fully adjustable, from 0 to full speed. 2. Two (2) PID Set point controllers shall be standard in the drive, allowing pressure or flow signals to be connected to the VFD, using the microprocessor in the VFD for the closed- loop control. The VFD shall have 250 ma of 24 VDC auxiliary power and be capable of loop powering a transmitter supplied by others. The PID set point shall be adjustable from the VFD keypad, analog inputs, or over the communications bus. There shall be two independent parameter sets for the PID controller and the capability to switch between the parameter sets via a digital input, serial communications or from the keypad. The independent parameter sets are typically used for night setback, switching between summer and winter set points, etc. 3. There shall be an independent, second PID loop that can utilize the second analog input and modulate one of the analog outputs to maintain the set point of an independent process (ie. valves, dampers, etc.). All set points, process variables, etc. to be accessible from the serial communication network. 4. Two (2) programmable analog inputs shall accept current or voltage signals. 5. Two (2) programmable analog outputs (0-20ma or 4-20 ma). The outputs may be programmed to output proportional to Frequency, Motor Speed, Output Voltage, Output Current, Motor Torque, Motor Power (kW), DC Bus voltage, Active Reference, Active Feedback, and other data. 6. Six (6) programmable digital inputs for maximum flexibility in interfacing with external devices. All digital inputs shall be programmable to initiate upon an application or removal of 24VDC or 24VAC. 7. Three (3) programmable, digital Form -C relay outputs. The relay outputs shall include programmable on and off delay times and adjustable hysteresis. The relays shall be rated for maximum switching current 8 amps at 24 VDC and 0.4 A at 250 VAC; Maximum voltage 300 VDC and 250 VAC; continuous current rating of 2 amps RMS. Outputs shall be true Form -C type contacts; open collector outputs are not acceptable. 8. Run permissive circuit - There shall be a run permissive circuit for damper or valve control. Regardless of the source of a run command (keypad, input contact closure, time -clock control, or serial communications), the VFD shall provide a dry contact closure that will signal the damper to open (VFD motor does not operate). When the damper is fully open, a normally open dry contact (end -switch) shall close. The closed end -switch is wired to a VFD digital input and allows VFD motor operation. Two separate safety interlock inputs shall be provided. When either safety is opened, the motor shall be commanded to coast to stop and the damper shall be commanded to close. The keypad shall display "start enable 1 (or 2) missing". The safety input status shall also be transmitted over the serial communications bus. 9. The VFD control shall include a programmable time delay for VFD start and a keypad indication that this time delay is active. A Form C relay output provides a contact closure to signal the VAV boxes open. This will allow VAV boxes to be driven open before the motor operates. The time delay shall be field programmable from 0 — 120 seconds. Start delay shall be active regardless of the start command source (keypad command, input contact closure, time -clock control, or serial communications), and when switching from drive to bypass. 10. Seven (7) programmable preset speeds. 11. Two independently adjustable accel and decel ramps with 1 — 1800 seconds adjustable time ramps. 12. The VFD shall include a motor flux optimization circuit that will automatically reduce applied motor voltage to the motor to optimize energy consumption and reduce audible motor noise. The VFD shall have selectable software for optimization of motor noise, energy consumption, and motor speed control. VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 13. The VFD shall include a carrier frequency control circuit that reduces the carrier frequency based on actual VFD temperature that allows higher carrier frequency settings without derating the VFD, 14. The VFD shall include password protection against parameter changes. D. The Keypad shall include a backlit LCD display. The display shall be in complete English words for programming and fault diagnostics (alpha -numeric codes are not acceptable). All VFD faults shall be displayed in English words. The keypad shall include a minimum of 14 assistants including: 1. Start-up assistant 2. Parameter assistants a. PID assistant b. Reference assistant c. I/O assistant d. Serial communications assistant e. Option module assistant f. Panel display assistant g. Low noise set-up assistant 3. Maintenance assistant 4. Troubleshooting assistant 5. Drive optimizer assistants E. All applicable operating values shall be capable of being displayed in engineering (user) units. A minimum of three operating values from the list below shall be capable of being displayed at all times. The display shall be in complete English words (alpha -numeric codes are not acceptable): 1. Output Frequency 2. Motor Speed (RPM, %, or Engineering units) 3. Motor Current 4. Motor Torque 5. Motor Power (kW) 6. DC Bus Voltage 7. Output Voltage F. Serial Communications 1. The VFD shall have an EIA -485 port as standard. The standard protocols shall be ASHRAE 135 - BACnet. Each individual drive shall have the protocol in the base VFD. The use of third party gateways and multiplexers is not acceptable. All protocols shall be "certified" BTL Listed for BACnet. Use of non -certified protocols is not allowed. 2. The BACnet connection shall be an EIA -485, MS/TP interface operating at 76.8 Kbps. The connection shall be tested by the BACnet Testing Labs (BTL) and be BTL Listed, The BACnet interface shall conform to the BACnet standard device type of an Applications Specific Controller (B -ASC). The interface shall support all BIBBs defined by the BACnet standard profile for a B -ASC including, but not limited to: a. Data Sharing — Read Property — B. b. Data Sharing - Write Property — B. c. Device Management — Dynamic Device Binding (Who -Is; I -Am). d. Device Management — Dynamic Object Binding (Who -Has; I -Have). e. Device Management — Communication Control — B. 3. If additional hardware is required to obtain the BACnet interface, the VFD manufacturer shall supply one BACnet gateway per drive. Multiple VFDs sharing one gateway shall not be acceptable. VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 4. Serial communication capabilities shall include, but not be limited to; run -stop control, speed set adjustment, proportional/integral/derivative PID control adjustments, current limit, accel/decel time adjustments, and lock and unlock the keypad. The drive shall have the capability of allowing the DDC to monitor feedback such as process variable feedback, output speed / frequency, current (in amps), % torque, power (kW), kilowatt hours (resettable), operating hours (resettable), and drive temperature. The DDC shall also be capable of monitoring the VFD relay output status, digital input status, and all analog input and analog output values. All diagnostic warning and fault information shall be transmitted over the serial communications bus. Remote VFD fault reset shall be possible. 5. Serial communication in bypass shall include, but not be limited to; bypass run -stop control, the ability to force the unit to bypass, and the ability to lock and unlock the keypad. The bypass shall have the capability of allowing the DDC to monitor feedback such as, current (in amps), kilowatt hours (resettable), operating hours (resettable), and bypass logic board temperature. The DDC shall also be capable of monitoring the bypass relay output status, and all digital input status. All bypass diagnostic warning and fault information shall be transmitted over the serial communications bus. Remote bypass fault reset shall be possible. 6. The VFD / bypass shall allow the DDC to control the drive and bypass digital and analog outputs via the serial interface. This control shall be independent of any VFD function. The analog outputs may be used for modulating chilled water valves or cooling tower bypass valves. The drive and bypass' digital (Form -C relay) outputs may be used to actuate a damper, open a valve or control any other device that requires a maintained contact for operation. In addition, all of the drive and bypass' digital inputs shall be capable of being monitored by the DDC system. This allows for remote monitoring of which (of up to 4) safeties are open. 7. The VFD shall include an independent PID loop for customer use. The independent PID loop would be used for chilled water value control. Both the VFD PID control loop and the independent PID control loop shall continue functioning even if the serial communications connection is lost. As default, the VFD shall keep the last good set point command and last good DO & AO commands in memory in the event the serial communications connection is lost and continue controlling the process. G. EMI / RFI filters. All VFD's shall include EMI/RFI filters. The onboard filters shall allow the VFD assembly to be CE Marked and the VFD shall meet product standard EN 61800-3 for the First Environment restricted level with up to 100 feet of motor cable. No Exceptions. Certified test reports shall be provided with the submittals confirming compliance to EN 61800-3, First Environment. H. All VFD's through 25HP at 480 V shall be protected from input and output power mis-wiring. The VFD shall sense this condition and display an alarm on the keypad. The VFD shall not sustain damage from this power mis-wiring condition. ADDITIONAL FEATURES — Optional features to be furnished and mounted by the drive manufacturer. All optional features shall be UL Listed by the drive manufacturer as a complete assembly and carry a UL508 label. 1. Fieldbus adapters - BACnet IP, shall be provided by adding of an optional card. J. BYPASS CONTROLLER 1. A complete factory wired and tested bypass system consisting of a door interlocked, padlockable circuit breaker, output contactor, bypass contactor, and fast acting VFD input fuses are required. UL Listed motor overload protection shall be provided in both drive and bypass modes. VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. The bypass enclosure door and VFD enclosure must be mechanically interlocked such that the disconnecting device must be in the "Off" position before either enclosure may be accessed. 3. The VFD and bypass package shall have a UL listed short circuit current rating (SCCR) of 100,000 amps and this rating shall be indicated on the UL data label. 4. Drive Isolation Fuses - To ensure maximum possible bypass operation, fast acting fuses, exclusive to the VFD, shall be provided to allow the VFD to disconnect from the line prior to clearing upstream branch circuit protection. This maintains bypass operation capability in the event of a VFD failure. Bypass designs which have no such fuses, or that incorporate fuses common to both the VFD and the bypass, will not be accepted. 5. The system (VFD and Bypass) tolerated voltage window shall allow the system to operate from a line of +30%, -35% nominal voltage range. The system shall incorporate circuitry that will allow the drive or bypass contactor to remain "sealed in" over this voltage tolerance at a minimum. 6. The bypass shall maintain positive contactor control through the voltage tolerance window of nominal voltage +30%, -35%. This feature is designed to avoid contactor coil failure during brown out / low line conditions and allow for input single phase operation when in the VFD mode. Designs that will not allow input single phase operation in the VFD mode are not acceptable. 7. Motor protection from single phase power conditions - the bypass system must be able to detect a single phase input power condition while running in bypass, disengage the motor in a controlled fashion, and give a single phase input power indication. Bypass systems not incorporating single phase protection in bypass mode are not acceptable. 8. The bypass system shall NOT depend on the VFD for bypass operation. The bypass system shall be designed for stand alone operation and shall be completely functional in both Hand and Automatic modes even if the VFD has been removed from the system for repair / replacement. Serial communications shall remain functional even with the VFD removed. 9. Serial communications — the bypass shall be capable of being monitored and controlled via serial communications. Communication shall be through BACnet IP. 10. Serial communication capabilities shall include, but not be limited to; bypass run -stop control; the ability to force the unit to bypass; and the ability to lock and unlock the keypad. The bypass shall have the capability of allowing the DDC to monitor feedback such as, current (in amps), kilowatt hours (resettable), operating hours (resettable), and bypass logic board temperature. The DDC shall also be capable of monitoring the bypass relay output status, and all digital input status. All bypass diagnostic warning and fault information shall be transmitted over the serial communications bus. Remote bypass fault reset shall be possible. The following additional status indications and settings shall be transmitted over the serial communications bus and / or via a Form -C relay output — keypad "Hand" or "Auto" selected, bypass selected, and broken belt indication. The DDC system shall also be able to monitor if the motor is running in the VFD mode or bypass mode over serial communications. A minimum of 50 field serial communications points shall be capable of being monitored in the bypass mode. 11. The bypass serial communications shall allow control of the bypass' digital outputs via the serial interface. This control shall be independent of any bypass function or operating state. The bypass' digital (relay) outputs may be used to actuate a damper, open a valve or control any other device that requires a maintained contact for operation. In addition, all of the bypass' digital inputs shall be capable of being monitored by the DDC system. 12. There shall be an adjustable motor current sensing circuit for the bypass and VFD modes to provide proof of flow (broken belt) indication. The condition shall be indicated on the keypad display, transmitted over the building automation protocol and / or via a Form -C relay output contact closure. The broken belt indication shall be programmable to be a system (drive and bypass) indication. The broken belt condition sensing algorithm shall be programmable to cause only a warning or a fault and / or system shutdown. 13. The digital inputs for the system shall accept 24VAC or 24VDC. The bypass shall incorporate an internally sourced power supply and not require an external control power VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS source. The bypass power board shall supply 250 ma of 24 VDC for use by others to power external devices. 14. There shall be a run permissive circuit for damper or valve control. Regardless of the source of a run command (keypad command, time -clock control, digital input, or serial communications) the bypass shall provide a dry contact closure that will signal the damper to open (motor does not operate). When the damper is fully open, a normally open dry contact (end -switch) shall close. The closed end -switch is wired to a bypass system input and allows motor operation. Up to four separate safety interlock inputs shall be provided. When any safety is opened, the motor shall be commanded to coast to stop, and the damper shall be commanded to close. This feature will also operate in Fireman's override / smoke control mode. 15. The bypass control shall monitor the status of the VFD and bypass contactors and indicate when there is a welded contactor contact or open contactor coil. This failed contactor condition shall be indicated on the bypass LCD display, programmed to fire a Form -C relay output, and / or over the serial communications protocol. 16. The bypass control shall include a programmable time delay for bypass start and keypad indication that this time delay is in process. A Form C relay output provides a contact closure to signal the VAV boxes open. This will allow VAV boxes to be driven open before the motor operates at full speed in the bypass mode. The time delay shall be field programmable from 0 —120 seconds. 17. There shall be a keypad adjustment to select manual or automatic transfer bypass. The user shall be able to select via keypad programming which drive faults will result in an automatic transfer to the bypass mode and which faults require a manual transfer to bypass. The user may select whether the system shall automatically transfer from drive to bypass mode on the following drive fault conditions: a. Over current b. Over voltage c. Under voltage d. Loss of analog input 18. The following operators shall be provided: a. Bypass Hand -Off -Auto b. Drive mode selector c. Bypass mode selector d. Bypass fault reset 19. The bypass shall include a two line, 20 character LCD display. The display shall allow the user to access and view: a. Energy savings — in US dollars b. Bypass motor amps c. Bypass input voltage— average and individual phase voltage d. Bypass power (kW) e. Bypass faults and fault logs f. Bypass warnings g. Bypass operating time (resettable) h. Bypass energy (kilowatt hours — resettable) I/O status j. Parameter settings / programming k. Printed circuit board temperature 20. The following indicating lights (LED type) or keypad display indications shall be provided. A test mode or push to test feature shall be provided. a. Power -on (Ready) b. Run enable c. Drive mode selected d. Bypass mode selected e. Drive running f. Bypass running g. Drive fault h. Bypass fault VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100%CONSTRUCTION DOCUMENTS Bypass H -O -A mode j. Automatic transfer to bypass selected k. Safety open I. Damper opening m. Damper end -switch made 21. The Bypass controller shall have six programmable digital inputs, and five programmable Form -C relay outputs. This I/O allows for a total System (VFD and Bypass) I/O count of 24 points as standard. The bypass I/O shall be available to the BAS / DDC system even with the VFD removed. 1. The on -board Form -C relay outputs in the bypass shall programmable for any of the following indications. a. System started b. System running c. Bypass override enabled d. Drive fault e. Bypass fault f. Bypass H -O -A position g. Motor proof -of -flow (broken belt) h. Overload i. Bypass selected j. Bypass run k. System started (damper opening) I. Bypass alarm m. Over temperature 22. The bypass shall provide a separate terminal strip for connection of freeze, fire, smoke contacts, and external start command. All external safety interlocks shall remain fully functional whether the system is in VFD or Bypass mode. The remote start/stop contact shall operate in VFD and bypass modes. The terminal strip shall allow for independent connection of up to four (4) unique safety inputs. 23. Class 10, 20, or 30 (programmable) electronic motor overload protection shall be included. K. Enclosures: 1. Provide the VFD and bypass panels with the appropriate NEMA rated enclosure for the following applications: a. Indoors: NEMA 1. b. Indoors (mechanical rooms): NEMA 12. c. Outdoors (Protected by overhang): NEMA 3R enclosure. d. Outdoors (exposed to windblown dust or water): NEMA 4 2. Provide appropriate ventilation of VFD cabinetry to maintain ambient temperature rating of the drive based upon application. On outdoor installations appropriate ventilation shall be powered ventilation fan(s) and external 12"x12"x1"paper filter arranged so as to not allow paper filter to be exposed to rain. 2.3 SOURCE QUALITY CONTROL A. Shop, inspect and perform standard productions tests for each controller. B. Make completed controllers available for inspection at manufacturer's factory prior to packaging for shipment. Notify the Owner at least seven days before inspection is allowed. C. Allow witnessing of factory inspections and tests at manufacturer's test facility. Notify the Owner at least seven days before inspections and tests are scheduled. VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 11 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION 3.1 EXAMINATION A. Section 01300 — Administrative Requirements: Coordination and project conditions. B. Verify that building environment can be maintained within the service and ambient temperature and humidity ratings required by the VFD manufacturer 3.2 INSTALLATION A. Installation shall be the responsibility of the mechanical contractor. The contractor shall install the drive in accordance with the recommendations of the VFD manufacturer as outlined in the VFD installation manual. B. Power wiring shall be completed by the electrical contractor, to NEC code 430.122 wiring requirements based on the VFD input current. Caution: VFDs supplied without internal reactors have substantially higher input current ratings, which may require larger input power wiring and branch circuit protection. The contractor shall complete all wiring in accordance with the recommendations of the VFD manufacturer as outlined in the installation manual. C. Install in accordance with NEMA ICS 7.1. D. Verify that mounting surface for VFDs are ready to receive work. Mount VFDs on the wall or at supports in locations identified on the drawings. E. Tighten accessible connections and mechanical fasteners after placing controller. F. Install fuses in fusible switches. G. Select and install overload heater elements in motor controllers to match installed motor characteristics. H. Install engraved plastic nameplates in accordance with Section 23 05 53. I. Neatly type label inside controller door identifying motor served, nameplate horsepower, full load amperes, code letter, service factor, and voltage/phase rating. Place label in clear plastic holder. J. Ground and bond controller in accordance with Section 26 05 26. K. Controls installer shall provide all wiring and conduit associated with the control signals into and out of the VFD to the DDC EMS and as required for any motor control interlocks. 3.3 FIELD QUALITY CONTROL A. Inspect and test in accordance with NETA ATS, except Section 4. B. Perform inspections and tests listed in NETA ATS, Section 7.16 and NEMA ICS 7.1. C. Perform power quality analysis per warranty requirements. VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 12 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.4 MANUFACTURER'S FIELD SERVICES A. VFD Start-up: Provide certified factory start-up for each drive by a factory authorized service center representative. A certified start-up form shall be filled out for each drive with a copy provided to the Owner, and a copy kept on file at the manufacturer. The following VFD start-up services are to be provided as a minimum: 1. Service center technician shall be responsible for verifying correct installation, power and control wiring connections, starting -up the drive, and checking out for proper operation. 2. Service center technician shall also provide all final adjustments to meet the specified performance requirements. 3.5 DEMONSTRATION AND TRAINING A. Provide 16 hours of instruction to be conducted at the project site with manufacturer's representative. The training shall be conducted at 4 hour maximums. Contractor to also provide two sets of VFD operation manuals for use at the training session and then provide to the Owner after completion of the session. 3.6 VARIABLE FREQUENCY DRIVE START-UP SERVICE A. Provide start-up commissioning of variable frequency drive and optional circuits by factory certified service technician experienced in start-up and repair services. Commissioning personnel shall be the same personnel that will provide factory service and warranty repairs at site. Sales personnel and other agents who are not factory certified technicians for drive field repair not acceptable. B. Include checking for verification of proper operation and installation and interface wiring to building automation system. Include as a minimum: 1. Verify contractor wire terminations to VFD optional circuitry. 2. Verify proper operation and reliability of VFD, motor being driven and building automation system. 3. Provide up to one hour of Owner/operator training on operation and service diagnostics during commissioning. 4. Measure to verify proper operation on: a. Motor voltage and frequency. Verify proper motor operation. b. Control input for proper building automation system interface and control calibration. c. Calibration check for: d. Minimum speed. e. Maximum speed. f. Acceleration and deceleration rates. g. Adjust as necessary. C. Configure VSD for automatic restart after a power failure or after an external fault is cleared. END OF SECTION 230514 VARIABLE FREQUENCY MOTOR CONTROLLERS 230514 - 13 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230517 - SLEEVES AND SLEEVE SEALS FOR HVAC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Sleeve -seal fittings. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. PART 2 - PRODUCTS 2.1 SLEEVE -SEAL FITTINGS A. Manufacturers: Subject to compliance with requirements: B. Description: Manufactured plastic, sleeve -type, waterstop assembly made for imbedding in concrete slab or wall. Unit has plastic or rubber waterstop collar with center opening to match piping OD. PART 3 - EXECUTION 3.1 SLEEVE INSTALLATION A. Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls. Install sleeves in concrete floors, concrete roof slabs, and concrete walls as new slabs and walls are constructed. 1. Permanent sleeves are not required for holes in slabs formed by molded -PE or -PP sleeves. 2. Cut sleeves to length for mounting flush with both surfaces. a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches above finished floor level. SLEEVES AND SLEEVE SEALS FOR HVAC PIPING 230517 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Fire -Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for firestopping specified in Division 07 Section "Penetration Firestopping." 3.2 SLEEVE -SEAL -FITTING INSTALLATION A. Install sleeve -seal fittings in new walls and slabs as they are constructed. B. Assemble fitting components of length to be flush with both surfaces of concrete slabs and walls. Position waterstop flange to be centered in concrete slab or wall. C. Secure nailing flanges to concrete forms. 3.3 SLEEVE AND SLEEVE -SEAL SCHEDULE A. Use sleeves and sleeve seals for the following piping -penetration applications: 1. Exterior Concrete Walls above Grade: a. Piping Smaller Than NPS 6. 2. Concrete Slabs -on -Grade: a. Piping Smaller Than NPS 6. END OF SECTION 230517 SLEEVES AND SLEEVE SEALS FOR HVAC PIPING 230517 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230519 - METERS AND GAGES FOR HVAC PIPING PART 1 - ENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Thermowells. 2. Dial -type pressure gages. 3. Gage attachments. 4. Test plugs. 5. Test -plug kits. 6. Insertion Electromagnetic flowmeters. 7. Insertion Electromagnetic, thermal -energy meters. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. B. Wiring Diagrams: For power, signal, and control wiring. 1.4 INFORMATIONAL SUBMITTALS A. Product Certificates: For each type of meter and gage, from manufacturer. 1.5 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For meters and gages to include in operation and maintenance manuals. PART2-PRODUCTS 2.1 FILLED -SYSTEM THERMOMETERS A. Metal -Case, Industrial -Style, Liquid -in -Glass Thermometers: Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Miljoco Corporation. METERS AND GAGES FOR HVAC PIPING 230519 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS b. Trerice, H. O. Co. c. Weiss Instruments, Inc. d. Winters Instruments - U.S. 2. Standard: ASME B40.200. 3. Case: Cast aluminum; 7 -inch nominal size unless otherwise indicated. 4. Case Form: Adjustable angle unless otherwise indicated. 5. Tube: Glass with magnifying lens and blue or red organic liquid. 6. Tube Background: Nonreflective aluminum with permanently etched scale markings graduated in deg F. 7. Window: Glass or plastic. 8. Stem: Aluminum and of length to suit installation. a. Design for Thermowell Installation: Bare stem. 9. Connector: 1-1/4 inches, with ASME B1.1 screw threads. 10. Accuracy: Plus or minus 1 percent of scale range or one scale division, to a maximum of 1.5 percent of scale range. 2.2 PRESSURE GAGES A. Direct -Mounted, Metal -Case, Dial -Type Pressure Gages: 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Miljoco Corporation. b. Trerice, H. O. Co. c. Watts Regulator Co.; a div. of Watts Water Technologies, Inc. d. Weiss Instruments, Inc. 2. Standard: ASME B40.100. 3. Case: Liquid -filled type; cast aluminum or drawn steel; 4 -112 -inch nominal diameter. 4. Pressure -Element Assembly: Bourdon tube unless otherwise indicated. 5. Pressure Connection: Brass, with NPS 1/4, ASME B1.20.1 pipe threads and bottom - outlet type unless back -outlet type is indicated. 6. Movement: Mechanical, with link to pressure element and connection to pointer. 7. Dial: Nonreflective aluminum with permanently etched scale markings graduated in psi. 8. Pointer Black metal. 9. Window: Glass or plastic. 10. Ring: Metal. 11. Accuracy: Grade A, plus or minus 1 percent of middle half of scale range. 2.3 GAGE ATTACHMENTS A. Snubbers: ASME B40.100, brass; with NPS 1/4, ASME B1.20.1 pipe threads and -type surge - dampening device. Include extension for use on insulated piping. METERS AND GAGES FOR HVAC PIPING 230519 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.4 TEST PLUGS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. Flow Design, Inc. 2. Miljoco Corporation. 3. Trerice, H. O. Co. 4. Watts Regulator Co.; a div. of Watts Water Technologies, Inc. 5. Weiss Instruments, Inc. B. Description: Test -station fitting made for insertion into piping tee fitting. C. Body: Brass or stainless steel with core inserts and gasketed and threaded cap. Include extended stem on units to be installed in insulated piping. D. Thread Size: NPS 1/4, ASME 131.20.1 pipe thread. E. Minimum Pressure and Temperature Rating: 500 psig at 200 deg F . F. Core Inserts: EPDM self-sealing rubber. 2.5 TEST -PLUG KITS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. Flow Design, Inc. 2. Miljoco Corporation. 3. Trerice, H. O. Co. 4. Watts RegulatorCo.; a div. of Watts Water Technologies, Inc. 5. Weiss Instruments, Inc. B. Furnish one test -plug kit(s) containing one thermometer(s), one pressure gage and adapter, and carrying case. Thermometer sensing elements, pressure gage, and adapter probes shall be of diameter to fit test plugs and of length to project into piping. C. Carrying Case: Metal or plastic, with formed instrument padding. 2.6 FLOWMETERS A. Insertion Electromagnetic Flow Meters: 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. ONICON Incorporated 2. Description: Bi-directional Flowmeter with sensor and indicator. 3. Factory programmed and ready for use upon delivery. 4. Scalable pulse output to totalize forward and reverse flow. 5. Separate pulse output for flow rate. METERS AND GAGES FOR HVAC PIPING 230519 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 6. Flow Range: Sensor and indicator shall cover operating range of equipment or system served. 7. Sensor: Inline type; for installing between pipe flanges and measuring flow directly in gallons per minute. a. Design: Flow metering for measuring electrically conductive liquids. b. Wetted metal component: 316 Stainless-steel body, with integral transmitter. c. Sensing Method: Electromagnetic Sensing d. Flow Range: 0.1 ft/sec to 20 ft/sec (200:1 turndown) e. Maximum Pressure Rating: 400 psig. f. Pressure Drop: Less than 0.1 psi at 12 ft/s velocity in 3" and larger pipes g. Input Power: 20-28 VDC, 250mA @ 24 VDC h. Liquid Temperature Range: 15 °F to 250 °F. Ambient Temperature Range: -20 °F to 150 °F. j. Minimum Temperature Rating: 500 deg F. k. Integral Transformer: For low -voltage power operation. 8. Accuracy: Plus or minus 1.0 percent for readings from 2 ft/sec to 20 ft/sec and 0.02 percent for below 2 ft/sec. 9. Operating Instructions: Include complete instructions with each flowmeter. 2.7 THERMAL -ENERGY METERS A. Insertion Electromagnetic , Thermal -Energy Meters: 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. ONICON Incorporated. 2. Description: System with insertion electromagnetic flow sensor, temperature sensors, transmitter, indicator, and connecting wiring. 3. Flow Sensor: Bi-directional Flowmeter with corrosion -resistant -metal body and transmitter; for installing in piping. a. Design: Total thermal -energy measurement. b. Minimum Pressure Rating: 150 psig. c. Minimum Temperature Range: 40 to 250 deg F. 4. Temperature Sensors: Insertion -type transducer. 5. Indicator: Solid-state, integrating -type meter; for wall mounting. a. Data Output: Six -digit electromechanical counter with readout in kilowatts per hour or British thermal units. b. Battery Pack: Five-year lithium battery. 6. Accuracy: Plus or minus 1 percent. 7. Display: Visually indicates total fluid volume in gallons and thermal -energy flow in kilowatts per hour or British thermal units. 8. Strainer: Full size of main line piping. 9. Operating Instructions: Include complete instructions with each thermal -energy meter system. METERS AND GAGES FOR HVAC PIPING 230519 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS PART 3 - EXECUTION 3.1 INSTALLATION A. Install thermowells with socket extending to center of pipe and in vertical position in piping tees. B. Install duct -thermometer mounting brackets in walls of ducts. Attach to duct with screws. C. Install direct -mounted pressure gages in piping tees with pressure gage located on pipe at the most readable position. D. Install valve and snubber in piping for each pressure gage for fluids (except steam). E. Install valve and syphon fitting in piping for each pressure gage for steam. F. Install test plugs in piping tees. G. Install flow indicators in piping systems in accessible positions for easy viewing. H. Assemble and install connections, tubing, and accessories between flow -measuring elements and flowmeters according to manufacturer's written instructions. I. Install flowmeter elements in accessible positions in piping systems. J. Install permanent indicators on walls or brackets in accessible and readable positions. K. Install connection fittings in accessible locations for attachment to portable indicators. L. Mount thermal -energy meters on wall if accessible; if not, provide brackets to support meters. M. Install thermometers in the following locations: 1. At the supply and return risers to the building. N. Install pressure gages in the following locations: 1. Suction and discharge of each pump. 3.2 CONNECTIONS A. Install meters and gages adjacent to machines and equipment to allow service and maintenance of meters, gages, machines, and equipment. B. Connect flowmeter -system elements to meters. C. Connect flowmeter transmitters to meters. 3.3 ADJUSTING A. After installation, calibrate meters according to manufacturer's written instructions. B. Adjust faces of meters and gages to proper angle for best visibility. METERS AND GAGES FOR HVAC PIPING 230519 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.4 PRESSURE -GAGE SCHEDULE A. Pressure gages at suction and discharge of each pump shall be the following: 1. Liquid -filled, direct -mounted, metal case. 2. Test plug with EPDM self-sealing rubber inserts. 3.5 PRESSURE -GAGE SCALE -RANGE SCHEDULE A. Scale Range for Chilled -Water Piping: 0 to 30 psi. 3.6 FLOWMETER SCHEDULE A. Flowmeters for Chilled -Water Piping: Insertion Electromagnetic type. 3.7 THERMAL -ENERGY METER SCHEDULE A. Thermal -Energy Meters for Chilled -Water Piping: Insertion Electromagnetic type. END OF SECTION 230519 METERS AND GAGES FOR HVAC PIPING 230519 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230523 - GENERAL -DUTY VALVES FOR HVAC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. B. Basic Requirements: Provisions of Section 230010, BASIC MECHANICAL REQUIREMENTS are a part of this Section. 1.2 SUMMARY A. General: Provide valves, cocks and specialties which are required for piping systems specified in other sections of these specifications. Section Includes: 1. Bronze ball valves. 2. Iron, grooved -end ball valves. 3. Iron, single -flange butterfly valves. 4. Iron, grooved -end butterfly valves. 5. Bronze swing check valves. 6. Iron swing check valves. 7. Iron, grooved -end swing -check valves. 8. Flow Balancing Valves C. Related Sections: 1. Section 230553 "Identification for HVAC Piping and Equipment" for valve tags and schedules. 1.3 DEFINITIONS A. CWP: Cold working pressure. B. EPDM: Ethylene propylene copolymer rubber. C. NBR: Acrylonitrile -butadiene, Buna-N, or nitrile rubber. D. NRS: Nonrising stem. E. OS&Y: Outside screw and yoke. F. RS: Rising stem. G. SWP: Steam working pressure. GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1.4 APPLICABLE STANDARDS A. General: All equipment, material, accessories, methods of construction and reinforcement, finish quality, workmanship and installation shall be in compliance with Section 230010. B. Pressure and Temperature Rating: Valves shall have a pressure and temperature rating equal to or exceeding the piping in which they are installed, except that valves shall be designed for a minimum steam working pressure (SWP) of 125 psi; water -oil -gas (WOG) pressure of 200 psi. 1.5 ACTION SUBMITTALS A. Product Data: For each type of valve indicated. B. General: Include the following data: 1. Manufacturers Literature: a. Dimensional outline drawing of each valve listed in this section including sizes available and pressure limitations. b. Outline drawing of each calibrated balancing and flow measuring valve including flow and pressure limitations. c. Outline drawing of each safety and pressure relief valve including discharge capacity and pressure limitations. 2. Installation Instructions: Manufacturer's printed installation instructions for all valves including copies shipped with the valves. 1.6 QUALITY ASSURANCE A. Source Limitations for Valves: Obtain each type of valve from single source from single manufacturer. B. ASME Compliance: 1. ASME B16.10 and ASME B16.34 for ferrous valve dimensions and design criteria. 2. ASME B31.1 for power piping valves. 3. ASME B31.9 for building services piping valves. 1.7 DELIVERY, STORAGE, AND HANDLING A. Prepare valves for shipping as follows: 1. Protect internal parts against rust and corrosion. 2. Protect threads, flange faces, grooves, and weld ends. 3. Set angle, gate, and globe valves closed to prevent rattling. 4. Set ball and plug valves open to minimize exposure of functional surfaces. 5. Set butterfly valves closed or slightly open. 6. Block check valves in either closed or open position. B. Use the following precautions during storage: 1. Maintain valve end protection. GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Store valves indoors and maintain at higher than ambient dew point temperature. If outdoor storage is necessary, store valves off the ground in watertight enclosures. C. Use sling to handle large valves; rig sling to avoid damage to exposed parts. Do not use handwheels or stems as lifting or rigging points. 1.8 BASIC VALVE REQUIREMENTS A. General: Valves and cocks may not be indicated in every instance on the drawings, but whether or not shown, all valves, cocks and check valves necessary for the proper operation of the system shall be furnished and installed. Valves shall have rising stems except in locations where space is limited; in these locations non -rising stem valves of equivalent material and pressure class will be accepted. Valves shall have the manufacturer's name or trademark, recommended service pressure, and size indicated by raised letters cast on the valve body. PART 2 - PRODUCTS 2.1 GENERAL REQUIREMENTS FOR VALVES A. Refer to HVAC valve schedule articles for applications of valves. B. Valve Pressure and Temperature Ratings: Not less than indicated and as required for system pressures and temperatures. C. Valve Sizes: Same as upstream piping unless otherwise indicated. D. Valve Actuator Types: 1. Gear Actuator: For quarter -turn valves NPS 8 and larger. 2. Handwheel: For valves other than quarter -turn types. 3. Handlever: For quarter -turn valves NPS 6 and smaller. 4. Chainwheel: Device for attachment to valve handwheel, stem, or other actuator; of size and with chain for mounting height, as indicated in the "Valve Installation" Article. E. Valves in Insulated Piping: With 2 -inch stem extensions and the following features: 1. Ball Valves: With extended operating handle of non -thermal -conductive material, and protective sleeve that allows operation of valve without breaking the vapor seal or disturbing insulation. 2. Butterfly Valves: With extended neck. F. Valve -End Connections: 1. Flanged: With flanges according to ASME B16.1 for iron valves. 2. Grooved: With grooves according to AWWA C606. 2.2 BRONZE BALL VALVES A. Two -Piece, Full -Port, Brass Ball Valves with Brass Trim: GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. American Valve, Inc. b. Conbraco Industries, Inc.; Apollo Valves. c. Crane Co.; Crane Valve Group; Crane Valves. d. Hammond Valve. e. Lance Valves; a division of Advanced Thermal Systems, Inc. f. Legend Valve. g. Milwaukee Valve Company. h. NIBCO INC. i. Red -White Valve Corporation. j. Watts Regulator Co.; a division of Watts Water Technologies, Inc. 2. Description: a. Standard: MSS SP -110. b. SWP Rating: 150 psig. c. CWP Rating: 600 psig. d. Body Design: Two piece. e. Body Material: Bronze. f. Ends: Threaded. g. Seats: PTFE or TFE. h. Stern: Bronze. i. Stern Seals: Double 0 -ring j. Ball: Chrome -plated brass. k. Port: Standard. 2.3 IRON, GROOVED -END BALL VALVES A. Two -Piece, Full -Port, Brass Ball Valves with Brass Trim: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Victaulic b. Anvil lnternational c. Gustin-Bacon 2. Description: a. SWP Rating: 800 psi. b. Body Design: Two piece, Standard Port. c. Body Material: Ductile Iron conforming to ASTM A-536, painted black enamel. d. Ends: Ductile Iron conforming to ASTM A-536, painted black enamel. e. Seats: TFE. f. Stem: Micro -finished Steel. g. Ball: Micro -finished Nickel -Plated Carbon Steel. h. Port: Standard. 2.4 IRON BALL VALVES A. Class 125, Iron Ball Valves: GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. American Valve, Inc. b. Conbraco Industries, Inc.; Apollo Valves. c. Kitz Corporation. d. Sure Flow Equipment Inc. e. Watts Regulator Co.; a division of Watts Water Technologies, Inc. 2. Description: a. Standard: MSS SP -72. b. CWP Rating: 200 psig (1380 kPa). c. Body Design: Split body. d. Body Material: ASTM A 126, gray iron. e. Ends: Flanged. f. Seats: PTFE or TFE. g. Stem: Stainless steel. h. Ball: Stainless steel. i. Port: Full. 2.5 IRON, SINGLE -FLANGE BUTTERFLY VALVES A. 150 CWP, Iron, Single -Flange Butterfly Valves with EPDM Seat and Aluminum -Bronze Disc: Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. ABZ Valve and Controls; a division of ABZ Manufacturing, Inc. b. Bray Controls; a division of Bray International. c. Conbraco Industries, Inc.; Apollo Valves. d. Cooper Cameron Valves; a division of Cooper Cameron Corp. e. Crane Co.; Crane Valve Group; Jenkins Valves. f. Crane Co.; Crane Valve Group; Stockham Division. g. DeZurik Water Controls. h. Hammond Valve. Kitz Corporation. j. Milwaukee Valve Company. k. NIBCO INC. I. Norriseal; a Dover Corporation company. m. Red -White Valve Corporation. n. Spence Strainers International; a division of CIRCOR International. o. Tyco Valves & Controls; a unit of Tyco Flow Control. p. Watts Regulator Co.; a division of Watts Water Technologies, Inc. 2. Description: a. Standard: MSS SP -67, Type I. b. CWP Rating: 150 psig. c. Body Design: Lug type; suitable for bidirectional dead-end service at rated pressure without use of downstream flange. d. Body Material: ASTM A 126, cast iron or ASTM A 536, ductile iron. e. Seat: EPDM. f. Stem: One- or two-piece stainless steel. GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS g Disc: Aluminum bronze. 2.6 IRON, GROOVED -END BUTTERFLY VALVES A. 175 CWP, Iron, Grooved -End Butterfly Valves: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Kennedy Valve; a division of McWane, Inc. b. Shurjoint Piping Products. c. Tyco Fire Products LP; Grinnell Mechanical Products. d. Victaulic Company. e. Gustin-Bacon. f. Anvil International 2. Description: a. Standard: MSS SP -67, Type I. b. CWP Rating: 175 psig. c. Body Material: Coated, ductile iron. d. Stem: Two-piece stainless steel. e. Disc: Coated, ductile iron. f. Seal: EPDM. 2.7 BRONZE SWING CHECK VALVES A. Class 125, Bronze Swing Check Valves with Bronze Disc: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. American Valve, Inc. b. Crane Co.; Crane Valve Group; Crane Valves. c. Crane Co.; Crane Valve Group; Jenkins Valves. d. Crane Co.; Crane Valve Group; Stockham Division. e. Hammond Valve. f. Kitz Corporation. g. Milwaukee Valve Company. h. NIBCO INC. i. Powell Valves. j. Red -White Valve Corporation. k. Watts Regulator Co.; a division of Watts Water Technologies, Inc. I. Zy-Tech Global Industries, Inc. 2. Description: a. Standard: MSS SP -80, Type 3. b. CWP Rating: 200 psig (1380 kPa). c. Body Design: Horizontal flow. d. Body Material: ASTM B 62, bronze. e. Ends: Threaded. f. Disc: Bronze. GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Class 150, Bronze Swing Check Valves with Bronze Disc: Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. American Valve, Inc. b. Crane Co.; Crane Valve Group; Crane Valves. c. Crane Co.; Crane Valve Group; Jenkins Valves. d. Crane Co.; Crane Valve Group; Stockham Division. e. Kitz Corporation. f. Milwaukee Valve Company. g. NIBCO INC. h. Red -White Valve Corporation. Zy-Tech Global Industries, Inc. 2. Description: a. Standard: MSS SP -80, Type 3. b. CWP Rating: 300 psig (2070 kPa). c. Body Design: Horizontal flow. d. Body Material: ASTM B 62, bronze. e. Ends: Threaded. f. Disc: Bronze. 2.8 IRON SWING CHECK VALVES A. Class 125, Iron Swing Check Valves with Metal Seats: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Crane Co.; Crane Valve Group; Crane Valves. b. Crane Co.; Crane Valve Group; Jenkins Valves. c. Crane Co.; Crane Valve Group; Stockham Division. d. Hammond Valve. e. Kitz Corporation. f. Legend Valve. g. Milwaukee Valve Company. h. NIBCO INC. Powell Valves. j. Red -White Valve Corporation. k. Sure Flow Equipment Inc. I. Watts Regulator Co.; a division of Watts Water Technologies, Inc. m. Zy-Tech Global Industries, Inc. Description: a. Standard: MSS SP -71, Type I. b. NPS 2-1/2 to NPS 12 (DN 65 to DN 300), CWP Rating: 200 psig (1380 kPa). c. NPS 14 to NPS 24 (DN 350 to DN 600), CWP Rating: 150 psig (1035 kPa). d. Body Design: Clear or full waterway. e. Body Material: ASTM A 126, gray iron with bolted bonnet. f. Ends: Flanged. g. Trim: Bronze. GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS h. Gasket: Asbestos free. B. Class 250, Iron Swing Check Valves with Metal Seats: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Crane Co.; Crane Valve Group; Crane Valves. b. Crane Co.; Crane Valve Group; Jenkins Valves. c. Crane Co.; Crane Valve Group; Stockham Division. d. Hammond Valve. e. Milwaukee Valve Company. f. NIBCO INC. g. Watts Regulator Co.; a division of Watts Water Technologies, Inc. 2. Description: a. Standard: MSS SP -71, Type I. b. NPS 2-1/2 to NPS 12 (DN 65 to DN 300), CWP Rating: 500 psig (3450 kPa). c. NPS 14 to NPS 24 (DN 350 to DN 600), CWP Rating: 300 psig (2070 kPa). d. Body Design: Clear or full waterway. e. Body Material: ASTM A 126, gray iron with bolted bonnet. f. Ends: Flanged. g. Trim: Bronze. h. Gasket: Asbestos free. 2.9 IRON, GROOVED -END SWING CHECK VALVES A. 300 CWP, Iron, Grooved -End Swing Check Valves: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Anvil International, Inc. b. Shurjoint Piping Products. c. Tyco Fire Products LP; Grinnell Mechanical Products. d. Victaulic Company. 2. Description: a. CWP Rating: 300 psig (2070 kPa). b. Body Material: ASTM A 536, ductile iron. c. Seal: EPDM. d. Disc: Spring operated, ductile iron or stainless steel. 2.10 FLOW BALANCING VALVES A. Automatic Flow Control Valve: Provide automatic flow control valves with variable openings which respond to pressure, factory set to control the water flow over an operating pressure differential at least 10 times the minimum required for full flow conditions. Valves shall be tamper proof when installed, and shall have body pressure tappings with a set of pressure and temperature test ports. Valves shall have flanged or grooved ends or a union either integral or directly adjacent to permit replacement of the control element. The automatic flow controls shall GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS be selected for the project by the manufacturer to provide flow rates matching the equipment requirements, including any increased or decreased flow rates that are indicated. The control range pressure differential shall not exceed 3 to 40 psi. B. Manufacturer: 1. Autoflow, Inc. 2. Griswold 3. Approved substitution C. Calibration Meter: Provide one portable differential pressure gauge calibration meter kit of same manufacturer as valves. Kit shall be housed in a hand -carrying case and shall contain all devices required, including pressure gauges, 5 foot meter hoses with disconnect ends, positive shutoff valves, operating instructions, and flow versus pressure drop curves, to enable testing and balancing of each size and type of balancing valve installed. 2.11 CHAINWHEELS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Babbitt Steam Specialty Co. 2. Roto Hammer Industries. 3. Trumbull Industries. B. Description: Valve actuation assembly with sprocket rim, brackets, and chain. 1. Brackets: Type, number, size, and fasteners required to mount actuator on valve. 2. Attachment: For connection to butterfly valve stems. 3. Sprocket Rim with Chain Guides: Ductile or cast iron, of type and size required for valve. 4. Chain: Hot -dip, galvanized steel, of size required to fit sprocket rim. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove special packing materials, such as blocks, used to prevent disc movement during shipping and handling. B. Operate valves in positions from fully open to fully closed. Examine guides and seats made accessible by such operations. C. Examine threads on valve and mating pipe for form and cleanliness. D. Examine mating flange faces for conditions that might cause leakage. Check bolting for proper size, length, and material. Verify that gasket is of proper size, that its material composition is suitable for service, and that it is free from defects and damage. Do not attempt to repair defective valves; replace with new valves. GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3.2 VALVE INSTALLATION A. Install valves with unions or flanges at each piece of equipment arranged to allow service, maintenance, and equipment removal without system shutdown. B. Locate valves for easy access and provide separate support where necessary. C. Install valves in horizontal piping with stem at or above center of pipe. D. Install valves in position to allow full stem movement. E. Install chainwheels on operators for butterfly valves NPS 4 and larger and more than 96 inches above floor. Extend chains to 60 inches above finished floor. F. Install isolation/shutoff valve at all main risers and main branch takeoffs, to permit isolation of piping sections for drainage. G. Install isolation/shutoff valves on each inlet and outlet of each piece of equipment to which water is piped to allow isolation, venting and drainage. Provide a flange, union, or groove between the valve and the equipment to permit disconnection, removal and service. H. Install check valves for proper direction of flow and as follows: 1. Swing Check Valves: In horizontal position with hinge pin level. 2. Y -pattern horizontal swing check valves shall be used in vertical lines. 3. Horizontal swing check valves shall be used with ball valves; 4. Wafer check valves shall be used with butterfly valves. 3.3 ADJUSTING A. Adjust or replace valve packing after piping systems have been tested and put into service but before final adjusting and balancing. Replace valves if persistent leaking occurs. 3.4 GENERAL REQUIREMENTS FOR VALVE APPLICATIONS A. If valve applications are not indicated, use the following: 1. Shutoff Service: Ball, or butterfly valves. 2. Butterfly Valve Dead -End Service: Single -flange (lug) type. 3. Throttling Service: Ball or butterfly valves, B. If valves with specified SWP classes or CWP ratings are not available, the same types of valves with higher SWP classes or CWP ratings may be substituted. C. Select valves, except wafer types, with the following end connections: 1. For Copper Tubing, NPS 2 and Smaller: Threaded ends except where solder -joint valve - end option is indicated in valve schedules below. 2. For Copper Tubing, NPS 2-1/2 to NPS 4: Flanged ends except where threaded valve -end option is indicated in valve schedules below. 3. For Copper Tubing, NPS 5 and Larger: Flanged ends. 4. For Steel Piping, NPS 2 and Smaller: Threaded ends. GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 5. For Steel Piping, NPS 2-1/2 to NPS 4: Flanged ends except where threaded valve -end option is indicated in valve schedules below. 6. For Steel Piping, NPS 5 and Larger: Flanged ends. 7. For Grooved -End Copper Tubing and Steel Piping except Steam and Steam Condensate Piping: Valve ends may be grooved. 3.5 CHILLED -WATER VALVE SCHEDULE A. Pipe NPS 2 and Smaller: 1. Bronze Valves: May be provided with solder -joint ends instead of threaded ends. 2. Ball Valves: Two piece, standard port, bronze with bronze trim. 3. Bronze Swing Check Valves: Class 125, bronze disc. B. Pipe NPS 2-1/2 and Larger 1. Iron Ball Valves, NPS 2-1/2 to NPS 10 (DN 65 to DN 250): Class 150. 2. Iron, Single -Flange Butterfly Valves, NPS 2-1/2 to NPS 12: 200 CWP, EPDM seat, aluminum -bronze disc. 3. Iron, Grooved -End Butterfly Valves, NPS 2-1/2 to NPS 12: 175 CWP. 4. Iron Swing Check Valves: Class 125, metal seats. 5. Iron, Grooved -End Check Valves, NPS 3 to NPS 12: 300 CWP. 3.6 HEATING -WATER VALVE SCHEDULE A. Pipe NPS 2 and Smaller: 1. Bronze Valves: May be provided with solder -joint ends instead of threaded ends. 2. Ball Valves: Two piece, standard port, bronze with bronze trim. 3. Bronze Swing Check Valves: Class 125, bronze disc. B. Pipe NPS 2-1/2 and Larger: 1. Iron Ball Valves, NPS 2-1/2 to NPS 10 (DN 65 to DN 250): Class 150. 2. Iron, Single -Flange Butterfly Valves, NPS 2-1/2 to NPS 12: 200 CWP, EPDM seat, aluminum -bronze disc. 3. Iron, Grooved -End Butterfly Valves, NPS 2-1/2 to NPS 12: 175 CWP. 4. Iron Swing Check Valves: Class 125, metal seats. 5. Iron, Grooved -End Check Valves, NPS 3 to NPS 12: 300 CWP. 3.7 FLOW BALANCING VALVES A. Location: Provide flow balancing valves where indicated. The exact location shall be determined using field measurements relating to the specific piping arrangement and the manufacturer's recommendations. B. Manufacturer' Recommendation: Install in accordance with manufacturer's recommendations including valve orientation and increases or decreases in pipe size at points of installation, together with minimum recommended lengths of straight pipe before and after points of installation. GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 11 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Calibration Meter: At the conclusion of the system test and balance and prior to final completion the meter shall be turned over to, and shall become the property of, the Owner. 3.8 DRAIN VALVES A. Location: Install drain valves at the base of all water piping risers (both supply and return) and at all low points in the piping system. Drain valves shall be fitted with schedule 80 hose connection end with cap unless otherwise indicated. END OF SECTION 230523 GENERAL -DUTY VALVES FOR HVAC PIPING 230523 - 12 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Metal pipe hangers and supports. 2. Fastener systems. B. Related Sections: 1. Section 055000 "Metal Fabrications" for structural -steel shapes and plates for trapeze hangers for pipe and equipment supports. 2. Section 230548 "Vibration and Seismic Controls for HVAC" for vibration isolation devices. 3. Section 233113 "Metal Ducts" for duct hangers and supports. 1.3 DEFINITIONS A. MSS: Manufacturers Standardization Society of The Valve and Fittings Industry Inc. 1.4 PERFORMANCE REQUIREMENTS A. Structural Performance: Hangers and supports for HVAC piping and equipment shall withstand the effects of gravity loads and stresses within limits and under conditions indicated according to ASCE/SEI 7. 1. Design supports for multiple pipes, including pipe stands, capable of supporting combined weight of supported systems, system contents, and test water. 2. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components. 3. Design seismic -restraint hangers and supports for piping and equipment. 1.5 ACTION SUBMITTALS A. Product Data: For each type of product indicated. 1.6 QUALITY ASSURANCE A. Structural Steel Welding Qualifications: Qualify procedures and personnel according to AWS DI.1/D1.1M, "Structural Welding Code- Steel." HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Pipe Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code. PART 2 - PRODUCTS 2.1 METAL PIPE HANGERS AND SUPPORTS A. Carbon -Steel Pipe Hangers and Supports: 1. Description: MSS SP -58, Types 1 through 58, factory -fabricated components. 2. Galvanized Metallic Coatings: Pregalvanized or hot dipped. 3. Nonmetallic Coatings: Plastic coating, jacket, or liner. 4. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of piping. 5. Hanger Rods: Continuous -thread rod, nuts, and washer made of carbon steel. 2.2 FASTENER SYSTEMS A. Mechanical -Expansion Anchors: Insert -wedge -type, zinc -coated steel anchors, for use in hardened portland cement concrete; with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used. 2.3 MISCELLANEOUS MATERIALS A. Structural Steel: ASTM A 36/A 36M, carbon -steel plates, shapes, and bars; black and galvanized. Grout: ASTM C 1107, factory -mixed and -packaged, dry, hydraulic -cement, nonshrink and nonmetallic grout; suitable for interior and exterior applications. 1. Properties: Nonstaining, noncorrosive, and nongaseous. 2. Design Mix: 5000 -psi , 28 -day compressive strength. PART 3 - EXECUTION 3.1 HANGER AND SUPPORT INSTALLATION A. Metal Pipe -Hanger Installation: Comply with MSS SP -69 and MSS SP -89. Install hangers, supports, clamps, and attachments as required to properly support piping from the building structure. B. Fastener System Installation: Install mechanical -expansion anchors in concrete after concrete is placed and completely cured. Install fasteners according to manufacturer's written instructions. C. Install hangers and supports complete with necessary attachments, inserts, bolts, rods, nuts, washers, and other accessories. HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Install hangers and supports to allow controlled thermal and seismic movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units. E. Install lateral bracing with pipe hangers and supports to prevent swaying. F. Load Distribution: Install hangers and supports so that piping live and dead loads and stresses from movement will not be transmitted to connected equipment. G. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and to not exceed maximum pipe deflections allowed by ASME 831.9 for building services piping. H. Insulated Piping: 1. Attach clamps and spacers to piping. a. Piping Operating above Ambient Air Temperature: Clamp may project through insulation. b. Piping Operating below Ambient Air Temperature: Use thermal -hanger shield insert with clamp sized to match OD of insert. c. Do not exceed pipe stress limits allowed by ASME B31.9 for building services piping. 2. Install MSS SP -58, Type 39, protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation. a. Option: Thermal -hanger shield inserts may be used. Include steel weight - distribution plate for pipe NPS 4 and larger if pipe is installed on rollers. 3. Install MSS SP -58, Type 40, protective shields on cold piping with vapor barrier. Shields shall span an arc of 180 degrees. a. Option: Thermal -hanger shield inserts may be used. Include steel weight - distribution plate for pipe NPS 4 and larger if pipe is installed on rollers. 4. Shield Dimensions for Pipe: Not less than the following: a. NPS 1/4 to NPS 3-1/2 : 12 inches long and 0.048 inch thick. b. NPS 4 : 12 inches long and 0.06 inch thick. 5. Thermal -Hanger Shields: Install with insulation same thickness as piping insulation. 3.2 METAL FABRICATIONS A. Fit exposed connections together to form hairline joints. Field weld connections that cannot be shop welded because of shipping size limitations. B. Field Welding: Comply with AWS D1.1/D1.1M procedures for shielded, metal arc welding; appearance and quality of welds; and methods used in correcting welding work; and with the following: 1. Use materials and methods that minimize distortion and develop strength and corrosion resistance of base metals. 2. Obtain fusion without undercut or overlap. HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3. Remove welding flux immediately. 4. Finish welds at exposed connections so no roughness shows after finishing and so contours of welded surfaces match adjacent contours. 3.3 ADJUSTING A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe. B. Trim excess length of continuous -thread hanger and support rods to 1-1/2 inches. 3.4 PAINTING A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field -painted surfaces. 1. Apply paint by brush or spray to provide a minimum dry film thickness of 2.0 mils . B. Touchup: Cleaning and touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal are specified in Section 099123 "Interior Painting" C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing -repair paint to comply with ASTM A 780. 3.5 HANGER AND SUPPORT SCHEDULE A. Specific hanger and support requirements are in Sections specifying piping systems and equipment. B. Comply with MSS SP -69 for pipe -hanger selections and applications that are not specified in piping system Sections. C. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing. D. Use carbon -steel pipe hangers and supports and attachments for general service applications. E. Use padded hangers for piping that is subject to scratching. F. Horizontal -Piping Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of noninsulated or insulated, stationary pipes NPS 1/2 to NPS 30 . G. Vertical -Piping Clamps: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers NPS 3/4 to NPS 24 . HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS H. Hanger -Rod Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types: 1. Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches for heavy loads. Use mechanical -expansion anchors instead of building attachments where required in concrete construction. END OF SECTION 230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230548 - VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Isolation pads. 2. Isolation mounts. 3. Spring isolators. 4. Duct silencers. 5. Acoustic housings. 6. Ductwork lagging. 1.3 DEFINITIONS A. ICC -ES: ICC -Evaluation Service. B. OSHPD: Office of Statewide Health Planning and Development for the State of California. 1.4 REFERENCES A. Air Movement and Control Association International, Inc.: 1. AMCA 300 - Reverberant Room Method for Sound Testing of Fans. American National Standards Institute: 1. ANSI S1.4 - Sound Level Meters. 2. ANSI S1.8 - Reference Quantities for Acoustical Levels. 3. ANSI S1.13 - Methods for the Measurement of Sound Pressure Levels in Air. 4. ANSI S12.36 - Survey Methods for the Determination of Sound Power Levels of Noise Sources. C. Air -Conditioning and Refrigeration Institute: 1. ARI 575 - Method of Measuring Machinery Sound within Equipment Space. D. American Society of Heating, Refrigerating and Air -Conditioning Engineers: 1. ASHRAE 68 - Laboratory Method of Testing In -Duct Sound Power Measurement Proce- dure for Fans. 2. ASHRAE Handbook - 2007 HVAC Applications Chapter 47. E. ASTM International: 1. ASTM E90 - Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT 230548 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. ASTM E477 - Standard Test Method for Measuring Acoustical and Airflow Performance of Duct Liner Materials and Prefabricated Silencers. 3. ASTM E596 - Standard Test Method for Laboratory Measurement of the Noise Reduction of Sound -Isolating Enclosures. F. Sheet Metal and Air Conditioning Contractors' National Association: 1. SMACNA - HVAC Duct Construction Standard - Metal and Flexible. 2. SMACNA - Restraint Manual: Guidelines for Mechanical Systems. 1.5 PERFORMANCE REQUIREMENTS A. Wind -Restraint Loading: 1. Basic Wind Speed: 110 mph. 2. Building Classification Category: I. 3. Minimum 10 Ib/sq. ft. multiplied by the maximum area of the HVAC component projected on a vertical plane that is normal to the wind direction, and 45 degrees either side of normal. 1.6 SUBMITTALS A. Product Data: For the following: 1. Include rated load, rated deflection, and overload capacity for each vibration isolation device. 2. Interlocking Snubbers: Include ratings for horizontal, vertical, and combined loads. 3. Acoustical Silencers. B. Delegated -Design Submittal: For vibration isolation and seismic -restraint details indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation. 1. Design Calculations: Calculate static and dynamic loading due to equipment weight and operation, wind forces required to select vibration isolators, wind restraints, and for designing vibration isolation bases. a. Coordinate design calculations with wind load calculations required for equipment mounted outdoors. Comply with requirements in other Division 23 Sections for equipment mounted outdoors. C. If the standard sizes of silencers offered by the silencer manufacturer or vendor do not provide attenuation equal to or greater than the specified insertion loss in each octave band 1 through 6, then at the time of bidding the manufacturer/vendor making the submission shall note all such discrepancies and provide alternative proposals and pricing to make up the discrepancies. The controlling requirements are the insertion loss, pressure drop and self -noise. D. Welding certificates. E. Sheet Metal: Coordinated shop drawings shall be submitted for review and approval to indicate the following: 1. Length, width, height, and elevation of bottom of each duct segment. 2. Sheet metal gauge VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT 230548 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3. Location of duct silencers, fire dampers, and balancing dampers. F. Air moving devices for classrooms (AHU's): Submit sound power levels in octave bands from 63 Hz through 8000 Hz inclusive for the operating conditions specified. Data shall be obtained in accordance with AMCA 300-85. If fans are variable speed, provide sound power level data for maximum rpm and also at 80% and 60% of maximum rpm. Provide discharge, inlet and case -radiated sound power data for all fans. 1. Submit for each fan a performance curve showing the operating point for which the acoustical data has been provided. G. Silencers: Submit test data from an independent laboratory showing the insertion loss and air -flow -regenerated noise of the specified silencers in octave bands from 63 Hz to 8000 Hz, measured in accordance with ASTM E477-73. Pressure drop ratings shall be measured for the same silencer tested for acoustical performance; the data shall be submitted with the acoustical performance data. The insertion loss of the silencers shall be measured and reported in octave band or 1/3 octave bands. 1.7 QUALITY ASSURANCE A. Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel." B. Wind Restraint devices shall comply with the wind rating as specified within this section. Restraint devices shall be suitable for the specific application and have a Florida structural engineering seal for compliance. PART 2 - PRODUCTS 2.1 VIBRATION ISOLATORS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Amber/Booth Company, Inc. 2. Kinetics Noise Control. 3. Mason Industries. Pads: Arranged in single or multiple layers of sufficient stiffness for uniform loading over pad area, molded with a nonslip pattern and galvanized -steel baseplates, and factory cut to sizes that match requirements of supported equipment. 1. Resilient Material: Oil- and water-resistant neoprene. C. Mounts: Double -deflection type, with molded, oil -resistant rubber, hermetically sealed compressed fiberglass, or neoprene isolator elements with factory -drilled, encapsulated top plate for bolting to equipment and with baseplate for bolting to structure. Color -code or otherwise identify to indicate capacity range. 1. Materials: Cast -ductile -iron or welded steel housing containing two separate and opposing, oil -resistant rubber or neoprene elements that prevent central threaded element and attachment hardware from contacting the housing during normal operation. VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT 230548 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Neoprene: Shock -absorbing materials compounded according to the standard for bridge - bearing neoprene as defined by AASHTO. D. Spring Hangers with Vertical -Limit Stop: Combination coil -spring and elastomeric-insert hanger with spring and insert in compression and with a vertical -limit stop. 1. Frame: Steel, fabricated for connection to threaded hanger rods and to allow for a maximum of 30 degrees of angular hanger -rod misalignment without binding or reducing isolation efficiency. 2. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load. 3. Minimum Additional Travel: 50 percent of the required deflection at rated load. 4. Lateral Stiffness: More than 80 percent of rated vertical stiffness. 5. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure. 6. Elastomeric Element: Molded, oil -resistant rubber or neoprene. 7. Adjustable Vertical Stop: Steel washer with neoprene washer "up -stop" on lower threaded rod. 8. Self -centering hanger rod cap to ensure concentricity between hanger rod and support spring coil. 2.2 FACTORY FINISHES A. Finish: Manufacturer's standard paint applied to factory -assembled and -tested equipment before shipping. 1. Powder coating on springs and housings. 2. All hardware shall be galvanized. Hot -dip galvanize metal components for exterior use. 3. Baked enamel or powder coat for metal components on isolators for interior use. 4. Color -code or otherwise mark vibration isolation and wind -control devices to indicate capacity range. 2.3 DUCT SILENCERS A. All prefabricated duct silencers shall be furnished by a single manufacturer with a minimum five years experience. The following manufacturers are pre -approved based on the quality of their products. The Acoustics Consultant and Architect must approve any alternates. All provided equipment must be in compliance with the specified design and performance requirements: 1. Industrial Acoustics Company, Bronx, New York 2. Vibro-Acoustics, Scarborough, Ontario 3. AeroAcoustic Corporation, Roselle, New Jersey 4. Pre -Approved Alternate Manufacturer Prior to Bid B. Rectangular duct silencers shall have outer casings of not less than 22 -gauge galvanized steel. Seams shall be lock formed and mastic filled. The internal baffles (splitters) shall be not less than 24 -gauge galvanized perforated steel having an open area of about 30%. The nosings shall be full radius or airfoil shape. C. The sound absorbing media shall be not less than 4.5 pcf glass/mineral fiber packed under 5% compression. The fiber fill shall be incombustible, mildew resistant and vermin proof. The sound absorbing material shall be protected from erosion. VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT 230548 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. If the silencer is supplied in modular sections, the silencer shall meet or exceed the specification for single -module silencers with respect to insertion loss, pressure drop, regenerated noise and air leakage. E. Rating: 1. ASTM E477 Minimum Required Insertion Loss and Maximum Allowable Generated Noise at 1000 fpm (7 m/sec). See schedules on Drawings. 2. Static Pressure Drop: see schedules on Drawings. 3. Air Tight Static Pressure: 10 inches wg (2.5 kPa). F. Performance: Achieve insertion loss self generated noise, and static pressure drop for cfm flow required per schedules on Drawings. 2.4 DUCTWORK LAGGING A. Acoustic Insulation: 2 inch thick, 3 to 5 Ib/cu ft density glass fiber or mineral wool insulation. B. Covering: Sheet lead with surface weight minimum 4 Ib/sq ft. C. Provide Duct lagging from sound attenuator location within mechanical room to mechanical room wall to prevent break-in noise. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine areas and equipment to receive vibration isolation and wind -control devices for compliance with requirements for installation tolerances and other conditions affecting performance. B. Examine roughing -in of reinforcement and cast -in-place anchors to verify actual locations before installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 APPLICATIONS A. Multiple Pipe Supports: Secure pipes to trapeze member with clamps approved for application by an evaluation service member of ICC -ES. B. Strength of Support and Seismic -Restraint Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static and seismic loads within specified loading limits. 3.3 FIELD QUALITY CONTROL A. Testing Agency: Owner will engage a qualified testing agency to perform tests and inspections. B. Tests and Inspections: VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT 230548 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Provide evidence of recent calibration of test equipment by a testing agency acceptable to authorities having jurisdiction. 2. Schedule test with Owner, through Architect, before connecting anchorage device to restrained component (unless postconnection testing has been approved), and with at least seven days' advance notice. 3. Obtain Architect's approval before transmitting test loads to structure. Provide temporary load -spreading members. 4. Test at least four of each type and size of installed anchors and fasteners selected by Architect. 5. Test to 90 percent of rated proof load of device. 6. Measure isolator restraint clearance. 7. Measure isolator deflection. 8. Verify snubber minimum clearances. 9. If a device fails test, modify all installations of same type and retest until satisfactory results are achieved. C. Remove and replace malfunctioning units and retest as specified above. D. Prepare test and inspection reports. 3.4 ADJUSTING A. Adjust isolators after piping system is at operating weight. B. Adjust limit stops on restrained spring isolators to mount equipment at normal operating height. After equipment installation is complete, adjust limit stops so they are out of contact during normal operation. C. Adjust active height of spring isolators. D. Adjust restraints to permit free movement of equipment within normal mode of operation. 3.5 HVAC VIBRATION -CONTROL RESTRAINT DEVICE SCHEDULE A. Supported or Suspended Equipment: 1. Air Handling Unit Vibration Pads: a. Material: Neoprene. b. Thickness: 3/4 inches. c. Provide Full sheet of Neoprene Under Base Rail of Units. END OF SECTION 230548 VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT 230548 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Equipment labels. 2. Warning signs and labels. 3. Pipe labels. 4. Duct labels. 5. Stencils. 6. Valve tags. 1.3 SUBMITTALS A. Product Data: For each type of product indicated. B. Valve numbering scheme. 1.4 COORDINATION A. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied. B. Coordinate installation of identifying devices with locations of access panels and doors. C. Install identifying devices before installing acoustical ceilings and similar concealment. PART 2 - PRODUCTS 2.1 EQUIPMENT LABELS A. Metal Labels for Equipment: 1. Material and Thickness: Aluminum, 0.032 -inch minimum thickness, and having predrilled or stamped holes for attachment hardware. 2. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch. 3. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering. 4. Adhesive: Contact -type permanent adhesive, compatible with label and with substrate. B. Label Content: Include equipment's Drawing designation or unique equipment number, Drawing numbers where equipment is indicated (plans, details, and schedules), plus the Specification Section number and title where equipment is specified. C. Equipment Label Schedule: For each item of equipment to be labeled, on 8 -1/2 -by -11 -inch bond paper. Tabulate equipment identification number and identify Drawing numbers where equipment is indicated (plans, details, and schedules), plus the Specification Section number and title where equipment is specified. Equipment schedule shall be included in operation and maintenance data. 2.2 CEILING GRID TAGS FOR EQUIPMENT LOCATED ABOVE HARD OR LAY -IN CEILING A. Description: 3/4" x 3" vinyl label, 3.0 Mil self adhesive vinyl similar to DuraLabel Pro. Label color shall be black text on a white background. The label shall contain the following information: 1. Equipment name: Per Scheduled Equipment Naming convention. B. All scheduled equipment above finish hard or lay -in ceiling shall be identified with an Equipment Tag. 2.3 WARNING SIGNS AND LABELS A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8 inch thick, and having predrilled holes for attachment hardware. B. Letter Color: Red. C. Background Color: White. D. Maximum Temperature: Able to withstand temperatures up to 160 deg F E. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch. F. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches , 1/2 inch for viewing distances up to 72 inches , and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering. G. Fasteners: Stainless-steel rivets. H. Adhesive: Contact -type permanent adhesive, compatible with label and with substrate. I. Label Content: Include caution and warning information, plus emergency notification instructions. IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.4 PIPE LABELS A. General Requirements for Manufactured Pipe Labels: Preprinted, color -coded, with lettering indicating service, and showing flow direction. Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to cover full circumference of pipe and to attach to pipe without fasteners or adhesive. C. Pipe Label Contents: Include identification of piping service using same designations or abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction. 1. Flow -Direction Arrows: Integral with piping system service lettering to accommodate both directions or as separate unit on each pipe label to indicate flow direction. 2. Lettering Size: At least 1-1/2 inches. 2.5 DUCT LABELS A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8 inch thick, and having predrilled holes for attachment hardware. B. Letter Color: Black. C. Background Color White. D. Maximum Temperature: Able to withstand temperatures up to 160 deg F. E. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch. F. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering. G. Adhesive: Contact -type permanent adhesive, compatible with label and with substrate. H. Duct Label Contents: Include identification of duct service using same designations or abbreviations as used on Drawings, duct size, and an arrow indicating flow direction. 1. Flow -Direction Arrows: Integral with duct system service lettering to accommodate both directions, or as separate unit on each duct label to indicate flow direction. 2. Lettering Size: At least 1-1/2 inches. 2.6 VALVE TAGS A. Valve Tags: Stamped or engraved with 1/4 -inch letters for piping system abbreviation and 1/2 - inch numbers. 1. Tag Material: Aluminum, 0.032 -inch minimum thickness, and having predrilled or stamped holes for attachment hardware. 2. Fasteners: Brass wire -link or beaded chain; or S -hook. IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Valve Schedules: For each piping system, on 8 -1/2 -by -11 -inch bond paper. Tabulate valve number, piping system, system abbreviation (as shown on valve tag), location of valve (room or space), normal -operating position (open, closed, or modulating), and variations for identification. Mark valves for emergency shutoff and similar special uses. 1. Valve -tag schedule shall be included in operation and maintenance data. PART 3 - EXECUTION 3.1 PREPARATION A. Clean piping and equipment surfaces of substances that could impair bond of identification devices, including dirt, oil, grease, release agents, and incompatible primers, paints, and encapsulants. 3.2 EQUIPMENT LABEL INSTALLATION A. Install or permanently fasten labels on each major item of mechanical equipment. B. Locate equipment labels where accessible and visible. C. All mechanical equipment, located above the ceiling and requiring maintenance or accessibility, shall be labeled on the ceiling or ceiling grid, directly below the indicated equipment. 1. Provide ceiling grid tags to locate scheduled equipment above T -bar type panel ceilings. Locate in corner of grid closest to equipment. 2. Provide ceiling tags to locate scheduled equipment above access panels in hard ceilings. Locate in corner of access panel closest to equipment. 3.3 PIPE LABEL INSTALLATION Piping Color -Coding: Painting of piping is specified in Division 9 Section "Interior Painting." B. Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior exposed locations as follows: 1. Near each valve and control device. 2. Near each branch connection, excluding short takeoffs for fixtures and terminal units. Where flow pattern is not obvious, mark each pipe at branch. 3. Near penetrations through walls, floors, ceilings, and inaccessible enclosures. 4. At access doors, manholes, and similar access points that permit view of concealed piping. 5. Near major equipment items and other points of origination and termination. 6. Spaced at maximum intervals of 50 feet along each run. Reduce intervals to 25 feet in areas of congested piping and equipment. 7. On piping above removable acoustical ceilings. Omit intermediately spaced labels. C. Pipe Label Color Schedule: Chilled -Water Piping: IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Background Color: White. b. Letter Color: Blue. 2. Refrigerant Piping: a. Background Color: Black. b. Letter Color: White. 3.4 DUCT LABEL INSTALLATION A. Install plastic -laminated duct labels with permanent adhesive on air ducts in the following color codes: 1. Blue: For cold -air supply ducts. 2. Yellow: For hot-air supply ducts. 3. Green: For exhaust-, outside-, relief-, return-, and mixed -air ducts. B. Locate labels near points where ducts enter into concealed spaces and at maximum intervals of 50 feet in each space where ducts are exposed or concealed by removable ceiling system. 3.5 VALVE -TAG INSTALLATION A. Install tags on valves and control devices in piping systems, except check valves; valves within factory -fabricated equipment units; shutoff valves; faucets; convenience and lawn -watering hose connections; and HVAC terminal devices and similar roughing -in connections of end-use fixtures and units. List tagged valves in a valve schedule. Valve -Tag Application Schedule: Tag valves according to size, shape, and color scheme and with captions similar to those indicated in the following subparagraphs: 1. Valve -Tag Size and Shape: a. Chilled Water: 2 inches, square. 2. Valve -Tag Color: a. Chilled Water: Natural. 3. Letter Color: a. Chilled Water: Black. END OF SECTION 230553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant -volume air systems. b. Variable -air -volume systems. c. General exhaust systems. d. Outside Air/Stale Exhaust systems. 2. Balancing Hydronic Piping Systems: a. Variable -flow hydronic systems. 1) Systems installed with pressure independent control valves shall not require hydronic system balancing. Flow shall be verified and adjusted for the pressure independent valve assembly for field conditions using the pressure independent control valve manufacturer's documented procedure for 25% of the total installed product. Exact locations of tested product to be coordinated with the commissioning agent. 1.3 DEFINITIONS A. AABC: Associated Air Balance Council. B. NEBB: National Environmental Balancing Bureau. C. TAB: Testing, adjusting, and balancing. D. TABB: Testing, Adjusting, and Balancing Bureau. E. TAB Specialist: An entity engaged to perform TAB Work. 1.4 SUBMITTALS A. LEED Submittal: 1. Air -Balance Report for LEED Prerequisite EQ 1: Documentation of work performed for ASHRAE 62.1-2004, Section 7.2.2, "Air Balancing." TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Qualification Data: Within 30 days of Contractor's Notice to Proceed, submit documentation that the TAB contractor and this Projects TAB team members meet the qualifications specified in "Quality Assurance" Article. C. Contract Documents Examination Report: Within 30 days of Contractor's Notice to Proceed, submit the Contract Documents review report as specified in Part 3. D. Strategies and Procedures Plan: Within 60 days of Contractor's Notice to Proceed, submit TAB strategies and step-by-step procedures as specified in "Preparation" Article. E. Certified TAB reports. F. Sample report forms. G. Instrument calibration reports, to include the following: 1. Instrument type and make. 2. Serial number. 3. Application. 4. Dates of use. 5. Dates of calibration. 1.5 QUALITY ASSURANCE A. TAB Contractor Qualifications: Engage a TAB entity certified by AABC, NEBB or TABB. 1. TAB Field Supervisor: Employee of the TAB contractor and certified by AABC, NEBB or TABB. 2. TAB Technician: Employee of the TAB contractor and who is certified by AABC, NEBB or TABB as a TAB technician. B. TAB Conference: Meet with Architect, Owner Representative, General Contractor, Engineer and Commissioning Authority on approval of the TAB strategies and procedures plan to develop a mutual understanding of the details. Require the participation of the TAB field supervisor and technicians. Provide seven days' advance notice of scheduled meeting time and location. 1. Agenda Items: a. The Contract Documents examination report. b. The TAB plan. c. Coordination and cooperation of trades and subcontractors. d. Coordination of documentation and communication flow. C. Certify TAB field data reports and perform the following: 1. Review field data reports to validate accuracy of data and to prepare certified TAB reports. 2. Certify that the TAB team complied with the approved TAB plan and the procedures specified and referenced in this Specification. D. TAB Report Forms: Use standard TAB contractor's forms approved by Commissioning Authority. TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 2 INDIAN RIVER COUNTY INTERGENERATIONAL RECREATION CENTER E. Instrumentation Type, Quantity, Accuracy, Section 5, "Instrumentation." 1.6 PROJECT CONDITIONS JULY 25, 2014 100% CONSTRUCTION DOCUMENTS and Calibration: As described in ASHRAE 111, A. Full Owner Occupancy: Owner will occupy the site and existing building during entire TAB period. Cooperate with Owner during TAB operations to minimize conflicts with Owner's operations. B. Partial Owner Occupancy: Owner may occupy completed areas of building before Substantial Completion. Cooperate with Owner during TAB operations to minimize conflicts with Owner's operations. 1.7 COORDINATION A. Notice: Provide seven days' advance notice for each test. Include scheduled test dates and times. B. Perform TAB after leakage and pressure tests on air and water distribution systems have been satisfactorily completed. PART 2 - PRODUCTS (Not Applicable) PART 3 - EXECUTION 3.1 EXAMINATION A. Examine the Contract Documents to become familiar with Project requirements and to discover conditions in systems' designs that may preclude proper TAB of systems and equipment. B. Examine systems for installed balancing devices, such as test ports, gage cocks, thermometer wells, flow -control devices, balancing valves and fittings, and manual volume dampers. Verify that locations of these balancing devices are accessible. C. Examine the approved submittals for HVAC systems and equipment. D. Examine design data including HVAC system descriptions, statements of design assumptions for environmental conditions and systems' output, and statements of philosophies and assumptions about HVAC system and equipment controls. E. Examine ceiling plenums and underfloor air plenums used for supply, return, or relief air to verify that they meet the leakage class of connected ducts as specified in Division 23 Section "Metal Ducts" and are properly separated from adjacent areas. Verify that penetrations in plenum walls are sealed and fire -stopped if required. F. Examine equipment performance data including fan and pump curves. 1. Relate performance data to Project conditions and requirements, including system effects that can create undesired or unpredicted conditions that cause reduced capacities in all or part of a system. TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Calculate system -effect factors to reduce performance ratings of HVAC equipment when installed under conditions different from the conditions used to rate equipment performance. To calculate system effects for air systems, use tables and charts found in AMCA 201, "Fans and Systems," or in SMACNA's "HVAC Systems - Duct Design." Compare results with the design data and installed conditions. G. Examine system and equipment installations and verify that field quality -control testing, cleaning, and adjusting specified in individual Sections have been performed. H. Examine test reports specified in individual system and equipment Sections. I. Examine HVAC equipment and filters and verify that bearings are greased, belts are aligned and tight, and equipment with functioning controls is ready for operation. J. Examine terminal units, such as variable -air -volume boxes, and verify that they are accessible and their controls are connected and functioning. K. Examine strainers. Verify that startup screens are replaced by permanent screens with indicated perforations. L. Examine heat -transfer coils for correct piping connections and for clean and straight fins. M. Examine system pumps to ensure absence of entrained air in the suction piping. N. Examine operating safety interlocks and controls on HVAC equipment. O. Report deficiencies discovered before and during performance of TAB procedures. Observe and record system reactions to changes in conditions. Record default set points if different from indicated values. 3.2 PREPARATION A. Prepare a TAB plan that includes strategies and step-by-step procedures. B. Complete system -readiness checks and prepare reports. Verify the following: 1. Permanent electrical -power wiring is complete. 2. Hydronic systems are filled, clean, and free of air. 3. Automatic temperature -control systems are operational. 4. Equipment and duct access doors are securely closed. 5. Isolating and balancing valves are open and control valves are operational. 6. Ceilings are installed in critical areas where air -pattern adjustments are required and access to balancing devices is provided. 7. Windows and doors can be closed so indicated conditions for system operations can be met. 3.3 GENERAL PROCEDURES FOR TESTING AND BALANCING A. Perform testing and balancing procedures on each system according to the procedures contained in AABC's "National Standards for Total System Balance", ASHRAE 111, NEBB's "Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems", and SMACNA's "HVAC Systems - Testing, Adjusting, and Balancing" and in this Section. TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Comply with requirements in ASHRAE 62.1-2004, Section 7.2.2, "Air Balancing." B. Cut insulation, ducts, pipes, and equipment cabinets for installation of test probes to the minimum extent necessary for TAB procedures. 1. After testing and balancing, patch probe holes in ducts with same material and thickness as used to construct ducts. 2. After testing and balancing, install test ports and duct access doors that comply with requirements in Division 23 Section "Air Duct Accessories." 3. Install and join new insulation that matches removed materials. Restore insulation, coverings, vapor barrier, and finish according to Division 23 Section "HVAC Insulation." C. Mark equipment and balancing devices, including damper -control positions, valve position indicators, fan -speed -control levers, and similar controls and devices, with paint or other suitable, permanent identification material to show final settings. D. Take and report testing and balancing measurements in inch -pound (IP) units. 3.4 GENERAL PROCEDURES FOR BALANCING AIR SYSTEMS A. Prepare test reports for both fans and outlets. Obtain manufacturer's outlet factors and recommended testing procedures. Crosscheck the summation of required outlet volumes with required fan volumes. B. Prepare schematic diagrams of systems' "as -built" duct layouts. C. For variable -air -volume systems, develop a plan to simulate diversity. D. Determine the best locations in main and branch ducts for accurate duct -airflow measurements. E. Check airflow patterns from the outdoor -air louvers and dampers and the return- and exhaust - air dampers through the supply -fan discharge and mixing dampers. F. Locate start -stop and disconnect switches, electrical interlocks, and motor starters. G. Verify that motor starters are equipped with properly sized thermal protection. H. Check dampers for proper position to achieve desired airflow path. I. Check for airflow blockages. J. Check condensate drains for proper connections and functioning. K. Check for proper sealing of air -handling -unit components. L. Verify that air duct system is sealed as specified in Division 23 Section "Metal Ducts." 3.5 PROCEDURES FOR CONSTANT -VOLUME AIR SYSTEMS A. Adjust fans to deliver total indicated airflows within the maximum allowable fan speed listed by fan manufacturer. 1. Measure total airflow. TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Where sufficient space in ducts is unavailable for Pitot -tube traverse measurements, measure airflow at terminal outlets and inlets and calculate the total airflow. 2. Measure fan static pressures as follows to determine actual static pressure: a. Measure outlet static pressure as far downstream from the fan as practical and upstream from restrictions in ducts such as elbows and transitions. b. Measure static pressure directly at the fan outlet or through the flexible connection. C. Measure inlet static pressure of single -inlet fans in the inlet duct as near the fan as possible, upstream from the flexible connection, and downstream from duct restrictions. d. Measure inlet static pressure of double -inlet fans through the wall of the plenum that houses the fan. 3. Measure static pressure across each component that makes up an air -handling unit, rooftop unit, and other air -handling and -treating equipment. a. Report the cleanliness status of filters and the time static pressures are measured. 4. Measure static pressures entering and leaving other devices, such as sound traps, heat - recovery equipment, and air washers, under final balanced conditions. 5. Review Record Documents to determine variations in design static pressures versus actual static pressures. Calculate actual system -effect factors. Recommend adjustments to accommodate actual conditions. 6. Obtain approval from Engineer and Commissioning Authority for adjustment of fan speed higher or lower than indicated speed. Comply with requirements in Division 23 Sections for air -handling units for adjustment of fans, belts, and pulley sizes to achieve indicated air -handling -unit performance. 7. Do not make fan -speed adjustments that result in motor overload. Consult equipment manufacturers about fan -speed safety factors. Modulate dampers and measure fan - motor amperage to ensure that no overload will occur. Measure amperage in full -cooling, full -heating, economizer, and any other operating mode to determine the maximum required brake horsepower. B. Adjust volume dampers for main duct, submain ducts, and major branch ducts to indicated airflows within specified tolerances. 1. Measure airflow of submain and branch ducts. a. Where sufficient space in submain and branch ducts is unavailable for Pitot -tube traverse measurements, measure airflow at terminal outlets and inlets and calculate the total airflow for that zone. 2. Measure static pressure at a point downstream from the balancing damper, and adjust volume dampers until the proper static pressure is achieved. 3. Remeasure each submain and branch duct after all have been adjusted. Continue to adjust submain and branch ducts to indicated airflows within specified tolerances. C. Measure air outlets and inlets without making adjustments. Measure terminal outlets using a direct -reading hood or outlet manufacturer's written instructions and calculating factors. TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Adjust air outlets and inlets for each space to indicated airflows within specified tolerances of indicated values. Make adjustments using branch volume dampers rather than extractors and the dampers at air terminals. 1. Adjust each outlet in same room or space to within specified tolerances of indicated quantities without generating noise levels above the limitations prescribed by the Contract Documents. 2. Adjust patterns of adjustable outlets for proper distribution without drafts. 3.6 PROCEDURES FOR VARIABLE -AIR -VOLUME SYSTEMS A. Compensating for Diversity: When the total airflow of all terminal units is more than the indicated airflow of the fan, place a selected number of terminal units at a minimum set -point airflow with the remainder at maximum -airflow condition until the total airflow of the terminal units equals the indicated airflow of the fan. Select the reduced -airflow terminal units so they are distributed evenly among the branch ducts. B. Pressure -Independent, Variable -Air -Volume Systems: After the fan systems have been adjusted, adjust the variable -air -volume systems as follows: 1. Set outdoor -air dampers at minimum, and set return- and exhaust -air dampers at a position that simulates full -cooling load. 2. Select the terminal unit that is most critical to the supply -fan airflow and static pressure. Measure static pressure. Adjust system static pressure so the entering static pressure for the critical terminal unit is not less than the sum of the terminal -unit manufacturer's recommended minimum inlet static pressure plus the static pressure needed to overcome terminal -unit discharge system losses. 3. Measure total system airflow. Adjust to within indicated airflow. 4. Set terminal units at maximum airflow and adjust controller or regulator to deliver the designed maximum airflow. Use terminal -unit manufacturer's written instructions to make this adjustment. When total airflow is correct, balance the air outlets downstream from terminal units the same as described for constant -volume air systems. 5. Set terminal units at minimum airflow and adjust controller or regulator to deliver the designed minimum airflow. Check air outlets for a proportional reduction in airflow the same as described for constant -volume air systems. a. If air outlets are out of balance at minimum airflow, report the condition but leave outlets balanced for maximum airflow. 6. Remeasure the return airflow to the fan while operating at maximum return airflow and minimum outdoor airflow. Adjust the fan and balance the return -air ducts and inlets the same as described for constant -volume air systems. 7. Measure static pressure at the most critical terminal unit and adjust the static -pressure controller at the main supply -air sensing station to ensure that adequate static pressure is maintained at the most critical unit. 8. Record final fan -performance data. C. Pressure -Dependent, Variable -Air -Volume Systems with Diversity: After the fan systems have been adjusted, adjust the variable -air -volume systems as follows: TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Set system at maximum indicated airflow by setting the required number of terminal units at minimum airflow. Select the reduced -airflow terminal units so they are distributed evenly among the branch ducts. 2. Adjust supply fan to maximum indicated airflow with the variable -airflow controller set at maximum airflow. 3. Set terminal units at full -airflow condition. 4. Adjust terminal units starting at the supply -fan end of the system and continuing progressively to the end of the system. Adjust inlet dampers of each terminal unit to indicated airflow. When total airflow is correct, balance the air outlets downstream from terminal units the same as described for constant -volume air systems. 5. Adjust terminal units for minimum airflow. 6. Measure static pressure at the sensor. 7. Measure the return airflow to the fan while operating at maximum return airflow and minimum outdoor airflow. Adjust the fan and balance the return -air ducts and inlets the same as described for constant -volume air systems. 3.7 GENERAL PROCEDURES FOR HYDRONIC SYSTEMS A. Prepare test reports with pertinent design data, and number in sequence starting at pump to end of system. Check the sum of branch -circuit flows against the approved pump flow rate. Correct variations that exceed plus or minus 5 percent. B. Prepare schematic diagrams of systems' "as -built" piping layouts C. Prepare hydronic systems for testing and balancing according to the following, in addition to the general preparation procedures specified above: 1. Open all manual valves for maximum flow. 2. Check flow -control valves for specified sequence of operation, and set at indicated flow. 3. Set differential -pressure control valves at the specified differential pressure. Do not set at fully closed position when pump is positive -displacement type unless several terminal valves are kept open. 4. Set system controls so automatic valves are wide open to district loop. 5. Check pump -motor load. If motor is overloaded, throttle main flow -balancing device so motor nameplate rating is not exceeded. 6. Check air vents for a forceful liquid flow exiting from vents when manually operated. 3.8 PROCEDURE FOR HYDRONIC SYSTEMS A. Systems installed with pressure independent control valves shall not require hydronic system balancing. Flow shall be verified and adjusted for the pressure independent valve assembly for field conditions using the pressure independent control valve manufacturer's documented procedure for 25% of the total installed product. Exact locations of tested product to be coordinated with the commissioning agent. 3.9 PROCEDURES FOR CHILLERS A. Balance water flow through each evaporator and condenser to within specified tolerances of indicated flow with all pumps operating. With only one chiller operating in a multiple chiller installation, do not exceed the flow for the maximum tube velocity recommended by the chiller manufacturer. Measure and record the following data with each chiller operating at design conditions: TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Evaporator -water entering and leaving temperatures, pressure drop, and water flow. 2. For water-cooled chillers, condenser -water entering and leaving temperatures, pressure drop, and water flow. 3. Evaporator and condenser refrigerant temperatures and pressures, using instruments furnished by chiller manufacturer. 4. Power factor if factory -installed instrumentation is furnished for measuring kilowatts. 5. Kilowatt input if factory -installed instrumentation is furnished for measuring kilowatts. 6. Capacity: Calculate in tons of cooling. 7. For air-cooled chillers, verify condenser -fan rotation and record fan and motor data including number of fans and entering- and leaving -air temperatures. 3.10 PROCEDURES FOR MOTORS A. Motors, 1/2 HP and Larger: Test at final balanced conditions and record the following data: 1. Manufacturer's name, model number, and serial number. 2. Motor horsepower rating. 3. Motor rpm. 4. Efficiency rating. 5. Nameplate and measured voltage, each phase. 6. Nameplate and measured amperage, each phase. 7. Starter thermal -protection -element rating. B. Motors Driven by Variable -Frequency Controllers: Test for proper operation at speeds varying from minimum to maximum. Test the manual bypass of the controller to prove proper operation. Record observations including name of controller manufacturer, model number, serial number, and nameplate data. 3.11 PROCEDURES FOR HEAT -TRANSFER COILS A. Measure, adjust, and record the following data for each water coil: 1. Entering- and leaving -water temperature. 2. Water flow rate. 3. Water pressure drop. 4. Dry-bulb temperature of entering and leaving air. 5. Wet -bulb temperature of entering and leaving air for cooling coils. 6. Airflow. 7. Air pressure drop. B. Measure, adjust, and record the following data for each electric heating coil: 1. Nameplate data. 2. Airflow. 3. Entering- and leaving -air temperature at full load. 4. Voltage and amperage input of each phase at full load and at each incremental stage. 5. Calculated kilowatt at full load. 6. Fuse or circuit -breaker rating for overload protection. 3.12 TOLERANCES A. Set HVAC system's air flow rates and water flow rates within the following tolerances: TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Supply, Return, and Exhaust Fans and Equipment with Fans: Plus or minus 10 percent. 2. Air Outlets and Inlets: Plus or minus 10 percent. 3. Cooling -Water Flow Rate: Plus or minus 10 percent. 3.13 REPORTING A. Initial Construction -Phase Report: Based on examination of the Contract Documents as specified in "Examination" Article, prepare a report on the adequacy of design for systems' balancing devices. Recommend changes and additions to systems' balancing devices to facilitate proper performance measuring and balancing. Recommend changes and additions to HVAC systems and general construction to allow access for performance measuring and balancing devices. B. Status Reports: Prepare monthly progress reports to describe completed procedures, procedures in progress, and scheduled procedures. Include a list of deficiencies and problems found in systems being tested and balanced. Prepare a separate report for each system and each building floor for systems serving multiple floors. 3.14 FINAL REPORT A. General: Prepare a certified written report; tabulate and divide the report into separate sections for tested systems and balanced systems. 1. Include a certification sheet at the front of the report's binder, signed and sealed by the certified testing and balancing engineer. 2. Include a list of instruments used for procedures, along with proof of calibration. B. Final Report Contents: In addition to certified field -report data, include the following: 1. Pump curves. 2. Fan curves. 3. Manufacturers' test data. 4. Field test reports prepared by system and equipment installers. 5. Other information relative to equipment performance; do not include Shop Drawings and product data. C. General Report Data: In addition to form titles and entries, include the following data: 1. Title page. 2. Name and address of the TAB contractor. 3. Project name. 4. Project location. 5. Architect's name and address. 6. Engineer's name and address. 7. Contractor's name and address. 8. Report date. 9. Signature of TAB supervisor who certifies the report. 10. Table of Contents with the total number of pages defined for each section of the report. Number each page in the report. 11. Summary of contents including the following: a. Indicated versus final performance. b. Notable characteristics of systems. TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS c. Description of system operation sequence if it varies from the Contract Documents. 12. Nomenclature sheets for each item of equipment. 13. Data for terminal units, including manufacturer's name, type, size, and fittings. 14. Notes to explain why certain final data in the body of reports vary from indicated values. 15. Test conditions for fans and pump performance forms including the following: a. Settings for outdoor-, return-, and exhaust -air dampers. b. Conditions of filters. C. Cooling coil, wet- and dry-bulb conditions. d. Face and bypass damper settings at coils. e. Fan drive settings including settings and percentage of maximum pitch diameter. f. Inlet vane settings for variable -air -volume systems. g. Settings for supply -air, static -pressure controller. h. Other system operating conditions that affect performance. D. System Diagrams: Include schematic layouts of air and hydronic distribution systems. Present each system with single -line diagram and include the following: 1. Quantities of outdoor, supply, return, and exhaust airflows. 2. Water and steam flow rates. 3. Duct, outlet, and inlet sizes. 4. Pipe and valve sizes and locations. 5. Terminal units. 6. Balancing stations. 7. Position of balancing devices. Air -Handling -Unit Test Reports: For air -handling units with coils, include the following: 1. Unit Data: a. Unit identification. b. Location. c. Make and type. d. Model number and unit size. e. Manufacturer's serial number. f. Unit arrangement and class. g. Discharge arrangement. h. Sheave make, size in inches, and bore. i. Center -to -center dimensions of sheave, and amount of adjustments in inches . j. Number, make, and size of belts. k. Number, type, and size of filters. 2. Motor Data: a. Motor make, and frame type and size. b. Horsepower and rpm. c. Volts, phase, and hertz. d. Full -load amperage and service factor. e. Sheave make, size in inches, and bore. f. Center -to -center dimensions of sheave, and amount of adjustments in inches. 3. Test Data (Indicated and Actual Values): TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 11 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Total air flow rate in cfm. b. Total system static pressure in inches wg. c. Fan rpm. d. Discharge static pressure in inches wg. e. Filter static -pressure differential in inches wg. f. Cooling -coil static -pressure differential in inches wg. g. Heating -coil static -pressure differential in inches wg. h. Outdoor airflow in cfm. Return airflow in cfm. j. Outdoor -air damper position. k. Return -air damper position. Vortex damper position. F. Apparatus -Coil Test Reports: 1. Coil Data: a. System identification. b. Location. c. Coil type. d. Number of rows. e. Fin spacing in fins per inch o.c. f. Make and model number. g. Face area in sq. ft. h. Tube size in NPS. i. Tube and fin materials. j. Circuiting arrangement. Test Data (Indicated and Actual Values): a. Air flow rate in cfm. b. Average face velocity in fpm. c. Air pressure drop in inches wg. d. Outdoor -air, wet- and dry-bulb temperatures in deg F. e. Return -air, wet- and dry-bulb temperatures in deg F. f. Entering -air, wet- and dry-bulb temperatures in deg F. g. Leaving -air, wet- and dry-bulb temperatures in deg F. h. Water flow rate in gpm. Water pressure differential in feet of head or psig. j. Entering -water temperature in deg F. k. Leaving -water temperature in deg F. G. Electric -Coil Test Reports: For electric furnaces, duct coils, and electric coils installed in central -station air -handling units, include the following: 1. Unit Data: a. System identification. b. Location. c. Coil identification. d. Capacity in Btu/h. e. Number of stages. f. Connected volts, phase, and hertz. g. Rated amperage. h. Air flow rate in cfm. i. Face area in sq. ft. TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 12 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS J. Minimum face velocity in fpm. 2. Test Data (Indicated and Actual Values): a. Heat output in Btu/h. b. Air flow rate in cfm. c. Air velocity in fpm. d. Entering -air temperature in deg F. e. Leaving -air temperature in deg F. f. Voltage at each connection. g. Amperage for each phase. H. Fan Test Reports: For supply, return, and exhaust fans, include the following: 1. Fan Data: a. System identification. b. Location. c. Make and type. d. Model number and size. e. Manufacturer's serial number. f. Arrangement and class. g. Sheave make, size in inches, and bore. h. Center -to -center dimensions of sheave, and amount of adjustments in inches. 2. Motor Data: a. Motor make, and frame type and size. b. Horsepower and rpm. c. Volts, phase, and hertz. d. Full -load amperage and service factor. e. Sheave make, size in inches, and bore. f. Center -to -center dimensions of sheave, and amount of adjustments in inches. g. Number, make, and size of belts. 3. Test Data (Indicated and Actual Values): a. Total airflow rate in cfm. b. Total system static pressure in inches wg. c. Fan rpm. d. Discharge static pressure in inches wg. e. Suction static pressure in inches wg. Round and Rectangular Duct Traverse Reports: Include a diagram with a grid representing the duct cross-section and record the following: Report Data: a. System and air -handling -unit number. b. Location and zone. c. Traverse air temperature in deg F. d. Duct static pressure in inches wg. e. Duct size in inches. f. Duct area in sq. ft. TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 13 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS g. Indicated air flow rate in cfm. h. Indicated velocity in fpm. Actual air flow rate in cfm. j. Actual average velocity in fpm. k. Barometric pressure in psig. J. Air -Terminal -Device Reports: 1. Unit Data: a. System and air -handling unit identification. b. Location and zone. c. Apparatus used for test. d. Area served. e. Make. f. Number from system diagram. g. Type and model number. h. Size. i. Effective area in sq. ft. 2. Test Data (Indicated and Actual Values): a. Air flow rate in cfm. b. Air velocity in fpm. c. Preliminary air flow rate as needed in cfm. d. Preliminary velocity as needed in fpm. e. Final air flow rate in cfm. f. Final velocity in fpm. g. Space temperature in deg F. K. Pump Test Reports: Calculate impeller size by plotting the shutoff head on pump curves and include the following: 1. Unit Data: a. Unit identification. b. Location. c. Service. d. Make and size. e. Model number and serial number. f. Water flow rate in gpm. g. Water pressure differential in feet of head or psig. h. Required net positive suction head in feet of head or psig. Pump rpm. j. Impeller diameter in inches. k. Motor make and frame size. I. Motor horsepower and rpm. m. Voltage at each connection. n. Amperage for each phase. o. Full -load amperage and service factor. p. Seal type. 2. Test Data (Indicated and Actual Values): TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 14 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS a. Static head in feet of head or psig. b. Pump shutoff pressure in feet of head or psig. c. Actual impeller size in inches. d. Full -open flow rate in gpm. e. Full -open pressure in feet of head or psig. f. Final discharge pressure in feet of head or psig. g. Final suction pressure in feet of head or psig. h. Final total pressure in feet of head or psig. i. Final water flow rate in gpm. j. Voltage at each connection. k. Amperage for each phase. L. Instrument Calibration Reports: 1. Report Data: a. Instrument type and make. b. Serial number. c. Application. d. Dates of use. e. Dates of calibration. 3.15 INSPECTIONS A. Initial Inspection: 1. After testing and balancing are complete, operate each system and randomly check measurements to verify that the system is operating according to the final test and balance readings documented in the final report. 2. Check the following for each system: a. Measure airflow of at least 10 percent of air outlets. b. Measure water flow of at least 5 percent of terminals. c. Measure room temperature at each thermostat/temperature sensor. Compare the reading to the set point. d. Verify that balancing devices are marked with final balance position. e. Note deviations from the Contract Documents in the final report. B. Final Inspection: 1. After initial inspection is complete and documentation by random checks verifies that testing and balancing are complete and accurately documented in the final report, request that a final inspection be made by Commissioning Authority. 2. The TAB contractor's test and balance engineer shall conduct the inspection in the presence of Commissioning Authority. 3. Commissioning Authority shall randomly select measurements, documented in the final report, to be rechecked. Rechecking shall be limited to either 10 percent of the total measurements recorded or the extent of measurements that can be accomplished in a normal 8 -hour business day. 4. If rechecks yield measurements that differ from the measurements documented in the final report by more than the tolerances allowed, the measurements shall be noted as "FAILED." TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 15 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 5. If the number of "FAILED" measurements is greater than 10 percent of the total measurements checked during the final inspection, the testing and balancing shall be considered incomplete and shall be rejected. C. TAB Work will be considered defective if it does not pass final inspections. If TAB Work fails, proceed as follows: 1. Recheck all measurements and make adjustments. Revise the final report and balancing device settings to include all changes; resubmit the final report and request a second final inspection. 2. If the second final inspection also fails, Owner may contract the services of another TAB contractor to complete TAB Work according to the Contract Documents and deduct the cost of the services from the original TAB contractor's final payment. D. Prepare test and inspection reports. 3.16 ADDITIONAL TESTS A. Within 90 days of completing TAB, perform additional TAB to verify that balanced conditions are being maintained throughout and to correct unusual conditions. B. Seasonal Periods: If initial TAB procedures were not performed during near -peak summer and winter conditions, perform additional TAB during near -peak summer and winter conditions. END OF SECTION 230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 16 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230700 - HVAC INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Insulation Materials: a. Cellular glass. b. Flexible elastomeric. c. Mineral fiber. 2. Adhesives. 3. Mastics. 4. Sealants. 5. Factory -applied jackets. 6. Field -applied jackets. 7. Tapes. B. Related Sections: 1. Division 21 Section "Fire -Suppression Systems Insulation." 2. Division 22 Section "Plumbing Insulation." 3. Division 23 Section "Metal Ducts" for duct liners. 1.3 SUBMITTALS A. Product Data: For each type of product indicated. Include thermal conductivity, water -vapor permeance thickness, and jackets (both factory- and field -applied if any). B. LEED Submittals: 1. Product Data for Credit EQ 4.1: For adhesives and sealants, documentation including printed statement of VOC content and chemical components. C. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work. 1. Detail application of protective shields, saddles, and inserts at hangers for each type of insulation and hanger. 2. Detail insulation application at elbows, fittings, dampers, specialties and flanges for each type of insulation. 3. Detail application of field -applied jackets. 4. Detail application at linkages of control devices. HVAC INSULATION 230700 - 1 INDIAN RIVER COUNTY. JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Material Test Reports: From a qualified testing agency acceptable to authorities having jurisdiction indicating, interpreting, and certifying test results for compliance of insulation materials, sealers, attachments, cements, and jackets, with requirements indicated. Include dates of tests and test methods employed. 1.4 QUALITY ASSURANCE A. Installer Qualifications: Skilled mechanics who have successfully completed an apprenticeship program or another craft training program certified by the Department of Labor, Bureau of Apprenticeship and Training. Fire -Test -Response Characteristics: Insulation and related materials shall have fire -test - response characteristics indicated, as determined by testing identical products per ASTM E 84, by a testing and inspecting agency acceptable to authorities having jurisdiction. Factory label insulation and jacket materials and adhesive, mastic, tapes, and cement material containers, with appropriate markings of applicable testing and inspecting agency. 1. Insulation Installed Indoors: Flame -spread index of 25 or less, and smoke -developed index of 50 or less. 2. Insulation Installed Outdoors: Flame -spread index of 75 or less, and smoke -developed index of 150 or less. 1.5 DELIVERY, STORAGE, AND HANDLING A. Packaging: Insulation material containers shall be marked by manufacturer with appropriate ASTM standard designation, type and grade, and maximum use temperature. 1.6 COORDINATION A. Coordinate size and location of supports, hangers, and insulation shields specified in Division 23 Section "Hangers and Supports for HVAC Piping and Equipment." B. Coordinate clearance requirements with piping Installer for piping insulation application, duct Installer for duct insulation application, and equipment Installer for equipment insulation application. Before preparing piping and ductwork Shop Drawings, establish and maintain clearance requirements for installation of insulation and field -applied jackets and finishes and for space required for maintenance. 1.7 SCHEDULING A. Schedule insulation application after pressure testing systems and, where required, after installing and testing heat tracing. Insulation application may begin on segments that have satisfactory test results. B. Complete installation and concealment of plastic materials as rapidly as possible in each area of construction. PART 2 - PRODUCTS HVAC INSULATION 230700-2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.1 INSULATION MATERIALS A. Comply with requirements in Part 3 schedule articles for where insulating materials shall be applied. B. Products shall not contain asbestos, lead, mercury, or mercury compounds. C. Products that come in contact with stainless steel shall have a leachable chloride content of less than 50 ppm when tested according to ASTM C 871. D. Insulation materials for use on austenitic stainless steel shall be qualified as acceptable according to ASTM C 795. E. Foam insulation materials shall not use CFC or HCFC blowing agents in the manufacturing process. F. Cellular Glass: Inorganic, incombustible, foamed or cellulated glass with annealed, rigid, hermetically sealed cells. Factory -applied jacket requirements are specified in "Factory -Applied Jackets" Article. 1. Products: Subject to compliance with requirements, provide the following: a. Pittsburgh Corning Corporation; Foamglas Super K. 2. Block Insulation: ASTM C 552, Type I. 3. Special -Shaped Insulation: ASTM C 552, Type III. 4. Board Insulation: ASTM C 552, Type IV. 5. Preformed Pipe Insulation with Factory -Applied ASJ: Comply with ASTM C 552, Type ll, Class 2. ASJ jacketing for all piping areas outside of mechanical rooms. 6. Preformed Pipe Insulation with Field -Applied PVC jacketing: Comply with ASTM C 552, Type II, Class 2. PVC jacketing for all piping areas inside mechanical rooms. 7. Factory fabricate shapes according to ASTM C 450 and ASTM C 585. G. Flexible Elastomeric: Closed -cell, sponge- or expanded -rubber materials. Comply with ASTM C 534, Type 1 for tubular materials and Type II for sheet materials. 1. Products: Subject to compliance with requirements, provide one of the following: a. Aeroflex USA Inc.; Aerocel. b. Armacell LLC; AP Armaflex. c. RBX Corporation; Insul-Sheet 1800 and Insul-Tube 180. Flexible Elastomeric Permitted Locations a. Pump housing. b. 4'-0" piping runout to AHU's. H. Mineral -Fiber Blanket Insulation: Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 553, Type 11 and ASTM C 1290, Type I. Factory -applied jacket requirements are specified in "Factory -Applied Jackets" Article. 1. Products: Subject to compliance with requirements, provide one of the following: a. CertainTeed Corp.; Duct Wrap. b. Johns Manville; Microlite. c. Knauf Insulation; Duct Wrap. d. Manson Insulation Inc.; Alley Wrap. e. Owens Corning; All -Service Duct Wrap. HVAC INSULATION 230700 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS Mineral -Fiber Board Insulation: Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 612, Type IA or Type IB. For duct and plenum applications, provide insulation. For equipment applications, provide insulation. Factory -applied jacket requirements are specified in "Factory -Applied Jackets" Article. Products: Subject to compliance with requirements, provide one of the following: a. CertainTeed Corp.; Commercial Board. b. Fibrex Insulations Inc.; FBX. c. Johns Manville; 800 Series Spin-Glas. d. Knauf Insulation; Insulation Board. e. Manson Insulation Inc.; AK Board. f. Owens Corning; Fiberglas 700 Series. 2.2 ADHESIVES A. Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated, unless otherwise indicated. Cellular -Glass Adhesive: Solvent -based resin adhesive, with a service temperature range of minus 75 to plus 300 deg F. 1. Products: Subject to compliance with requirements, provide one of the following: a. Childers Products, Division of ITW; CP -96. b. Foster Products Corporation, H. B. Fuller Company; 81-33. 2. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). C. Flexible Elastomeric Adhesive: Comply with MIL -A -24179A, Type II, Class I. 1. Products: Subject to compliance with requirements, provide one of the following: a. Aeroflex USA Inc.; Aeroseal. b. Armacell LCC; 520 Adhesive. c. Foster Products Corporation, H. B. Fuller Company; 85-75. d. RBX Corporation; Rubatex Contact Adhesive. 2. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). D. Mineral -Fiber Adhesive: Comply with MIL -A -3316C, Class 2, Grade A. 1. Products: Subject to compliance with requirements, provide one of the following: a. Childers Products, Division of ITW; CP -82. b. Foster Products Corporation, H. B. Fuller Company; 85-20. c. ITW TACC, Division of Illinois Tool Works; S-90/80. d. Marathon Industries, Inc.; 225. e. Mon -Eco Industries, Inc.; 22-25. 2. For indoor applications, use adhesive that has a VOC content of 80 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). HVAC INSULATION 230700 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS E. ASJ Adhesive, and FSK Jacket Adhesive: Comply with MIL -A -3316C, Class 2, Grade A for bonding insulation jacket lap seams and joints. 1. Products: Subject to compliance with requirements, provide one of the following: a. Childers Products, Division of ITW; CP -82. b. Foster Products Corporation, H. B. Fuller Company; 85-20. c. ITW TACC, Division of Illinois Tool Works; S-90/80. d. Marathon Industries, Inc.; 225. e. Mon -Eco Industries, Inc.; 22-25. 2. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). F. PVC Jacket Adhesive: Compatible with PVC jacket. 1. Products: Subject to compliance with requirements, provide one of the following: a. Dow Chemical Company (The); 739, Dow Silicone. b. Johns -Manville; Zeston Perma-Weld, CEEL-TITE Solvent Welding Adhesive. c. P.I.C. Plastics, Inc.; Welding Adhesive. d. Speedline Corporation; Speedline Vinyl Adhesive. 2. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 2.3 MASTICS A. Materials shall be compatible with insulation materials, jackets, and substrates; comply with MIL -C -19565C, Type II. Vapor -Barrier Mastic: Water based; suitable for indoor and outdoor use on below ambient services. C. For indoor applications, use mastic that has a voc content of 50 G/L or less when calculated according to 40 CFR 59, subpart D (EPA Method 24). 1. Products: Subject to compliance with requirements, provide one of the following: a. Childers Products, Division of ITW; CP -35. b. Foster Products Corporation, H. B. Fuller Company; 30-90. c. ITW TACC, Division of Illinois Tool Works; CB -50. d. Marathon Industries, Inc.; 590. e. Mon -Eco Industries, Inc.; 55-40. f. Vimasco Corporation; 749. 2. Water -Vapor Permeance: ASTM E 96, Procedure B, 0.013 perm at 43 -mil dry film thickness. 3. Service Temperature Range: Minus 20 to plus 180 deg F . 4. Solids Content: ASTM D 1644, 59 percent by volume and 71 percent by weight. 5. Color: White. HVAC INSULATION 230700 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.4 SEALANTS A. Joint Sealants: 1. Joint Sealants for Cellular -Glass Products: Subject to compliance with requirements,: a. Childers Products, Division of ITW; CP -76. b. Foster Products Corporation, H. B. Fuller Company; 30-45. c. Pittsburgh Corning Corporation; Pittseal 444. 2. Materials shall be compatible with insulation materials, jackets, and substrates. 3. Permanently flexible, elastomeric sealant. 4. Service Temperature Range: Minus 100 to plus 300 deg F. 5. Color: White or gray. 6. For indoor applications, use sealants that have a VOC content of 250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). B. ASJ Flashing Sealants, and Vinyl, PVDC, and PVC Jacket Flashing Sealants: 1. Products: Subject to compliance with requirements, provide the following: a. Childers Products, Division of ITW; CP -76. 2. Materials shall be compatible with insulation materials, jackets, and substrates. 3. Fire- and water-resistant, flexible, elastomeric sealant. 4. Service Temperature Range: Minus 40 to plus 250 deg F. 5. Color: White. 6. For indoor applications, use sealants that have a VOC content of 250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 2.5 FACTORY -APPLIED JACKETS A. Insulation system schedules indicate factory -applied jackets on various applications. When factory -applied jackets are indicated, comply with the following: ASJ: White, kraft -paper, fiberglass -reinforced scrim with aluminum -foil backing; complying with ASTM C 1136, Type I. 2.6 FIELD -APPLIED JACKETS A. Field -applied jackets shall comply with ASTM C 921, Type I, unless otherwise indicated. B. PVC Jacket: High -impact -resistant, UV -resistant PVC complying with ASTM D 1784, Class 16354-C; thickness as scheduled; roll stock ready for shop or field cutting and forming. Thickness is indicated in field -applied jacket schedules. 1. Products: Subject to compliance with requirements, provide one of the following: a. Johns Manville; Zeston. b. P.I.C. Plastics, Inc.; FG Series. c. Proto PVC Corporation; LoSmoke. HVAC INSULATION 230700-6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS d. Speedline Corporation; SmokeSafe. 2. Adhesive: As recommended by jacket material manufacturer. 3. Color: White. 4. Factory -fabricated fitting covers to match jacket if available; otherwise, field fabricate. Shapes: 45- and 90 -degree, short- and long -radius elbows, tees, valves, flanges, unions, reducers, end caps, soil -pipe hubs, traps, mechanical joints, and P -trap and supply covers for lavatories. 5. Factory -fabricated tank heads and tank side panels. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions for compliance with requirements for installation and other conditions affecting performance of insulation application. 1. Verify that systems and equipment to be insulated have been tested and are free of defects. 2. Verify that surfaces to be insulated are clean and dry. 3. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 PREPARATION A. Surface Preparation: Clean and dry surfaces to receive insulation. adversely affect insulation application. Surface Preparation: Clean and prepare surfaces to be insulated. corrosion coating to insulated surfaces as follows: Remove materials that will Before insulating, apply a Carbon Steel: Coat carbon steel operating at a service temperature between 32 and 300 deg F with an epoxy coating. Consult coating manufacturer for appropriate coating materials and application methods for operating temperature range. C. Mix insulating cements with clean potable water; if insulating cements are to be in contact with stainless-steel surfaces, use demineralized water. 3.3 GENERAL INSTALLATION REQUIREMENTS A. Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces; free of voids throughout the length of equipment, ducts and fittings, and piping including fittings, valves, and specialties. B. Install insulation materials, forms, vapor barriers or retarders, jackets, and thicknesses required for each item of equipment, duct system, and pipe system as specified in insulation system schedules. HVAC INSULATION 230700-7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Install accessories compatible with insulation materials and suitable for the service. Install accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or dry state. D. Install insulation with longitudinal seams at top and bottom of horizontal runs. E. Install multiple layers of insulation with longitudinal and end seams staggered. F. Do not weld brackets, clips, or other attachment devices to piping, fittings, and specialties. G. Keep insulation materials dry during application and finishing. H. Install insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive recommended by insulation material manufacturer. Install insulation with least number of joints practical. J. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at hangers, supports, anchors, and other projections with vapor -barrier mastic. 1. Install insulation continuously through hangers and around anchor attachments. 2. For insulation application where vapor barriers are indicated, extend insulation on anchor legs from point of attachment to supported item to point of attachment to structure. Taper and seal ends at attachment to structure with vapor -barrier mastic. 3. Install insert materials and install insulation to tightly join the insert. Seal insulation to insulation inserts with adhesive or sealing compound recommended by insulation material manufacturer. 4. Cover inserts with jacket material matching adjacent pipe insulation. Install shields over jacket, arranged to protect jacket from tear or puncture by hanger, support, and shield. K. Apply adhesives, mastics, and sealants at manufacturer's recommended coverage rate and wet and dry film thicknesses. L. Install insulation with factory -applied jackets as follows: 1. Draw jacket tight and smooth. 2. Cover circumferential joints with 3 -inch- wide strips, of same material as insulation jacket. Secure strips with adhesive and outward clinching staples along both edges of strip, spaced 4 inches o.c. 3. Overlap jacket longitudinal seams at least 1-1/2 inches . Install insulation with longitudinal seams at bottom of pipe. Clean and dry surface to receive self-sealing lap. Staple laps with outward clinching staples along edge at 2 inches o.c. a. For below ambient services, apply vapor -barrier mastic over staples. 4. Cover joints and seams with tape as recommended by insulation material manufacturer to maintain vapor seal. 5. Where vapor barriers are indicated, apply vapor -barrier mastic on seams and joints and at ends adjacent to duct and pipe flanges and fittings. M. Cut insulation in a manner to avoid compressing insulation more than 75 percent of its nominal thickness. N. Finish installation with systems at operating conditions. Repair joint separations and cracking due to thermal movement. HVAC INSULATION 230700 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS O. Repair damaged insulation facings by applying same facing material over damaged areas. Extend patches at least 4 inches beyond damaged areas. Adhere, staple, and seal patches similar to butt joints. P. For above ambient services, do not install insulation to the following: 1. Vibration -control devices. 2. Testing agency labels and stamps. 3. Nameplates and data plates. 4. Manholes. 5. Handholes. 6. Cleanouts. 3.4 PENETRATIONS A. Insulation Installation at Underground Exterior Wall Penetrations: Terminate insulation flush with sleeve seal. Seal terminations with flashing sealant. Insulation Installation at Fire -Rated Wall and Partition Penetrations: Install insulation continuously through penetrations of fire -rated walls and partitions. Terminate insulation at fire damper sleeves for fire -rated wall and partition penetrations. Externally insulate damper sleeves to match adjacent insulation and overlap duct insulation at least 2 inches. 1. Comply with requirements in Division 07 Section "Penetration Firestopping" for firestopping and fire -resistive joint sealers. 3.5 EQUIPMENT, TANK, AND VESSEL INSULATION INSTALLATION A. Flexible Elastomeric Thermal Insulation Installation for Tanks and Vessels: Install insulation over entire surface of tanks and vessels. Apply 100 percent coverage of adhesive to surface with manufacturer's recommended adhesive. Seal longitudinal seams and end joints. B. Insulation Installation on Pumps: 1. Fabricate metal boxes lined with insulation. Fit boxes around pumps and coincide box joints with splits in pump casings. Fabricate joints with outward bolted flanges. Bolt flanges on 6 -inch centers, starting at corners. Install 3/8 -inch- diameter fasteners with wing nuts. Alternatively, secure the box sections together using a latching mechanism. 2. For below ambient services, install a vapor barrier at seams, joints, and penetrations. Seal between flanges with replaceable gasket material to form a vapor barrier. 3.6 GENERAL PIPE INSULATION INSTALLATION A. Requirements in this article generally apply to all insulation materials except where more specific requirements are specified in various pipe insulation material installation articles. B. Insulation Installation on Fittings, Valves, Strainers, Flanges, and Unions: HVAC INSULATION 230700 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. Install insulation over fittings, valves, strainers, flanges, unions, and other specialties with continuous thermal and vapor -retarder integrity, unless otherwise indicated. 2. Insulate pipe elbows using preformed fitting insulation or mitered fittings made from same material and density as adjacent pipe insulation. Each piece shall be butted tightly against adjoining piece and bonded with adhesive. Fill joints, seams, voids, and irregular surfaces with insulating cement finished to a smooth, hard, and uniform contour that is uniform with adjoining pipe insulation. 3. Insulate tee fittings with preformed fitting insulation or sectional pipe insulation of same material and thickness as used for adjacent pipe. Cut sectional pipe insulation to fit. Butt each section closely to the next and hold in place with tie wire. Bond pieces with adhesive. 4. Insulate valves using preformed fitting insulation or sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. For valves, insulate up to and including the bonnets, valve stuffing -box studs, bolts, and nuts. Fill joints, seams, and irregular surfaces with insulating cement. 5. Insulate strainers using preformed fitting insulation or sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. Fill joints, seams, and irregular surfaces with insulating cement. Insulate strainers so strainer basket flange or plug can be easily removed and replaced without damaging the insulation and jacket. Provide a removable reusable insulation cover. For below ambient services, provide a design that maintains vapor barrier. 6. Insulate flanges and unions using a section of oversized preformed pipe insulation. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. 7. Cover segmented insulated surfaces with a layer of finishing cement and coat with a mastic. Install vapor -barrier mastic for below ambient services and a breather mastic for above ambient services. Reinforce the mastic with fabric -reinforcing mesh. Trowel the mastic to a smooth and well -shaped contour. S. Label the outside insulation jacket of each union with the word "UNION." Match size and color of pipe labels. C. Insulate instrument connections for thermometers, pressure gages, pressure temperature taps, test connections, flow meters, sensors, switches, and transmitters on insulated pipes, vessels, and equipment. Shape insulation at these connections by tapering it to and around the connection with insulating cement and finish with finishing cement, mastic, and flashing sealant. D. Install removable insulation covers at locations indicated. Installation shall conform to the following: 1. Make removable flange and union insulation from sectional pipe insulation of same thickness as that on adjoining pipe. Install same insulation jacket as adjoining pipe insulation. 2. When flange and union covers are made from sectional pipe insulation, extend insulation from flanges or union long at least two times the insulation thickness over adjacent pipe insulation on each side of flange or union. Secure flange cover in place with stainless- steel or aluminum bands. Select band material compatible with insulation and jacket. 3. Construct removable valve insulation covers in same manner as for flanges except divide the two-part section on the vertical center line of valve body. 4. When covers are made from block insulation, make two halves, each consisting of mitered blocks wired to stainless-steel fabric. Secure this wire frame, with its attached insulation, to flanges with tie wire. Extend insulation at least 2 inches over adjacent pipe insulation on each side of valve. Fill space between flange or union cover and pipe HVAC INSULATION 230700 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS insulation with insulating cement. Finish cover assembly with insulating cement applied in two coats. After first coat is dry, apply and trowel second coat to a smooth finish. 5. Unless a PVC jacket is indicated in field -applied jacket schedules, finish exposed surfaces with a metal jacket. 3.7 CELLULAR -GLASS INSULATION INSTALLATION A. Insulation Installation on Straight Pipes and Tubes: 1. Secure each layer of insulation to pipe with wire or bands and tighten bands without deforming insulation materials. 2. Where vapor barriers are indicated, seal longitudinal seams, end joints, and protrusions with vapor -barrier mastic and joint sealant. 3. For insulation with factory -applied jackets on above ambient services, secure laps with outward clinched staples at 6 inches o.c. 4. For insulation with factory -applied jackets on below ambient services, do not staple longitudinal tabs but secure tabs with additional adhesive as recommended by insulation material manufacturer and seal with vapor -barrier mastic and flashing sealant. B. Insulation Installation on Pipe Flanges: 1. Install preformed pipe insulation to outer diameter of pipe flange. 2. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness of pipe insulation. 3. Fill voids between inner circumference of flange insulation and outer circumference of adjacent straight pipe segments with cut sections of cellular -glass block insulation of same thickness as pipe insulation. 4. Install jacket material with manufacturer's recommended adhesive, overlap seams at least 1 inch, and seal joints with flashing sealant. C. Insulation Installation on Pipe Fittings and Elbows: 1. Install preformed sections of same material as straight segments of pipe insulation when available. Secure according to manufacturer's written instructions. 2. When preformed sections of insulation are not available, install mitered sections of cellular -glass insulation. Secure insulation materials with wire or bands. D. Insulation Installation on Valves and Pipe Specialties: 1. Install preformed sections of cellular -glass insulation to valve body. 2. Arrange insulation to permit access to packing and to allow valve operation without disturbing insulation. 3. Install insulation to flanges as specified for flange insulation application. 3.8 FLEXIBLE ELASTOMERIC INSULATION INSTALLATION A. Seal longitudinal seams and end joints with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. B. Insulation Installation on Pipe Flanges: Install pipe insulation to outer diameter of pipe flange. HVAC INSULATION 230700 - 11 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness of pipe insulation. 3. Fill voids between inner circumference of flange insulation and outer circumference of adjacent straight pipe segments with cut sections of sheet insulation of same thickness as pipe insulation. 4. Secure insulation to flanges and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated, C. Insulation Installation on Pipe Fittings and Elbows: 1. Install mitered sections of pipe insulation. 2. Secure insulation materials and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. D. Insulation Installation on Valves and Pipe Specialties: 1. Install preformed valve covers manufactured of same material as pipe insulation when available. 2. When preformed valve covers are not available, install cut sections of pipe and sheet insulation to valve body. Arrange insulation to permit access to packing and to allow valve operation without disturbing insulation. 3. Install insulation to flanges as specified for flange insulation application. 4. Secure insulation to valves and specialties and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. 3.9 MINERAL -FIBER INSULATION INSTALLATION A. Blanket Insulation Installation on Ducts and Plenums: Secure with adhesive and insulation pins. 1. Apply adhesives according to manufacturer's recommended coverage rates per unit area, for 100 percent coverage of duct and plenum surfaces. 2. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and transitions. 3. Install either capacitor -discharge -weld pins and speed washers or cupped -head, capacitor -discharge -weld pins on sides and bottom of horizontal ducts and sides of vertical ducts as follows: a. On duct sides with dimensions 18 inches and smaller, place pins along longitudinal centerline of duct. Space 3 inches maximum from insulation end joints, and 16 inches o.c. b. On duct sides with dimensions larger than 18 inches , place pins 16 inches o.c. each way, and 3 inches maximum from insulation joints. Install additional pins to hold insulation tightly against surface at cross bracing. c. Pins may be omitted from top surface of horizontal, rectangular ducts and plenums. d. Do not overcompress insulation during installation. e. Impale insulation over pins and attach speed washers. f. Cut excess portion of pins extending beyond speed washers or bend parallel with insulation surface. Cover exposed pins and washers with tape matching insulation facing. 4. For ducts and plenums with surface temperatures below ambient, install a continuous unbroken vapor barrier. Create a facing lap for longitudinal seams and end joints with HVAC INSULATION 230700 - 12 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS insulation by removing 2 inches from 1 edge and 1 end of insulation segment. Secure laps to adjacent insulation section with 1/2 -inch outward -clinching staples, 1 inch o.c. Install vapor barrier consisting of factory- or field -applied jacket, adhesive, vapor -barrier mastic, and sealant at joints, seams, and protrusions. a. Repair punctures, tears, and penetrations with tape or mastic to maintain vapor - barrier seal. b. Install vapor stops for ductwork and plenums operating below 50 deg F at 18 -foot intervals. Vapor stops shall consist of vapor -barrier mastic applied in a Z-shaped pattern over insulation face, along butt end of insulation, and over the surface. Cover insulation face and surface to be insulated a width equal to 2 times the insulation thickness but not less than 3 inches. 5. Overlap unfaced blankets a minimum of 2 inches on longitudinal seams and end joints. At end joints, secure with steel bands spaced a maximum of 18 inches o.c. 6. Install insulation on rectangular duct elbows and transitions with a full insulation section for each surface. Install insulation on round and flat -oval duct elbows with individually mitered gores cut to fit the elbow. 7. Insulate duct stiffeners, hangers, and flanges that protrude beyond insulation surface with 6 -inch- wide strips of same material used to insulate duct. Secure on alternating sides of stiffener, hanger, and flange with pins spaced 6 inches o.c. B. Board Insulation Installation on Ducts and Plenums: Secure with adhesive and insulation pins. 1. Apply adhesives according to manufacturer's recommended coverage rates per unit area, for 100 percent coverage of duct and plenum surfaces. 2. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and transitions. 3. Install either capacitor -discharge -weld pins and speed washers or cupped -head, capacitor -discharge -weld pins on sides and bottom of horizontal ducts and sides of vertical ducts as follows: a. On duct sides with dimensions 18 inches and smaller, place pins along longitudinal centerline of duct. Space 3 inches maximum from insulation end joints, and 16 inches o.c. b. On duct sides with dimensions larger than 18 inches, space pins 16 inches o.c. each way, and 3 inches maximum from insulation joints. Install additional pins to hold insulation tightly against surface at cross bracing. c. Pins may be omitted from top surface of horizontal, rectangular ducts and plenums. d. Do not overcompress insulation during installation. e. Cut excess portion of pins extending beyond speed washers or bend parallel with insulation surface. Cover exposed pins and washers with tape matching insulation facing. 4. For ducts and plenums with surface temperatures below ambient, install a continuous unbroken vapor barrier. Create a facing lap for longitudinal seams and end joints with insulation by removing 2 inches from 1 edge and 1 end of insulation segment. Secure laps to adjacent insulation section with 1/2 -inch outward -clinching staples, 1 inch o.c. Install vapor barrier consisting of factory- or field -applied jacket, adhesive, vapor -barrier mastic, and sealant at joints, seams, and protrusions. a. Repair punctures, tears, and penetrations with tape or mastic to maintain vapor - barrier seal. b. Install vapor stops for ductwork and plenums operating below 50 deg F at 18 -foot intervals. Vapor stops shall consist of vapor -barrier mastic applied in a Z-shaped HVAC INSULATION 230700 - 13 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS pattern over insulation face, along butt end of insulation, and over the surface. Cover insulation face and surface to be insulated a width equal to 2 times the insulation thickness but not less than 3 inches. 5. Install insulation on rectangular duct elbows and transitions with a full insulation section for each surface. Groove and score insulation to fit as closely as possible to outside and inside radius of elbows. Install insulation on round and flat -oval duct elbows with individually mitered gores cut to fit the elbow. 6. Insulate duct stiffeners, hangers, and flanges that protrude beyond insulation surface with 6 -inch- wide strips of same material used to insulate duct. Secure on alternating sides of stiffener, hanger, and flange with pins spaced 6 inches o.c. 3.10 FIELD -APPLIED JACKET INSTALLATION A. Where PVC jackets are indicated, install with 1 -inch overlap at longitudinal seams and end joints; for horizontal applications, install with longitudinal seams along top and bottom of tanks and vessels. Seal with manufacturer's recommended adhesive. 1. Apply two continuous beads of adhesive to seams and joints, one bead under lap and the finish bead along seam and joint edge. 3.11 FINISHES A. Duct, Equipment, and Pipe Insulation with ASJ, Glass -Cloth, or Other Paintable Jacket Material: Paint jacket with paint system identified below and as specified in Division 09 painting Sections. Flat Acrylic Finish: Two finish coats over a primer that is compatible with jacket material and finish coat paint. Add fungicidal agent to render fabric mildew proof. a. Finish Coat Material: Interior, flat, latex -emulsion size. B. Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats of insulation manufacturer's recommended protective coating. C. Color: Final color as selected by Architect. Vary first and second coats to allow visual inspection of the completed Work. 3.12 FIELD QUALITY CONTROL A. Testing Agency: Owner will engage a qualified testing agency to perform tests and inspections. B. Tests and Inspections: 1. Inspect ductwork, randomly selected by Architect, by removing field -applied jacket and insulation in layers in reverse order of their installation. Extent of inspection shall be limited to three location(s) for each duct system defined in the "Duct Insulation Schedule, General" Article. 2. Inspect field -insulated equipment, randomly selected by Architect, by removing field - applied jacket and insulation in layers in reverse order of their installation. Extent of inspection shall be limited to three location(s) for each type of equipment defined in the "Equipment Insulation Schedule" Article. For large equipment, remove only a portion adequate to determine compliance. HVAC INSULATION 230700-14 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 3. Inspect pipe, fittings, strainers, and valves, randomly selected by Architect, by removing field -applied jacket and insulation in layers in reverse order of their installation. Extent of inspection shall be limited to three locations of straight pipe, three locations of threaded fittings, three locations of welded fittings, two locations of threaded strainers, two locations of welded strainers, three locations of threaded valves, and three locations of flanged valves for each pipe service defined in the "Piping Insulation Schedule, General" Article. C. All insulation applications will be considered defective Work if sample inspection reveals noncompliance with requirements. 3.13 DUCT INSULATION SCHEDULE, GENERAL A. Plenums and Ducts Requiring Insulation: 1. Indoor, concealed supply and outdoor air. 2. Indoor, exposed supply and outdoor air. 3. Indoor, concealed return located in nonconditioned space. 4. Indoor, exposed return located in nonconditioned space. 5. Indoor, concealed exhaust between isolation damper and penetration of building exterior. 6. Indoor, exposed exhaust between isolation damper and penetration of building exterior. Items Not Insulated: 1. Metal ducts with duct liner of sufficient thickness to comply with energy code and ASHRAE/IESNA 90.1. 2. Factory -insulated flexible ducts. 3. Flexible connectors. 4. Factory -insulated access panels and doors. 3.14 INDOOR DUCT AND PLENUM INSULATION SCHEDULE A. Concealed, round and flat -oval, supply -air duct insulation shall be the following: 1. Mineral -Fiber Blanket: 1-1/2 inches thick and 0.75-Ib/cu. ft. nominal density. B. Concealed, round and flat -oval, return -air duct insulation shall be the following: 1. Mineral -Fiber Blanket: 1-1/2 inches thick and 0.75-Ib/cu. ft. nominal density. C. Concealed, rectangular, supply -air duct insulation shall be the following: 1. Mineral -Fiber Blanket: 1-1/2 inches thick and 0.75-Ib/cu. ft. nominal density. D. Concealed, rectangular, return -air duct insulation shall be the following: 1. Mineral -Fiber Blanket: 1-1/2 inches thick and 0.75-lb/cu. ft. nominal density. E. Concealed, rectangular, supply/return-air duct insulation inside mechanical rooms shall be the following: 1. Mineral -Fiber Board: 1-1/2 inches thick and 2-Ib/cu. ft. nominal density. HVAC INSULATION 230700 - 15 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS F. Concealed, return -air plenum insulation shall be the following: 1. Mineral -Fiber Blanket: 1-1/2 inches thick and 0.75-Ib/cu. ft. nominal density. 3.15 EQUIPMENT INSULATION SCHEDULE A. Insulation materials and thicknesses are identified below. If more than one material is listed for a type of equipment, selection from materials listed is Contractor's option. B. Insulate indoor equipment in paragraphs below that is not factory insulated. C. Chilled -water air -separator insulation shall be the following: 1. Flexible Elastomeric: 1 inch thick. 3.16 PIPING INSULATION SCHEDULE, GENERAL A. Acceptable preformed pipe and tubular insulation materials and thicknesses are identified for each piping system and pipe size range. If more than one material is listed for a piping system, selection from materials listed is Contractor's option. 3.17 INDOOR PIPING INSULATION SCHEDULE A. Chilled Water, above 40 Deg F : 1. NPS 6 and Smaller: Insulation shall be one of the following: a. Cellular Glass: 1-1/2 inches thick. b. Flexible Elastomeric: 1 inch thick (Limited to 4 foot run -outs to cooling coils). 3.18 INDOOR, FIELD -APPLIED JACKET SCHEDULE A. Install jacket over insulation material. For insulation with factory -applied jacket, install the field - applied jacket over the factory -applied jacket. B. If more than one material is listed, selection from materials listed is Contractor's option. C. Piping, Mechanical Rooms: 1. PVC: 20 mils thick. 3.20 OUTDOOR, UNDERGROUND CHILLED WATER PIPING. A. All outdoor chilled water piping shall be pre -insulated metal piping with welded joints. Pre - insulated piping manufacturer shall provide shop drawings routing, thrust blocks, expansion loops, etc. for engineer's review. END OF SECTION 230700 HVAC INSULATION 230700-16 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230900 - INSTRUMENTATION AND CONTROL FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes control equipment for HVAC systems and components, including control components for terminal heating and cooling units not supplied with factory -wired controls. B. Related Sections include the following: 1. Division 23 Section "Meters and Gages for HVAC Piping" for measuring equipment that relates to this Section. 2. Division 23 Section "Sequence of Operations for HVAC Controls" for requirements that relate to this Section. 1.3 DEFINITIONS A. DDC: Direct digital control. B. I/O: Input/output. C. MS/TP: Master slave/token passing. D. PC: Personal computer. E. PID: Proportional plus integral plus derivative. 1.4 SYSTEM PERFORMANCE A. Comply with the following performance requirements: 1. Graphic Display: Display graphic with minimum 20 dynamic points with current data within 10 seconds. 2. Graphic Refresh: Update graphic with minimum 20 dynamic points with current data within 8 seconds. 3. Object Command: Reaction time of less than two seconds between operator command of a binary object and device reaction. 4. Object Scan: Transmit change of state and change of analog values to control units or workstation within six seconds. 5. Alarm Response Time: Annunciate alarm at workstation within 45 seconds. Multiple workstations must receive alarms within five seconds of each other. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 1 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 6. Program Execution Frequency: Run capability of applications as often as five seconds, but selected consistent with mechanical process under control. 7. Performance: Programmable controllers shall execute DDC PID control loops, and scan and update process values and outputs at least once per second. 8. Reporting Accuracy and Stability of Control: Report values and maintain measured variables within tolerances as follows: a. Water Temperature: Plus or minus 1 deg F. b. Water Flow: Plus or minus 2 percent of full scale. c. Water Pressure: Plus or minus 5 percent of full scale. d. Space Temperature: Plus or minus 1 deg F. e. Ducted Air Temperature: Plus or minus 1 deg F. f. Outside Air Temperature: Plus or minus 2 deg F. g. Dew Point Temperature: Plus or minus 3 deg F. h. Temperature Differential: Plus or minus 0.25 deg F. i. Relative Humidity: Plus or minus 2 percent. j. Airflow (Pressurized Spaces): Plus or minus 3 percent of full scale. k. Airflow (Measuring Stations): Plus or minus 5 percent of full scale. I. Airflow (Terminal): Plus or minus 10 percent of full scale. m. Air Pressure (Space): Plus or minus 0.01 -inch wg. n. Air Pressure (Ducts): Plus or minus 0.1 -inch wg. o. Electrical: Plus or minus 5 percent of reading. 1.5 SEQUENCE OF OPERATION See Control Diagrams on Design Documents for Sequences of Operations. 1.6 SUBMITTALS A. Product Data: Include manufacturer's technical literature for each control device. Indicate dimensions, capacities, performance characteristics, electrical characteristics, finishes for materials, and installation and startup instructions for each type of product indicated. 1. DDC System Hardware: Bill of materials of equipment indicating quantity, manufacturer, and model number. Include technical data for operator workstation equipment, interface equipment, control units, transducers/transmitters, sensors, actuators, valves, relays/switches, control panels, and operator interface equipment. 2. Control System Software: Include technical data for operating system software, operator interface, color graphics, and other third -party applications. 3. Controlled Systems: Instrumentation list with element name, type of device, manufacturer, model number, and product data. Include written description of sequence of operation including schematic diagram. B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. 1. Bill of materials of equipment indicating quantity, manufacturer, and model number. 2. Schematic flow diagrams showing fans, pumps, coils, dampers, valves, and control devices. 3. Wiring Diagrams: Power, signal, and control wiring. 4. Details of control panel faces, including controls, instruments, and labeling. 5. Written description of sequence of operation. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 2 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 6. Schedule of dampers including size, leakage, and flow characteristics. 7. Schedule of valves including flow characteristics. 8. DDC System Hardware: a. Wiring diagrams for control units with termination numbers. b. Schematic diagrams and floor plans for field sensors and control hardware. c. Schematic diagrams for control, communication, and power wiring, showing trunk data conductors and wiring between operator workstation and control unit locations. 9. Control System Software: List of color graphics indicating monitored systems, data (connected and calculated) point addresses, output schedule, and operator notations. 10. Controlled Systems: a. Schematic diagrams of each controlled system with control points labeled and control elements graphically shown, with wiring. b. Scaled drawings showing mounting, routing, and wiring of elements including bases and special construction. c. Written description of sequence of operation including schematic diagram. d. Points list. C. Data Communications Protocol Certificates: Certify that each proposed DDC system component complies with ASHRAE 135. D. Software and Firmware Operational Documentation: Include the following: 1. Software operating and upgrade manuals. 2. Program Software Backup: On a magnetic media or compact disc, complete with data files. 3. Device address list. 4. Printout of software application and graphic screens. 5. Software license required by and installed for DDC workstations and control systems. E. Field quality -control test reports. F. Operation and Maintenance Data: For HVAC instrumentation and control system to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 01 Section "Operation and Maintenance Data," include the following: 1. Maintenance instructions and lists of spare parts for each type of control device and compressed -air station. 2. Interconnection wiring diagrams with identified and numbered system components and devices. 3. Keyboard illustrations and step-by-step procedures indexed for each operator function. 4. Inspection period, cleaning methods, cleaning materials recommended, and calibration tolerances. 5. Calibration records and list of set points. 1.7 QUALITY ASSURANCE A. Installer Qualifications: Automatic control system manufacturer's authorized representative who is trained and approved for installation of system components required for this Project. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 3 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. C. Comply with ASHRAE 135 for DDC system components. 1.8 DELIVERY, STORAGE, AND HANDLING A. Factory -Mounted Components: Where control devices specified in this Section are indicated to be factory mounted on equipment, arrange for shipping of control devices to equipment manufacturer. B. System Software: Update to latest version of software at Project completion. 1.9 COORDINATION A. Coordinate location of thermostats, humidistats, and other exposed control sensors with plans and room details before installation. B. Coordinate equipment with Division 27 Section "Clock Systems" to achieve compatibility with equipment that interfaces with that system. C. Coordinate equipment with Division 16 Section "Network Lighting Controls" to achieve compatibility with equipment that interfaces with that system. D. Coordinate supply of conditioned electrical branch circuits for control units and operator workstation. E. Coordinate equipment with Division 16 Section "Electrical Power Monitoring and Control" to achieve compatibility of communication interfaces. F. Coordinate equipment with Division 16 Section "Panelboards" to achieve compatibility with starter coils and annunciation devices. G. Coordinate size and location of concrete bases. Cast anchor -bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in Division 03 Section "Cast -in -Place Concrete." 1.10 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. Replacement Materials: One replacement diaphragm or relay mechanism for each unique valve motor. PART 2 - PRODUCTS INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 4 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. 2.2 CONTROL SYSTEM A. Manufacturers: 1. Johnson Controls 2. Delta Controls 3. Trane; Worldwide Applied Systems Group 4. Schneider Electric B. Control system shall consist of sensors, indicators, actuators, final control elements, interface equipment, other apparatus, and accessories to control mechanical systems. C. Control system shall consist of sensors, indicators, actuators, final control elements, interface equipment, other apparatus, accessories, and software connected to distributed controllers operating in multiuser, multitasking environment on token -passing network and programmed to control mechanical systems. An operator workstation permits interface with the network via dynamic color graphics with each mechanical system, building floor plan, and control device depicted by point -and -click graphics.® D. Control system shall include the following: 1. Building lighting control system specified in Division 16 Section "Network Lighting Controls." a. BMS contractor shall provide a digital signal to the network lighting controllers for operation of all lighting systems for the facility. b. BMS contractor shall provide a 7 day/365 days a year schedule for programming the operation of the lighting system. 2. Power Monitoring of Electric Water Heaters. 3. Trending and Alarming required to implement the measurement and verification required by Part D of the IMPMV guidelines. 2.3 DDC EQUIPMENT A. Operator Workstation: One PC-based microcomputer(s) with minimum configuration as follows: 1. Motherboard: With 8 integrated USB 2.0 ports, integrated Intel Pro 10/100 (Ethernet), integrated audio, bios, and hardware monitoring. 2. Processor Intel Core 4 Quad Processor E4400, 2 MB L2 Cache, 2.00 GHz, 800 FSB. 3. Random -Access Memory: 2 GB Dual Channel DDR2 SDRAM at 667 MHz — 2DIMMS. 4. Graphics: Video adapter, minimum 128MB NVIDIA GeForce 8300GS 5. Monitor: 19 inches, LCD color. 6. Keyboard: QWERTY, 105 keys in ergonomic shape. 7. Floppy -Disk Drive: 1.44 MB. 8. Hard -Disk Drive: 300 GB. 9. 16X DVD -ROM Read/Write Drive INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 5 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 10. Mouse: Three button, optical. 11. Uninterruptible Power Supply: 2 kVa. 12. Operating System: Microsoft Windows XP Professional with high-speed Internet access. a. ASHRAE 135 Compliance: Workstation shall use ASHRAE 135 protocol and communicate using ISO 8802-3 (Ethernet) datalink/physical layer protocol. 13. Printer: Color, ink -jet type as follows: a. Print Head: 4800 x 1200 dpi optimized color resolution. b. Paper Handling: Minimum of 100 sheets. c. Print Speed: Minimum of 17 ppm in black and 12 ppm in color. 14. Application Software: a. I/O capability from operator station. b. System security for each operator via software password and access levels. c. Automatic system diagnostics; monitor system and report failures. d. Database creation and support. e. Automatic and manual database save and restore. f. Dynamic color graphic displays with up to 10 screen displays at once. g. Custom graphics generation and graphics library of HVAC equipment and symbols. h. Alarm processing, messages, and reactions. Trend logs retrievable in spreadsheets and database programs. j. Alarm and event processing. k. Object and property status and control. Automatic restart of field equipment on restoration of power. m. Data collection, reports, and logs. Include standard reports for the following: 1) Current values of all objects. 2) Current alarm summary. 3) Disabled objects. 4) Alarm lockout objects. 5) Logs. n. Custom report development. o. Utility and weather reports. p. Workstation application editors for controllers and schedules. q. Maintenance management. 15. Custom Application Software: a. English language oriented. b. Full -screen character editor/programming environment. c. Allow development of independently executing program modules with debugging/simulation capability. d. Support conditional statements. e. Support floating-point arithmetic with mathematic functions. f. Contains predefined time variables. B. Diagnostic Terminal Unit: Portable notebook -style, PC-based microcomputer terminal capable of accessing system data by connecting to system network with minimum configuration as follows: INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 6 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 1. System: With one integrated USB 2.0 port, integrated Intel Pro 10/100 (Ethernet), integrated audio, bios, and hardware monitoring. 2. Processor: Intel® CoreTM 2 Duo T5250 (2MB cache/1.5GHz/667Mhz FSB) 3. Random -Access Memory: 1GB3 Shared Dual Channel4 DDR2 SDRAM at 667MHz. Specifications - Memory 4. Graphics: Video adapter, minimum Intel® Integrated Graphics Media Accelerator X3100 5. Monitor: 13.3" UltraSharpTM WXGA display with TrueLifeTM 6. Keyboard: QWERTY 105 keys in ergonomic shape. 7. Hard -Disk Drive: 200 GB. 8. Integrated Slot -Load DVD+/-RW13 Drive 9. Pointing Device: Touch pad or other internal device. C. Control Units: Modular, comprising processor board with programmable, nonvolatile, random- access memory; local operator access and display panel; integral interface equipment; and backup power source. 1. Units monitor or control each I/O point; process information; execute commands from other control units, devices, and operator stations; and download from or upload to operator workstation or diagnostic terminal unit. 2. Stand-alone mode control functions operate regardless of network status. Functions include the following: a. Global communications. b. Discrete/digital, analog, and pulse I/O. c. Monitoring, controlling, or addressing data points. d. Software applications, scheduling, and alarm processing. e. Testing and developing control algorithms without disrupting field hardware and controlled environment. 3. Standard Application Programs: a. Electric Control Programs: Demand limiting, duty cycling, automatic time scheduling, start/stop time optimization, night setback/setup, on-off control with differential sequencing, staggered start, antishort cycling, PID control, DDC with fine tuning, and trend logging. b. HVAC Control Programs: Optimal run time, supply -air reset, and enthalpy switchover. c. Chiller Control Programs: Control function of condenser -water reset, chilled -water reset, and equipment sequencing. d. Programming Application Features: Include trend point; alarm processing and messaging; weekly, monthly, and annual scheduling; energy calculations; run-time totalization; and security access. e. Remote communications. f. Maintenance management. g. Units of Measure: Inch -pound and SI (metric). 4. Local operator interface provides for download from or upload to operator workstation or diagnostic terminal unit. 5. ASHRAE 135 Compliance: Control units shall use ASHRAE 135 protocol and communicate using ISO 8802-3 (Ethernet) datalink/physical layer protocol. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 7 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Local Control Units: Modular, comprising processor board with electronically programmable, nonvolatile, read-only memory; and backup power source. 1. Units monitor or control each I/O point, process information, and download from or upload to operator workstation or diagnostic terminal unit. 2. Stand-alone mode control functions operate regardless of network status. Functions include the following: a. Global communications. b. Discrete/digital, analog, and pulse I/O. c. Monitoring, controlling, or addressing data points. 3. Local operator interface provides for download from or upload to operator workstation or diagnostic terminal unit. 4. ASHRAE 135 Compliance: Control units shall use ASHRAE 135 protocol and communicate using ISO 8802-3 (Ethernet) datalink/physical layer protocol. E. I/O Interface: Hardwired inputs and outputs may tie into system through controllers. Protect points so that shorting will cause no damage to controllers. 1. Binary Inputs: Allow monitoring of on-off signals without external power. 2. Pulse Accumulation Inputs: Accept up to 10 pulses per second. 3. Analog Inputs: Allow monitoring of low -voltage (0- to 10-V dc), current (4 to 20 mA), or resistance signals. 4. Binary Outputs: Provide on-off or pulsed low -voltage signal, selectable for normally open or normally closed operation. 5. Analog Outputs: Provide modulating signal, either low voltage (0- to 10-V dc) or current (4 to 20 mA). 6. Tri-State Outputs: Provide two coordinated binary outputs for control of three-point, floating -type electronic actuators. 7. Universal I/Os: Provide software selectable binary or analog outputs. F. Power Supplies: Transformers with Class 2 current -limiting type or overcurrent protection; limit connected loads to 80 percent of rated capacity. DC power supply shall match output current and voltage requirements and be full -wave rectifier type with the following: 1. Output ripple of 5.0 mV maximum peak to peak. 2. Combined 1 percent line and load regulation with 100-mic.sec. response time for 50 percent load changes. 3. Built-in overvoltage and overcurrent protection and be able to withstand 150 percent overload for at least 3 seconds without failure. G. Power Line Filtering: Internal or external transient voltage and surge suppression for workstations or controllers with the following: 1. Minimum dielectric strength of 1000 V. 2. Maximum response time of 10 nanoseconds. 3. Minimum transverse -mode noise attenuation of 65 dB. 4. Minimum common -mode noise attenuation of 150 dB at 40 to 100 Hz. 2.4 ELECTRONIC SENSORS A. Description: Vibration and corrosion resistant; for wall, immersion, or duct mounting as required. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 8 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS B. Thermistor Temperature Sensors and Transmitters: 1. Manufacturers: a. Ebtron, Inc. b. I.T.M. Instruments Inc. c. RDF Corporation. 2. Accuracy: Plus or minus 0.5 deg F at calibration point. 3. Wire: Twisted, shielded -pair cable. 4. Insertion Elements in Ducts: Single point, 8 inches long; use where not affected by temperature stratification or where ducts are smaller than 9 sq. ft. 5. Averaging Elements in Ducts: 18 inches long, rigid; use where prone to temperature stratification or where ducts are larger than 10 sq. ft. 6. Insertion Elements for Liquids: Brass or stainless-steel socket with minimum insertion length of 2-1/2 inches. 7. Room Sensor Cover Construction: Manufacturer's standard locking covers. a. Set -Point Adjustment: Exposed. b. Set -Point Indication: Concealed. c. Thermometer: Concealed. d. Color: White. e. Orientation: Vertical. 8. Outside -Air Sensors: Watertight inlet fitting, shielded from direct sunlight. 9. Room Security Sensors: Stainless-steel cover plate with insulated back and security screws. C. Humidity Sensors: Bulk polymer sensor element. 1. Manufacturers: a. BEC Controls Corporation. b. General Eastern Instruments. c. MAMAC Systems, Inc. d. ROTRONIC Instrument Corp. e. TCS/Basys Controls. f. Vaisala. 2. Accuracy: 2 percent full range with linear output. 3. Room Sensor Range: 20 to 80 percent relative humidity. 4. Room Sensor Cover Construction: Manufacturer's standard locking covers. a. Set -Point Adjustment: Concealed. b. Set -Point Indication: Concealed. c. Color: White. d. Orientation: Vertical. 5. Duct Sensor: 20 to 80 percent relative humidity range with element guard and mounting plate. 6. Outside -Air Sensor: 20 to 80 percent relative humidity range with mounting enclosure, suitable for operation at outdoor temperatures of minus 22 to plus 185 deg F. 7. Duct and Sensors: With element guard and mounting plate, range of 0 to 100 percent relative humidity. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 9 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS D. Pressure Transmitters/Transducers: 1. Manufacturers: a. BEC Controls Corporation. b. General Eastern Instruments. c. MAMAC Systems, Inc. d. ROTRONIC Instrument Corp. e. TCS/Basys Controls. f. Vaisala. 2. Static -Pressure Transmitter: Nondirectional sensor with suitable range for expected input, and temperature compensated. a. Accuracy: 2 percent of full scale with repeatability of 0.5 percent. b. Output: 4 to 20 mA. c. Building Static -Pressure Range: 0- to 0.25 -inch wg. d. Duct Static -Pressure Range: 0- to 5 -inch wg. 3. Water Pressure Transducers: Stainless-steel diaphragm construction, suitable for service; minimum 150-psig operating pressure; linear output 4 to 20 mA. 4. Water Differential -Pressure Transducers: Stainless-steel diaphragm construction, suitable for service; minimum 150-psig operating pressure and tested to 300-psig; linear output 4 to 20 mA. 5. Differential -Pressure Switch (Air or Water): Snap acting, with pilot -duty rating and with suitable scale range and differential. 6. Pressure Transmitters: Direct acting for gas, liquid, or steam service; range suitable for system; linear output 4 to 20 mA. 2.5 STATUS SENSORS A. Status Inputs for Fans: Differential -pressure switch with pilot -duty rating and with adjustable range of 0- to 5 -inch wg. B. Status Inputs for Pumps: Differential -pressure switch with pilot -duty rating and with adjustable pressure -differential range of 8 to 60 psig, piped across pump. C. Status Inputs for Electric Motors: Comply with ISA 50.00.01, current -sensing fixed- or split -core transformers with self -powered transmitter, adjustable and suitable for 175 percent of rated motor current. D. Current Switches: Self -powered, solid-state with adjustable trip current, selected to match current and system output requirements. E. Electronic Valve/Damper Position Indicator: Visual scale indicating percent of travel and 2- to 10-V dc, feedback signal. F. Water -Flow Switches: Bellows -actuated mercury or snap -acting type with pilot -duty rating, stainless-steel or bronze paddle, with appropriate range and differential adjustment, in NEMA 250, Type 1 enclosure. 1. Manufacturers: a. BEC Controls Corporation. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 10 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS b. I.T.M. Instruments Inc. 2.6 FLOW MEASURING STATIONS A. Air Flow Measuring Device: Provide where indicated multi -point thermal dispersion airflow traverse stations for continuous measurement of air volume. Each traverse station shall consist of a multiple array Dual "bead -in -glass" sensing locations. Air flow measurement station shall be sized to match actual duct size. Sensor density shall comply with manufactures recommendations (Density type) to insure specified accuracy in actual installation field conditions/location. 1. Air flow measurement station shall be + 2% of reading, with 0.25% repeatability. a. Provide Bacnet interface for BMS system interface. BMS shall monitor the following points at each AFM location: 1) Instaneous Airflow 2) Time weighted airflow average 3) Temperature b. Acceptable Manufacture/Model: 1) Ebtron Gold Series - GTN116-PD 2) Or approved equal 2. Chilled Water Flow: Provide chilled water monitoring station consisting of a chilled water flow meter, chilled water supply and return water temperature sensors utilizing matching calibrated sensors. a. The BCS shall monitor chilled water usage in "ton -hours" or "kiloton -hours", with an accuracy of plus or minus 0.75% with a turn down range from 0.1fps to 33 fps. b. Acceptable Manufacture/Model: 1) Onicon F3200 with System 10 BTU Meter 2) Or approved equal 2.7 THERMOSTATS A. Manufacturers: 1. Erie Controls. 2. Danfoss Inc.; Air -Conditioning and Refrigeration Div. 3. Heat -Timer Corporation. 4. Sauter Controls Corporation. 5. tekmar Control Systems, Inc. 6. Theben AG - Lumilite Control Technology, Inc. Low -Voltage, On -Off Thermostats: NEMA DC 3, 24-V, bimetal -operated, mercury -switch type, with adjustable or fixed anticipation heater, concealed set -point adjustment, 55 to 85 deg F set - point range, and 2 deg F maximum differential. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 11 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS C. Immersion Thermostat: Remote -bulb or bimetal rod -and -tube type, proportioning action with adjustable throttling range and adjustable set point. D. Electric, Low -Limit Duct Thermostat: Snap -acting, single -pole, single -throw, manual -reset switch that trips if temperature sensed across any 12 inches of bulb length is equal to or below set point. 1. Bulb Length: Minimum 20 feet . 2. Quantity: One thermostat for every 20 sqft. of coil surface. 2.8 HUMIDISTATS A. Manufacturers: 1. MAMAC Systems, Inc. 2. ROTRONIC Instrument Corp. B. Duct -Mounting Humidistats: Electric insertion, 2 -position type with adjustable, 2 percent throttling range, 20 to 80 percent operating range, and single- or double -pole contacts. 2.9 ACTUATORS A. Electric Motors: Size to operate with sufficient reserve power to provide smooth modulating action or two -position action. 1. Comply with requirements in Division 15 Section "Common Motor Requirements for HVAC Equipment." 2. Permanent Split -Capacitor or Shaded -Pole Type: Gear trains completely oil immersed and sealed. Equip spring -return motors with integral spiral -spring mechanism in housings designed for easy removal for service or adjustment of limit switches, auxiliary switches, or feedback potentiometer. 3. Nonspring-Return Motors for Valves Larger Than NPS 2-1/2 : Size for running torque of 150 in. x Ibf and breakaway torque of 300 in. x Ibf . 4. Spring -Return Motors for Valves Larger Than NPS 2-1/2 Size for running and breakaway torque of 150 in. x Ibf . 5. Nonspring-Return Motors for Dampers Larger Than 25 Sq. Ft.: Size for running torque of 150 in. x Ibf and breakaway torque of 300 in. x Ibf . 6. Spring -Return Motors for Dampers Larger Than 25 Sq. Ft. : Size for running and breakaway torque of 150 in. x Ibf . B. Electronic Actuators: Direct -coupled type designed for minimum 60,000 full -stroke cycles at rated torque. 1. Manufacturers: a. Belimo Aircontrols (USA), Inc. 2. Valves: Size for torque required for valve close off at maximum pump differential pressure. 3. Dampers: Size for running torque calculated as follows: a. Parallel -Blade Damper with Edge Seals: 7 inch-Ib/sq. ft. of damper. b. Opposed -Blade Damper with Edge Seals: 5 inch-Ib/sq. ft. of damper. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 12 INDIAN RIVER COUNTY JULY25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS c. Parallel -Blade Damper without Edge Seals: 4 inch-Ib/sq. ft of damper. d. Opposed -Blade Damper without Edge Seals: 3 inch-Ib/sq. ft. of damper. e. Dampers with 2- to 3 -Inch wg of Pressure Drop or Face Velocities of 1000 to 2500 fpm : Increase running torque by 1.5. f. Dampers with 3- to 4 -Inch wg of Pressure Drop or Face Velocities of 2500 to 3000 fpm : Increase running torque by 2.0. 4. Coupling: V -bolt and V-shaped, toothed cradle. 5. Overload Protection: Electronic overload or digital rotation -sensing circuitry. 6. Fail -Safe Operation: Mechanical, spring -return mechanism. Provide external, manual gear release on nonspring-return actuators. 7. Power Requirements (Two -Position Spring Return): 24-V ac. 8. Power Requirements (Modulating): Maximum 10 VA at 24-V ac or 8 W at 24-V dc. 9. Proportional Signal: 2- to 10-V dc or 4 to 20 mA, and 2- to 10-V dc position feedback signal. 10. Temperature Rating: Minus 22 to plus 122 deg F. 11. Temperature Rating (Smoke Dampers): Minus 22 to plus 250 deg F . 12. Run Time: 12 seconds open, 5 seconds closed. 2.10 CONTROL VALVES A. Butterfly Valves: 200-psig, 150-psig maximum pressure differential, ASTM A 126 cast-iron or ASTM A 536 ductile -iron body and bonnet, extended neck, stainless-steel stem, field - replaceable EPDM or Buna N sleeve and stem seals. 1. Body Style: Wafer. 2. Disc Type: Aluminum bronze. 3. Sizing: 1-psig maximum pressure drop at design flow rate. 2.11 DAMPERS Manufacturers: 1. Air Balance Inc. 2. Don Park Inc.; Autodamp Div. 3. TAMCO (T. A. Morrison & Co. Inc.). 4. United Enertech Corp. 5. Greenheck 6. Ruskin B. Dampers: AMCA-rated, parallel -blade design; 0.108 -inch- minimum thick, galvanized -steel or 0.125 -inch- minimum thick, extruded -aluminum frames with holes for duct mounting; damper blades shall not be less than 0.064 -inch- thick galvanized steel with maximum blade width of 8 inches and length of 48 inches . 1. Secure blades to 1/2 -inch- diameter, zinc -plated axles using zinc -plated hardware, with oil -impregnated sintered bronze blade bearings, blade -linkage hardware of zinc -plated steel and brass, ends sealed against spring -stainless-steel blade bearings, and thrust bearings at each end of every blade. 2. Operating Temperature Range: From minus 40 to plus 200 deg F. 3. Edge Seals, Standard Pressure Applications: Closed -cell neoprene. 4. Edge Seals, Low -Leakage Applications: Use inflatable blade edging or replaceable rubber blade seals and spring-loaded stainless-steel side seals, rated for leakage at less INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 13 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS than 10 cfm per sq. ft. of damper area, at differential pressure of 4 -inch wg when damper is held by torque of 50 in. x Ibf; when tested according to AMCA 500D. 2.12 CONTROL CABLE A. Electronic and fiber-optic cables for control wiring are specified in Division 16 Section "Communications Horizontal Cabling." PART 3 - EXECUTION 3.1 EXAMINATION A. Verify that power supply is available to control units and operator workstation. 3.2 INSTALLATION A. Install software in control units and operator workstation(s). Implement all features of programs to specified requirements and as appropriate to sequence of operation. B. Connect and configure equipment and software to achieve sequence of operation specified. C. Verify location of thermostats, humidistats, and other exposed control sensors with Drawings and room details before installation. Install devices 48 inches above the floor. 1. Install averaging elements in ducts and plenums in crossing or zigzag pattern. D. Install automatic dampers according to Division 15 Section "Air Duct Accessories." E. Install damper motors on outside of duct in warm areas, not in locations exposed to outdoor temperatures. F. Install labels and nameplates to identify control components according to Division 15 Section "Identification for HVAC Piping and Equipment." G. Install hydronic instrument wells, valves, and other accessories according to Division 15 Section "Hydronic Piping." Install steam and condensate instrument wells, valves, and other accessories according to Division 15 Section "Steam and Condensate Heating Piping." I. Install refrigerant instrument wells, valves, and other accessories according to Division 15 Section "Refrigerant Piping." J. Install duct volume -control dampers according to Division 15 Sections specifying air ducts. K. Install electronic and fiber-optic cables according to Division 16 Section "Communications Horizontal Cabling." 3.3 ELECTRICAL WIRING AND CONNECTION INSTALLATION INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 14 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS A. Install raceways, boxes, and cabinets according to Division 16 Section "Raceway and Boxes for Electrical Systems." B. Install building wire and cable according to Division 16 Section "Low -Voltage Electrical Power Conductors and Cables." C. Install signal and communication cable according to Division 16 Section "Communications Horizontal Cabling." 1. Conceal cable, except in mechanical rooms and areas where other conduit and piping are exposed. 2. Install exposed cable in raceway. 3. Install concealed cable in raceway. 4. Bundle and harness multiconductor instrument cable in place of single cables where several cables follow a common path. 5. Fasten flexible conductors, bridging cabinets and doors, along hinge side; protect against abrasion. Tie and support conductors. 6. Number -code or color -code conductors for future identification and service of control system, except local individual room control cables. 7. Install wire and cable with sufficient slack and flexible connections to allow for vibration of piping and equipment. Connect manual -reset limit controls independent of manual -control switch positions. Automatic duct heater resets may be connected in interlock circuit of power controllers. E. Connect hand -off -auto selector switches to override automatic interlock controls when switch is in hand position. 3.4 FIELD QUALITY CONTROL Manufacturer's Field Service: Engage a factory -authorized service representative to inspect, test, and adjust field -assembled components and equipment installation, including connections, and to assist in field testing. Report results in writing. B. Perform the following field tests and inspections and prepare test reports: 1. Operational Test: After electrical circuitry has been energized, start units to confirm proper unit operation. Remove and replace malfunctioning units and retest. 2. Test and adjust controls and safeties. 3. Test calibration of electronic controllers by disconnecting input sensors and stimulating operation with compatible signal generator. 4. Test each point through its full operating range to verify that safety and operating control set points are as required. 5. Test each control loop to verify stable mode of operation and compliance with sequence of operation. Adjust PID actions. 6. Test each system for compliance with sequence of operation. 7. Test software and hardware interlocks. C. DDC Verification: 1. Verify that instruments are installed before calibration, testing, and loop or leak checks. 2. Check instruments for proper location and accessibility. 3. Check instrument installation for direction of flow, elevation, orientation, insertion depth, and other applicable considerations. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 15 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS 4. Check instrument tubing for proper fittings, slope, material, and support. 5. Check installation of air supply for each instrument. 6. Check flow instruments. Inspect tag number and line and bore size, and verify that inlet side is identified and that meters are installed correctly. 7. Check pressure instruments, piping slope, installation of valve manifold, and self- contained pressure regulators. 8. Check temperature instruments and material and length of sensing elements. 9. Check control valves. Verify that they are in correct direction. 10. Check DDC system as follows: a. Verify that DDC controller power supply is from emergency power supply, if applicable. b. Verify that wires at control panels are tagged with their service designation and approved tagging system. c. Verify that spare I/O capacity has been provided. d. Verify that DDC controllers are protected from power supply surges. Replace damaged or malfunctioning controls and equipment and repeat testing procedures. 3.5 ADJUSTING A. Calibrating and Adjusting: 1. Calibrate instruments. 2. Make three-point calibration test for both linearity and accuracy for each analog instrument. 3. Calibrate equipment and procedures using manufacturer's written recommendations and instruction manuals. Use test equipment with accuracy at least double that of instrument being calibrated. 4. Control System Inputs and Outputs: a. Check analog inputs at 0, 50, and 100 percent of span. b. Check analog outputs using milliampere meter at 0, 50, and 100 percent output. c. Check digital inputs using jumper wire. d. Check digital outputs using ohmmeter to test for contact making or breaking. e. Check resistance temperature inputs at 0, 50, and 100 percent of span using a precision -resistant source. 5. Flow a. Set differential pressure flow transmitters for 0 and 100 percent values with 3 -point calibration accomplished at 50, 90, and 100 percent of span. b. Manually operate flow switches to verify that they make or break contact. 6. Pressure: a. Calibrate pressure transmitters at 0, 50, and 100 percent of span. b. Calibrate pressure switches to make or break contacts, with adjustable differential set at minimum. 7. Temperature: a. Calibrate resistance temperature transmitters at 0, 50, and 100 percent of span using a precision -resistance source. INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 16 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS b. Calibrate temperature switches to make or break contacts. 8. Stroke and adjust control valves and dampers without positioners, following the manufacturer's recommended procedure, so that valve or damper is 100 percent open and closed. 9. Stroke and adjust control valves and dampers with positioners, following manufacturer's recommended procedure, so that valve and damper is 0, 50, and 100 percent closed. 10. Provide diagnostic and test instruments for calibration and adjustment of system. 11. Provide written description of procedures and equipment for calibrating each type of instrument. Submit procedures review and approval before initiating startup procedures. B. Adjust initial temperature and humidity set points. C. Occupancy Adjustments: When requested within 12 months of date of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to Project during other than normal occupancy hours for this purpose. END OF SECTION 230900 INSTRUMENTATION AND CONTROL FOR HVAC 230900 - 17 INDIAN RIVER COUNTY JULY 25, 2014 INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS SECTION 230993 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. Related Sections include the following: 1. Division 23 Section "Instrumentation and Control for HVAC" for control equipment and devices and for submittal requirements. 1.3 DEFINITIONS A. DDC: Direct digital control. 1.4 CENTRAL REFRIGERATION EQUIPMENT SEQUENCES A. Start and Stop Condenser -Water Pump(s): 1. Enable: Allow pump to start when water is in cooling tower: a. Input Device: Water pressure transducer. b. Output Device: Hard wired through motor starter; DDC system binary output. c. Action: Confirm water in cooling -tower sump. 2. Enable: When outdoor -air temperature conditions are met: a. Input Device: DDC system outdoor -air temperature. b. Output Device: Hard wired through motor starter; DDC system binary output. c. Action: Confirm outdoor -air temperature is above 50 deg F. 3. Enable: When demand conditions are met: a. Input Device: DDC system software demand. b. Action: Confirm cooling demand from ventilation system(s). 4. Initiate: a. Input Device: DDC system time schedule. b. Output Device: Binary output. c. Action: Energize pump(s). SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 1