Indian River County Turner <br /> { <br /> R Administration Complex <br /> Final GMP Summary <br /> Qualifications & Assumptions <br /> Report Date : August 16, 2005 <br /> Drawings : <br /> no clarification <br /> Bid Package 15 Fire Protection <br /> Specifications : <br /> 1 Ref , Section 13915 - 2- 2 . 3 & 2 . 4 and 15300 -3 - 2 . 03 . 6 . 1 , 2 : The GMP includes black steel <br /> schedule 10 piping for sizes 2 . 5 " & above and black steel schedule 40 piping for sizes 2" <br /> & below . <br /> 2 Ref . Section 13915 - 10 - 4 . 2 . D . 1 . b : The GMP includes controls from five (5) relay panels to <br /> fourteen ( 14 ) motorized dampers required ( not shown ) to regulate FM - 200 gas volume . <br /> Controls to operate fire/smoke dampers for the Sprinkler/FM200 systems is furnished and <br /> installed by the Fire Alarm contractor . <br /> 3 Section 15300 : The GMP is based on water supply flow rates provided in the <br /> specifications per Staley Consulting , Inc . <br /> 4 The GMP excludes the following : <br /> a . Ref . Section 13915 -3 -2 . 8 : Dry pipe system , including air compressor , dry type <br /> sprinklers , dry valves and piping . <br /> b . Ref . Section 13915-9 -3 . 16 and 15300 - 9 -3 . 01 . E : Cleaning and painting the exterior of <br /> sprinkler piping . Galvanized piping is not painted . Painting of exposed piping is <br /> provided by Section 09900 . <br /> c . Ref . Section 13915 - 10 -4 . 2 . D . 1 . b : Graphic annunciator panels for FM200 systems . <br /> 5 The sprinklers heads are included within 3 " of the center of the ceiling tiles . <br /> Drawings : <br /> 1 Ref . 1 - FP1 . 2 . 1 and 2- FP1 . 1 . 1 : The GMP includes 155 degree white concealed heads as <br /> shown ; upright heads are 155 degree brass quick response and one foot from deck ; other <br /> upright heads are 200 degree on sprig - ups , one foot from deck to be relocated in the <br /> future ; sidewall heads are 200 degree brass for bottom of elevator pits and covered <br /> exterior patio . <br /> 2 Ref . 1 - FP1 . 2 . 1 and 2 - FP1 . 1 . 1 : All heads will be within 3 " of center of tile . <br /> 3 The GMP excludes the following : <br /> a . Pre - engineered and dry chemical fire protection systems for kitchen hoods . <br /> b . Preaction , dry- pipe and anti -freeze loop fire protection systems . <br /> Page 17 <br />