shall be transmitted to the panel manufacturer . Any discrepancy between the <br /> information shown on the plans and that provided by the electric company shall be <br /> brought to the attention of the Engineer. <br /> B , Components <br /> The control panel shall include power distribution components for a duplex motor control <br /> center including but not limited to the following components : <br /> 1 . Main Circuit Breaker <br /> 2 , Generator Circuit Breaker w/Mechanical Interlock <br /> 3 , Surge Arrestor <br /> 4 , Motor Circuit Breaker <br /> 5 , Motor Starters <br /> 6 , 120 V . Duplex Receptacle with 15 Amp . Breaker <br /> 7 . Control Power Circuit Breaker <br /> g . Generator Receptacle <br /> The control panel shall include control components including but not limited to the <br /> following : <br /> 1 , Control Relays <br /> . 2 . Automatic Alternator <br /> 3 , Hand-Off-Auto Switches <br /> 4 , Run Lights <br /> 5 , Elapsed Time Meters <br /> 6 , Exterior Alarm Horn <br /> T Exterior Flashing Alarm Lamp <br /> g . Phase monitor and shutoffs for each pump <br /> 9 , Seal failure detector with indicator lamp and reset for each pump <br /> 10 . RTU data acquisition and control system <br /> C . Component Requirements <br /> 1 . All motor branch circuit breakers, motor starters and control relays shall be of highest <br /> industrial quality , securely fastened to the removable back panels with screws and <br /> lock washers . Back panels shall be tapped to accept all mounting screws . Self- <br /> tapping screws shall not be used to mount any component. <br /> 2 , A thermal-magnetic circuit breaker, appropriately sized for the service and ground <br /> fault interrupting capacity, as manufactured by Square D Company , or approved <br /> equal , shall be furnished for the main breaker. All circuit breakers shall be sealed by <br /> the manufacturer after calibration to prevent tampering . A motor circuit breaker <br /> shall be provided for each motor starter. Each motor circuit breaker shall be <br /> adequately sized to meet the pump motor and station operating conditions . <br /> 3 . A mechanical disconnect mechanism shall be installed on each circuit breaker to <br /> provide a means of disconnecting power to the pump motors . Operator handles for <br /> the disconnect mechanisms shall be located on the exterior of the control <br /> compartment door. <br /> 4 , An open frame, across-the -line, NEMA rated, magnetic motor starter, Bulletin 709 <br /> as manufactured by Allen-Bradley Company , or approved equal, shall be furnished <br /> 02539 — Submersible Pump Station (Rev. ) <br /> 025394 <br />