Laserfiche WebLink
6 <br /> ANSWER NO . 11 <br /> Roll- up Door/Window —Metal that is Hurricane Rated <br /> QUESTION NO. 12 <br /> Please confirm the model # of the drink display cooler on the equipment list. (Section 45 <br /> 1 . 6 . 6 . a ) <br /> ANSWER NO . 12 <br /> True model No . GDM49 or substitute as approved by Owner. (Will be reflected in Addendum <br /> No . 2 – Technical Specifications . ) <br /> QUESTION NO. 13 <br /> Please confirm the lavatory sink model #, the True model No . GDM - 19 is not a sink. (Section <br /> 45 . 1 . B. 6 . h ) <br /> ANSWER NO. 13 <br /> The Advance Tabco Model #7- PS-86 or substitute as approved by Owner. (Will be reflected in <br /> Addendum No . 2 On Technical Specifications ) <br /> QUESTION NO. 14 <br /> Confirm only one electrical room is required for the building and not one in each restroom . <br /> (Section 45 . 1 . 13 . 7 . b . 25 ) <br /> ANSWER NO. 14 <br /> Only one ( 1 ) electrical room is required for the concession/restroom building. <br /> QUESTION NO . 15 <br /> The chain link fence specifications and detail on Sheet C-3 conflicts with technical <br /> specifications section 16, FDOT specifications, which takes precedent ? <br /> ANSWER NO. 15 <br /> Chain link fence shall be black vinyl coated, 6' high, 9 gauge wire (6 gauge w/ vinyl coating) . <br /> QUESTION NO . 16 <br /> Section 47 of the Technical Specifications, part C, line 4, calls for fence post spacing of 8' <br /> maximum, this conflicts with fence specifications and detail on Sheet G3 as well as FDOT <br /> specification, what post spacing should be provided ? <br /> FAPublic Works\ENGINEERING DIVISION PROJECTS\ 1126 - South Co Park Multi Purpose Fields\Admim\Meetings\Pre-bid Meeting Minutes I1 - <br /> 0542.doc <br />