v , <br /> SUBARTICLE 346- 10 . 1 (Page 337) is deleted and the following substituted : <br /> 34640 . 1 General : When a concrete acceptance strength test result falls more than 500 <br /> psi below the specified minimum strength, and the Department determines that an investigation <br /> is necessary, make an investigation into the structural adequacy of the LOT of concrete <br /> represented by that acceptance strength test result at no additional expense to the Department . <br /> The Engineer may also require the Contractor to perform additional strength testing as necessary <br /> to determine structural adequacy of the concrete . <br /> Furnish either a structural analysis performed by the Specialty Engineer to <br /> establish strength adequacy or drilled core samples as specified in 34640 . 3 to determine the in- <br /> place strength of the LOT of concrete in question at no additional expense to the Department. <br /> Obtain the Engineer ' s approval before taking any core samples . When the concrete is deemed to <br /> have low strength, obtain and test the cores and report the data to the Engineer within 14 days of <br /> the 28 day compressive strength tests . Core strength test results obtained from the structure will <br /> be accepted by both the Contractor and the Department as the in-place strength of the LOT of <br /> concrete in question . The core strength test results will be final and used in lieu of the cylinder <br /> strength test results for determination of structural adequacy and any pay adjustment. The <br /> Department will calculate the strength value to be the average of the compressive strengths of the <br /> three individual cores . This will be accepted as the actual measured value . <br /> SUBARTICLE 34640 . 2 (Pages 337 — 338) is deleted and the following substituted. <br /> 34640 .2 Determination of Structural Adequacy : If core strength test results are less <br /> than 500 psi below the specified minimum strength, consider the concrete represented by the <br /> cores structurally adequate . If the core strength test results are more than 500 psi below the <br /> specified minimum strength, the Department will consider the concrete represented by the cores <br /> structurally questionable . Submit a structural analysis performed by the Specialty Engineer. If <br /> the results of the structural analysis indicate adequate strength to serve its intended purpose with <br /> adequate durability, and is approved by the Department, the Contractor may leave the concrete in <br /> place subject to the requirements of 346- 11 , otherwise , remove and replace the LOT of concrete <br /> in question at no additional expense to the Department. <br /> SUBARTICLE 346- 11 . 2 (Page 338) is deleted and the following substituted. <br /> 34641 .2 Basis for Pay Adjustments : When an acceptance strength test result falls more <br /> than 500 psi below the specified minimum strength, core samples may be obtained in accordance <br /> with ASTM C 42 from the respective LOT of concrete represented by the low acceptance <br /> strength test result for determining pay adjustments . Price adjustment will be applied to the <br /> certified invoice price the Contractor paid for the concrete or the precast product . <br /> SECTION 346 (Pages 317 — 340) is expanded by the following new Article : <br /> 34642 Pay Reduction for Plastic Properties <br /> - 126 - <br /> FPID ( S ) : 423186 - 1 - 58 - 01 <br /> 77 <br /> jj <br /> nv <br />