Laserfiche WebLink
INDIAN RIVER COUNTY JULY 25, 2014 <br />INTERGENERATIONAL RECREATION CENTER 100% CONSTRUCTION DOCUMENTS <br />C. Fire -Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at <br />pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for <br />firestopping specified in Division 07 Section "Penetration Firestopping." <br />3.2 SLEEVE -SEAL -FITTING INSTALLATION <br />A. Install sleeve -seal fittings in new walls and slabs as they are constructed. <br />B. Assemble fitting components of length to be flush with both surfaces of concrete slabs and <br />walls. Position waterstop flange to be centered in concrete slab or wall. <br />C. Secure nailing flanges to concrete forms. <br />3.3 SLEEVE AND SLEEVE -SEAL SCHEDULE <br />A. Use sleeves and sleeve seals for the following piping -penetration applications: <br />1. Exterior Concrete Walls above Grade: <br />a. Piping Smaller Than NPS 6. <br />2. Concrete Slabs -on -Grade: <br />a. Piping Smaller Than NPS 6. <br />END OF SECTION 230517 <br />SLEEVES AND SLEEVE SEALS FOR HVAC PIPING 230517 - 2 <br />