ANSWER NO. 4 <br />Cost of 6" Fire Main shall be included in the bid price for "Construction Intergenerational Building including Slab, <br />Building, Doors, Windows and all Items as indicated on the Plan Specifications and in the Contract Documents <br />(Complete and Ready for use)." <br />QUESTION NO. 5 <br />There is a bid item for 4" HDPE (N-12) 180 LF, the plans do not show where this is to be installed. Please clarify as <br />to where this is to be installed. <br />ANSWER NO. 5 <br />Bid item for 4" HDPE (N-12) 180 LF has been changed to 380 LF. This will be for tying into the existing underdrains <br />between the Lacrosse fields. Also, two (2) additional Type C Inlets have been added, 260 LF of 15" CAP, 260 LF of <br />18" CAP, and 75 LF of 24" CAP to the existing swale on the west end of the Lacrosse field and drain to proposed <br />Wet Detention Pond. There are no existing construction plans for this additional work. <br />QUESTION NO. 6 <br />Sheet E1.00.01 top left - calls for "Type SLC Pole Base to be on detail 3/E1.00.03. This detail is missing. <br />ANSWER NO. 6 <br />This detail is on Sheet E1.03 <br />QUESTION NO. 7 <br />Sheet E1.00.01 calls for a 2000 Amp MTS. E1.00.02 (RISER) calls for a 1600 Amp MTS. Which is right? <br />ANSWER NO. 7 <br />1600A is correct as shown on the power riser diagram. <br />QUESTION NO. 8 <br />Upon review of the project documents we do see symbol for sound system speaker locations indicated on E1.03.01 <br />and E1.03.02 but there is no other information as to the sound system equipment or system configuration. Please <br />advise. <br />ANSWER NO. 8 <br />Owner is to provide local AV systems. <br />Page 3 of 7 <br />F:\Public Works\ENGINEERING DIVISION PROJECTS\I 135-S County Park Intergeneratiional Rec Facility \Admim\ADDENDUMS\Addendum No. 3 11-5-2014.doc <br />