Laserfiche WebLink
ADDENDUM NO. 3 11/5/2014 <br />3. Bell and Spigot Connections: <br />Joints in bell and spigot pipe shall be push -on, mechanical, or restrained <br />joints in accordance with AWWA Standard C-111 (ANSI 21.11-85), or <br />latest revision. Mechanical joint pipe set -screw type retainer glands will <br />not be permitted. <br />4. Flanged Connections: <br />Flanged pipe with screwed -on flanges shall be furnished with long hubs, <br />and the flanges shall be screwed on the threaded end of the pipe in the <br />shop, and the face of the flange and end of pipe refaced together. There <br />shall be no leakage through the pipe threads and the flanges shall be <br />designed to prevent corrosion of the threads from outside. The back of <br />the hub shall be caulked where the hub threads joint with the pipe. <br />5. Valve Box Adjustments: <br />Cost of valve nut extenders shall be included in cost of valve box <br />adjustments where needed. <br />E. Disinfecting Potable Water Pipelines <br />Before being placed in service, all potable water pipelines shall be chlorinated in accordance <br />with the latest edition of AWWA C-651, "Standard Procedure for Disinfecting Water Mains", <br />except that the use of tablets is strictly prohibited. The procedure shall be approved by the <br />Engineer. The location of the chlorination and sampling points will be as specified by the <br />Florida Department of Environmental Protection, Water Distribution System Permit. Taps for <br />chlorination and sampling shall be uncovered and backfilled by the Contractor, as required. <br />ITEM OF PAYMENT <br />Payment for the work specified in this item shall be made under: <br />Bid Item No <br />Bid Item No <br />Bid Item No. <br />Bid Item No. <br />Bid Item No. <br />indicated) - <br />Bid Item No. <br />Bid Item No. <br />Watermain <br />. 83 - Sanitary Sewer Manhole (4' - 6' Depth) - Per Each <br />. 84 - Sanitary Sewer Manhole (6' - 8' Depth) - Per Each <br />85 - 8" PVC Sanitary Sewer - Per Linear Foot <br />86 - 3" Potable Service - Per Each <br />87 - 8" Potable Water Main with Valves and Appurtences (as <br />Per Linear Foot <br />88 - Siamese Fire Truck Connection - Per Each <br />89 - Relocate Existing Fire Hydrant (Includes 40 LF - 6" PVC <br />- Per Each <br />Bid Item No. 90 - Furnish and Install Fire Hydrant Assembly (Complete with 6" <br />Gate Valve and Pipe) - Per Assembly <br />01025-32 Technical Specifications <br />F:\Public Works\ENGINEERING DIVISION PROJECTS11135-5 County Park Intergeneratiional Rec <br />Facilitv\Admim1ADDENDUMS\Technical Specs (SITE) -Addendum No. 311-5-2014 doc <br />