Laserfiche WebLink
the same raceway, except in load gutter in meter room. <br />(p) In the wiring of cold-storage plants and rooms or buildings <br />of similar character, all wires used for light, heat or power shall <br />be Installed In rigid galvanized or sherardized metal threaded conduit, <br />and galvanized metal outlet boxes, cut-out and distribution cabinets <br />and fittings installed. Conduits shall be installed in such manner that <br />they will drain to the outlets and cabinets conductors Installed in con- <br />duit must comply with the National Electrical Code Standard for damp <br />or wet locations. All conduits entering or leaving refrigeration boxes <br />must have an approved seal-off fitting, <br />(q) The minimum wire capacity for window display lighting <br />shall be not less than 100 watts per linear foot and shall not exceed <br />six outlets per circuit Including the convenience receptacles and not <br />more than two receptacles with each lighting circuit. The minimum <br />size wire for these circuits shall be 20arnp. capacity. A minimum <br />of two outlets shall be required at least one abov(� the one below. All <br />fixed lighting shall be equipped with switches. <br />(r) Permanently Installed electrical space heaters In bath - <br />rooms shall be installed so that heaters will not be easily exposed to <br />combustible materials. But said heaters shall not be installed behind <br />doors, under or near towel racks, or near shower curtains or window <br />curtains. trach heater must be on a separate circuit with a mininium <br />wire size of No. 12 AWG or larger. <br />(s) One branch-circuit for signs shall be provided for each <br />store frontage for each Individual occupancy, said outlets to termi - <br />nate outside, on or near the front of the building. Sign outlets and <br />window lighting shall be controlled by wall switches. (It is suggested <br />that these switches be installed near panel, so that time clock instal- <br />lation, if desired, will be conveniently located and less unsightly. <br />and (t) Sufficient bathroom a toilet lighting must be Installed <br />28 <br />