Laserfiche WebLink
(4) Underground direct burial circuits shall be adequately <br />sleeved under slabs, sidewalks, roads, flower beds, or <br />when entering or leaving a building. <br />To the total of these three, such demand factors as permitted <br />by N. E. C. should be applied. <br />Section 29. VOLTAGE DROP. The maximum allowable volt- <br />age drop shall be as follows: <br />(1) Lighting -- Mains and Feeders combined, 1% drop from <br />point of attachment to Service drops to point of distribu- <br />tton (panel) for branch circuits. Branches, 29V, from dis - <br />tribution panel to receivers. <br />(2) Power -- Mains and feeders combined, .37, from point of <br />attachment to service drop, to distribution panel. Branches, <br />1% from distribution point to receivers. <br />(3) tAghting and power combined -- The Maximum allowable <br />voltage drop for lighting and power combined shall be 17, <br />from point of service entrance to final distribution point. <br />Branches shall be In accordance with the above allowable <br />voltage drop. <br />Section 30, APPEALS - DECISIONS OF BOARD OF ADJUST- <br />MENTS AND APPRAIJS. Sections 112 and 113 of the Southern Standard <br />Building Code, 1965 Edition, adopted by reference In Article 11, <br />Section I., of this resolution as part of the Building Code, are hereby <br />adopted, as modified in the Building Code, and matte a part of this <br />Electrical Code. <br />Section 31, BOARD OF AD USTMENTS AND APPEAUS. The <br />Board of Adjustments and Appeals appointed under the, provisions of <br />the Building Code is hereby made the Board of Adjustments and Appeals <br />of the Electrical Code. <br />30 <br />