Provide a factory lubricated low friction, coilable, high-density conduit constructed over <br />high-density polyethylene (HDPE). Provide outer duct conduit with a smooth outer wall, <br />and inner wall, and ensure the conduit is capable of being coiled on reels and continuous <br />lengths, transported, stored outdoors and subsequently uncoiled for installation without <br />affecting its properties or performance. Include multi -duct conduit organizers at all points <br />where the multi -duct conduit enters and exits into a junction, pull box, splice vault, or <br />similar structure. Provide conduit spacers that are appropriately sized relative to the ducts. <br />7.4.3 HDPE Innerduct <br />Provide a factory lubricated, industry sized 1.5" or 2" inside diameter as listed in the plans, <br />low friction, coilable, conduit constructed of virgin HDPE innerduct. Said innerduct shall <br />conform to ASTM D — 2239 and meet the following minimum requirements: Smooth wall <br />SDR — 11, nominal outer diameter of 1.592 inches, minimum inner diameter 1.360 inches <br />and a minimum wall thickness of 0.106 inches. Provide conduit with a smooth outer wall <br />and ridged inner wall and ensure the conduit is capable of being coiled on reels in <br />continuous lengths, transported, stored outdoors subsequently uncoiled for installation <br />without affecting its properties or performance. Innerduct shall be furnished in the <br />following factory extruded colors: orange, white, black and yellow as specified. Red shall <br />be reserved for electric. <br />Provide mechanical duct plugs that provide a watertight barrier when installed in an <br />unused conduit or outer duct conduit. Provide duct plugs sized in accordance with the <br />conduit furnished. Provide duct plugs that are removable. All conduit shall come with <br />factory installed duct plugs to keep out dust, dirt, and water. <br />Provide mechanical sealing devices that provide a watertight barrier between the conduit <br />and communications cable. Provide mechanical sealing devices sized in accordance with <br />conduit furnished and with appropriately sized holes for the communications cable. <br />Provide mechanical sealing devices that are removable. <br />7.4.4 Secondary Underground Conduit <br />Furnish and install HDPE or PVC conduit sized per plans for additional pipe in common <br />trench. Install the proper size and quantity of conduits to be used in accordance with the <br />minimum conduit size and quantity requirements of the NEC and as approved by the <br />Owner. <br />7.4.5 Above Ground Conduit <br />Furnish and install conduit for above ground use (a riser assembly on a utility service pole <br />for the purpose of bringing power from above ground to underground conduit/duct, or <br />bridge mounted or other above ground structure) consisting of galvanized rigid steel (GRS), <br />aluminum, or Schedule 80 PVC conduit in accordance with ASTM D 1785, as approved by <br />the Owner. <br />Furnish and install Schedule 80 PVC conduit, aluminum or Rigid Metal Conduit (RMC) for <br />bridge crossings, attached to the bridge structures, under the parapet, wherever feasible <br />and applicable. All rigid steel conduit material utilized shall be compliant with UL -6, ANSI <br />C-80.1 and to Article 346 of the NEC. All aluminum conduits shall be aluminum 6063 <br />aluminum alloy, T — 1 Temper, ANCI C80.5, and NEC 250.118 (2). All required connectors, <br />adapters, fittings, conduit straps or "U" guard clamps and incidentals required and <br />necessary for the above ground installations shall be galvanized and provided to construct <br />a complete conduit/duct system. <br />No reducing couplings or reduction in the inside diameter of conduit shall be permitted. <br />No intermediate <br />metallic conduit (IMC) or thin — wall type electrical conduit shall be permitted for outdoor <br />use. <br />Furnish and install galvanized metal conduit grounding bushing, or aluminum metal <br />conduit grounding bushing on the terminating ends of all GRS/aluminum conduit runs. The <br />bushings shall have an insert made of plastic and or other suitable material to protect <br />25 <br />