Surge Protection: Primary surge suppression shall consist of a wall or flush mounted unit <br />with 12 AWG terminals with a maximum 80kA (8/202s), protecting lines L -N, L -G, L -L, <br />and N -G. The unit shall meet the following environmental requirements; <br />1. Ambient temperatures of -402F to 1852F (-402C to 852C working) and 95% RH (non - <br />condensing). Dimensions shall be 4.5"H x 2.9"W x 2.3"D; <br />2. A nine -outlet (seven switched, two un -switched) rack mounted surge suppressor unit <br />shall be installed. The maximum surge current shall be 84kA with a load current of 15A <br />or 20A at a working voltage of 120V 50/60Hz; <br />3. A 19" DIN rail kit assembly shall be installed and have enough space for 32 modular <br />surge suppressor devices (RJ11, RJ45, or BNC connector type) attached, meeting the <br />following criteria: ambient temperature of -402F to 1852F (-202C to 852C working) and <br />95% RH (non -condensing). Dimensions shall be 5.04"H x .99"W x 2.25"D <br />j) Common Grounding System: A floor mounted 12 -position ground bar is to be provided <br />with the cabinet. <br />7.9.5 Outer Cabinet Construction <br />The cabinet shall contain R-4 insulation to control the effect of environmental conditions. Cabinet shall <br />be of 1/8", 5052 Aluminum construction with white powder coat finish to eliminate rusting. Outer door <br />shall have NEMA 3R rated with neoprene gasketing for maximum equipment protection and shall have <br />heavy-duty 3 -point hardware. All hinges shall be 1/8" aluminum with a stainless steel piano hinge, or <br />continuous door length stainless steel hinges. <br />7.9.6 Inner Cabinet (NEMA 4) Construction <br />The cabinet shall be a NEMA 4 rated cabinet with approximate dimensions of 20"W x 24"H x 12"D. The <br />cabinet shall be constructed of 16-guage stainless steel or other non -corrosive material. The cabinet shall <br />contain one 12-guage mounting plate with 10"-32" x 2" treaded hole pattern mounted to the rear of the <br />cabinet. The cabinet shall contain one heat sink mounted to the outside rear of the inner cabinet tangent <br />to the mounting plate. <br />7.9.7 Device Cabinet Base <br />Install device cabinet base that provides an environmentally secure enclosure to house fiber optic splice <br />closure, fiber optic drop cable slack, data cable slack, and power cable slack. The base shall be specifically <br />fabricated to accommodate the detector cabinet as specified within this Section A268. Neoprene <br />gasketing shall be supplied by the device cabinet base vendor that shall be applied by the installation <br />contractor between the base and the detector cabinet. The device cabinet base shall meet or exceed the <br />following minimum requirements: <br />a) Outside dimensions shall be approximately 16"H x 40"W x 24"D or 16"H x 24"W x 24"D; <br />b) Shall be fabricated from 1/8" aluminum; <br />c) Shall have an epoxy powder coating; <br />d) Shall have a front access panel with captive stainless steel screws; <br />e) Shall have an open top and open bottom, each with a 2" lip for mounting and/or <br />attachment of the detector cabinet; <br />f) Shall have a conduit mounting plate of same size (width and depth), made of 1/4" <br />stainless steel 316. <br />g) All screws and hardware shall be stainless steel. 7.9.8 Base Plate <br />All bridge pedestals shall have the existing open cable raceways sealed. These raceways shall be sealed <br />by way of 1/4" stainless steel plates, anchored over the raceway by way of epoxy anchor drilled into the <br />pedestal at a minimum depth of 11/4". There shall be two sizes of base plates, 18" x 12" and 10" x 10". <br />The Contractor shall install the engineer's system manager supplied base plates where noted and/or <br />depicted within the plan set. <br />7.9.9 Hub Cabinet Type VI (Master Hub Cabinet) <br />39 <br />