Laserfiche WebLink
A. MOUNTING HEIGHTS: <br />(a) Receptacles at 18" or as noted <br />(b) Telephone outlets at 18" or as noted <br />B. RECEPTACLES: Wall receptacles shall be intermediate grade, duplex S- <br />wire grounding type. Devices shall be rated at 15A1125V. 'Receptacles and <br />switches shall be back and side -wired with screw terminals. <br />C. Power Outlets. Type and size as noted. <br />6. DISCONNECT SWITCHES <br />A. FfdSIBLE disconnect switches shall be furnished with enclosures as <br />required by exposures either NEMA 1 or 3R and shall be horsepower rated, <br />general duty with fuses as noted. <br />B. tvON-FUSIBLE disconnect switches shall be provided for all motors <br />located out of sight of motor controller and where indicated on the <br />drawings. Disconnect switches shall disconnect all ungrounded conductors. <br />C. FUSES to be furnished for fusible equipment. Motor fuses shall be Bus <br />I"usetrons rated between 125 and 150 percent of motor name plate rating. <br />7. PANELBOARD, LOADCENTER <br />A. Panelboard and loadcenters shall be as noted on plans with cover and <br />typewritten directory inside of cover. Panelboards shall be the product of <br />ITE, Square D or Cutler Hammer, <br />B. Panel Bus shall be copper. <br />S. LIGHTING FIXTURES <br />A. Provide lighting fixtures as indicated on die schedule. <br />9. IDEM - CATION <br />A. Tag all conductors and identify major conduits in or at wireways, panels, <br />pullboxes, switchboards, cabinets and similar items to assist in furore circuit <br />tracing. Conductor tabs shall be. nonconductive. <br />B. Identify all circuits and equipment to correspond with the plans and <br />specifications. <br />C. All switchgear will be labeled with engraved phenolic nameplates. <br />D. All junction boxes shall have type of system and voltage of contained <br />conductors stenciled on inside of box cover. <br />MA -3 <br />r <br />II <br />