Laserfiche WebLink
4D <br />a <br />,, <br />notice, the work of correcting such defect may be accomplished by the <br />owner and the contractor shall be liable for the cost of this work. <br />7. The contractor shall convey to the owner any additional guarantees or <br />warrantees provided by the manufacturer of an individual item of equipment <br />} or material. <br />2. RACEWAY <br />1 A. EMT may be used for all branch circuit wiring in areas above grade and <br />within the building. All EMT shall be galvanized. All EMT fittings shall be <br />steel compression type. <br />B. PVC, schedule 40, may be used for all branch circuit wiring below grade. <br />I C. GRC shall be used for wiring when transitioning from below grade to <br />l above grade and subject to physical damage. <br />3. WIRE AND CABLE <br />I <br />A. Conductors shall be copper. Insulation shall be type THHNnEWN for <br />sizes No. 12 to 8 AWG. For conductors No. 5 and larger, insulation shall <br />be d are ttype <br />be stranded. Branch conduit outlets shall be connected asTHW. Minimum. size wire No. 12Conductors No. 0indicalarger d er <br />13, COLOR CODES: Conductors shall be color coded throughout. Same color <br />shall be used for branch circuit wiring of a given phase. Conductors No. b <br />AWG and larger may be Black, but shall be identified with colored tape in <br />junction boxes, pull boxes, panels, and service equipment. <br />., (a) 120/208V - Shalt be Black, Red, or Blue with White for neutral. <br />(b) Continuity of neutrals of multi -wire branch circuits shall not be <br />made on terminals of any device. This will assure no opening of <br />neutral in replacement of device. <br />C. SPLICES: <br />(a) #10 and below - Scotchiok or equal <br />(b) #8 and larger - Hi Press or mechanical connector <br />(c) Epoxy splices shall be used for all below grade splices. <br />4. BOXES - <br />A. OUTLET" BOXES shall be one-piece or projection welded galvanized <br />stamped steel for gang sizes required. Sectional boxes will not be <br />acceptable. Boxes larger than standard shall be provided in accordance with <br />National Electrical Code where necessary to prevent crowding of wires. <br />k <br />5. WHiNG DEVICES <br />IGA-2. <br />