40 <br />40 <br />• <br />Preferred characteristics of this facility include: <br />• The buildings and its access road are located outside the Category 5 storm surge innundation. <br />• The buildings and its access road arc located outside the 500 -year floodplain (Zone X). <br />Marginal characteristics of this facility include: <br />• The building has a lightweight roof system. <br />• There is a limited exposure to large and small wind-borne debris within 300 feet of facility. <br />The building shows signs of deterioration. <br />• No verification of reinforced exterior walls. <br />• The building is within the Vulnerability Zone of two Section 302 facilities but with low release <br />potential. <br />Non-compliant characteristic of this facility include: <br />• The building; has unprotected windows and doors that [cad into shelter areas. <br />• No verification of wind parameters used in a 1965 design. <br />Retrofit Recommendation: <br />Mater <br />• Have a structural engineer evaluate roof system and define load path to determine modifications <br />required to resist uplift and bending forces. <br />Install shutters or other protective systems on unprotected systems windows to exterior doors to <br />meet the SSC Standard SSTD 12-94 of Dade County version of the South Florida Building <br />Code (Section 2314.1, 2314.5 and 1-2314.4). <br />Minor (Please note that while these minor retrofit recommendations will enhance the integrity of <br />shelter space evaluated they will not increase potential usable shelter square footage.) <br />• Remove potential lay -down hazards. <br />• Remove potential debris hazards. <br />• Secure portable classrooms and mobile homes on the site. <br />