I . Option <br /> a. 200 amp three phase meter can <br /> b . 200 amp main circuit breaker N3R 42 circuit panel with 8 three pole 30 amp breakers . <br /> c. Service feeders. (4) 3/0 conductors in a 2 %i' raceway. 150' <br /> d . Build Service Rack out of 2" galvanized pipe with galvanized uni-strut to accommodate <br /> meter can , electrical panel and one lighting contactor cabinet sized at 72" high , 36" wide <br /> and 12" deep . The lighting contactor will be provided by the sports lighting manufacturer <br /> and installed . <br /> e. Pull necessary permits <br /> 2. Ootion B <br /> a. 400 amp three phase meter can <br /> b. 400 amp main circuit breaker N3R 42 circuit panel with 8 three pole 60 amp breakers . <br /> c. Service feeders. (4) 500 mcm conductors in a 4" raceway. 150' <br /> d. Build Service Rack out of 2" galvanized pipe with galvanized uni-strut to accommodate <br /> meter can, electrical panel and one lighting contactor cabinet sized at 72" high , 36" wide <br /> and 12" deep . The lighting contactor will be provided by the sports lighting manufacturer <br /> and installed . <br /> e. Pull necessary permits <br /> 3 . Option C <br /> a . 600 amp three phase meter can <br /> b . 600 amp main circuit breaker N3R 42 circuit panel with 12 three pole 60 amp breakers . <br /> c. Service feeders . (2) 4" raceways with (4) 300 mcm conductors in a 4" raceway. 150' <br /> d . Build Service Rack out of 3" galvanized pipe with galvanized uni-strut to accommodate <br /> meter can , electrical panel and one lighting contactor cabinet sized at 72" high , 36" wide <br /> and 12" deep . The lighting contactor will be provided by the sports lighting manufacturer <br /> and installed . <br /> e. Pull necessary permits <br /> B. CONDUIT, PULL BOXES AND CONDUCTORS <br /> Provide equipment and labor to install conduit, pull boxes and conductors . All installations are to be <br /> in pvc schedule 40 pipe at a burial depth of 36" with twin conductors. <br /> C. LIGHTNING PROTECTION <br /> Surge Arrestors : UL labeled and rated for 277/480V, 3 phase, 4 wire, as manufactured by Erico <br /> (TDX-50) or equal and shall be attached to the bottom of the remote ballast enclosure and/or on <br /> line side of main electrical panel . <br /> Jacksonville Spec 04-24r5.doc 11 Created on 12/1/2006 4:32 PM <br />