Laserfiche WebLink
I. All conduits on exposed work shall be run at right angles to and parallel with the surrounding <br /> wall or slab . No diagonal runs will be allowed. Bends in parallel conduit runs shall be <br /> concentric . All conduits shall be run perfectly straight and true . <br /> J . Conduit stub outs for future construction shall be provided with threaded PVC end caps at each <br /> end . <br /> K . All earth, sod , etc . , moved during the installation of underground conduit shall be replaced by the <br /> contractor to its original state . <br /> L . Conduits terminating in gasketed enclosures shall be terminated with conduit hubs . <br /> M . All conduits terminating through concrete shall be painted with bitumastic from 6 inches below to <br /> 6 inches above slab . <br /> N . All exposed , outdoor PVC conduits and boxes shall be painted with two (2) coats of silver paint. <br /> O . The ends of all conduits terminating in panels , cabinets, and equipment shall be filled with <br /> silicone gel . Filling shall be done after the cable has been pulled in order to prevent moisture and <br /> insects in the terminating enclosure . <br /> END OF SECTION <br /> i <br /> 1 <br /> I <br /> i <br /> i <br /> 044572017 <br /> 16110 - 3 <br /> I <br />