Laserfiche WebLink
C. Combination Starter Units <br />1. Combination starters shall include a motor circuit protector (MCP) in series with a motor <br />controller and an overload protective device. The MCP shall have an adjustable magnetic <br />trip range up to 1000 percent of rated continuous current and a trip test feature. MCP's <br />shall be labeled in accordance with U1489. <br />2. Motor starters: 3 Pole, 600 Volt, shall be electrically operated. Provide NEMA sizes as <br />required for the specific horsepowers. Minimum size shall be NEMA Size I . Fractional <br />size starters are not acceptable. IEC rated starters shall not be acceptable. Starters shall <br />have 120 Volt encapsulated operating coils; individual control power transformers with <br />primary and secondary fuses and silver cadmium oxide renewable line contacts. <br />3. Multi -speed and reversing starters shall include two motor rated contactors mechanically <br />and electrically interlocked so that only one device may be energized at any time. <br />4. Reduced voltage starters: Solid state, six SCR, full wave type with adjustable current limit <br />and voltage ramp to control starting torque, automatic load sensing circuit to minimize <br />energy consumption, line and load side surge protection and noise suppression and <br />controlled deceleration adjustment to reduce the effects of surges caused by centrifugal <br />pump loads. Provide heat sinks and ventilation to remove heat from the structure. Each <br />starter shall include a motor horsepower rated isolation contactor to positively disconnect <br />the line voltage when the SCR control is off. Each solid state reduced voltage starter shall <br />include a by-pass full voltage motor starter (FVNR) which shall be capable of operating <br />the motor in an across the line start mode. The FVNR starter shall be controlled <br />independent of the SSRV so that in the event of the SSRV failure the motor will remain <br />operable via the FVNR by-pass starter. The SSRV and the FVNR by-pass shall be <br />completely isolated to allow for servicing and maintenance of either while the other <br />remains operable, provide all necessary contactors, controls, relays, wiring, etc. <br />5. Wye -delta starters shall be closed circuit transition for use with 6 or 12 lead motors. <br />6. Contactors: Electrically held, 120 VAC coil operator, suitable for tungsten, ballast, or <br />resistive non -motor loads, with over current protection, control transformer and contact <br />ratings and poles as necessary. <br />7. Motor overload protection: Standard, 3 Pole, thermal bi-metallic or melting alloy type, <br />with push -to -test feature. Electronic or adjustable overload relays will not be acceptable. <br />Overload relays for submersible pump motors shall be ambient compensated, quick trip, <br />Class 10. Overload relays shall be manually reset from outside the enclosure by means of <br />an insulated pushbutton. Provide auxiliary alarm contacts as necessary. <br />8. Auxiliary contacts: Form C, NEMA A600 rating, as required by the control schemes. <br />Provide 1 -normally open and 1 normally closed spare contacts on each starter. Additional . <br />auxiliary contacts shall be furnished as required by the control schematic. <br />9. Control power transformers: Two winding type, 120 VAC secondary, fused in accordance <br />with the NEC. Provide extra capacity as required. <br />044572017 <br />16480-5 <br />