Laserfiche WebLink
8 . Winding insulation class and treatment. <br /> 9 . Rated ambient temperature . <br /> 10 . Service factor. <br /> 11 . Voltage , phase , and frequency rating . <br /> 12 . Full load current at rated horsepower for application voltage . <br /> 13 . Starting code letter , or locked rotor KVA, or current . <br /> 14 . Special winding configuration such as part-winding , star-delta . <br /> 15 . Rated full load speed . <br /> 16 . Power Factor at full load, 75 percent, and 50 percent load . <br /> 17 . Motor efficiency, nominal and guaranteed values . <br /> 18 . Motor torque speed curves from zero to full load speed. <br /> 19 . Test results . <br /> 1 .05 FACTORY TESTING <br /> A. Each motor shall be shop tested to determine compliance with requirements of the IEEE, ANSI <br /> and NEMA. Tests shall be as follows: <br /> B . Motors less than 50 horsepower: Each motor shall be subjected to a standard short commercial <br /> test including the following: <br /> 1 . Running light current <br /> 2 . Locked rotor current <br /> 3 . High potential <br /> 4 . Winding resistance <br /> 5 . Bearing inspection <br /> C. Motors between 50 and 100 h.p . : Each motor shall be subjected to the above tests and shall be <br /> furnished with certified test results. <br /> D. Efficiency: Motors rated 25 through 100 h.p. shall be individually tested for efficiency. <br /> i <br /> 044572017 <br /> 16490 - 2 1 <br />