the same raceway,: except in load gutter in meter room. <br />(p) In the wiring of cold -storage plants and rooms or buildings <br />of similar character, all wires used for light, heat or power shall <br />be installed in rigid galvanized or sherardized metal. threaded conduit, <br />and galvanized metal outlet boxes, cut-out and distribution cabinets <br />and fittings installed. Conduits shall be installed in such manner that <br />they will drain to the outlets and cabinets conductors installed in con- <br />duit must comply with the National Electrical Code Standard for damp <br />or wet locations. All conduits entering or leaving refrigeration boxes <br />must have an approved seal -off fitting. <br />(q) The minimum wire capacity for window display lighting <br />shall be not less than 100 watts per linear foot and shall not exceed. <br />six outlets per circuit including the convenience receptacles and not <br />more than two receptacles with each lighting circuit. The minimum <br />size wire for these circuits shall be 20 amp. capacity. A minimum <br />of two outlets shall be required at least one above the one below. All <br />fixed lighting shall be equipped with switches. <br />(r) Permanently installed electrical space heaters :in.bath- <br />rooms shall be installed so that heaters will not be easily exposed to <br />combustible materials. But said heaters shall not be installed behind <br />doors, under or near towel racks, or near shower curtains or window <br />curtains. Each heater must be on a separate circuit with a minimum <br />wire size of No. 12 AWG or larger. <br />(s) One branch -circuit for signs shall be provided for each <br />store frontage for each individual occupancy, said outlets to termi - <br />nate outside, on or near the front of the building. Sign outlets and <br />window lighting. shall be controlled by wall switches. (It is suggested <br />that these switches be installed near panel, so that time clock instal- <br />lation, if desired, will be conveniently located and less unsightly. ) <br />(t) Sufficient bathroomand toilet lighting must be installed <br />28 a Ok . �. PAGE134 <br />FEB :2 11961 <br />