Laserfiche WebLink
(4) Underground direct burial circuits shall be adequately <br />sleeved under slabs, sidewalks, roads, flower beds, or <br />when entering or leaving a building. <br />To the total of these three, such demand factors as permitted <br />by N. E. C. should be applied. <br />Section 29. VOLTAGE DROP. The maximum allowable volt- <br />age drop shall be as follows: <br />(1) Lighting -- Mains and Feeders combined, 1% drop from. <br />point of attachment to Service drops to point of distribu- <br />tion (panel) for branch circuits. Branches, 2% from dis <br />tribution panel to receivers. <br />(2) Power -- Mains and feeders combined, 3% from pointof <br />attachment to service drop, to distribution panelBranches, <br />1% from distribution point to receivers. <br />(3) Lighting and power combined -- The Maximum allowable <br />voltage drop for lighting and power combined shall be' 1% <br />from point of service entrance to final distribution point. <br />Branches shall be in accordance with the above allowable <br />voltage drop. <br />Section 30. APPEALS - DECISIONS OF BOARD OF ADJUST- <br />MENTS AND APPEALS. Sections 112 and 113 of the Southern' Standard <br />Building Code, 1965 Edition, adopted by reference in Article II, <br />Section 1', of this resolution as part of the Building Code, are hereby <br />adopted, as modified in the Building Code, and made a part of this <br />Electrical Code. <br />Section 31. BOARD OF ADJUSTMENTS AND APPEALS. The <br />Board. of Adjustments and Appeals appointed under the provisions of <br />the Building Code is hereby made the Board of Adjustments and Appeals <br />of the Electrical Code. <br />30 <br />FEB. 2 1 1969 <br />BOOK ` `: PAGE - <br />