<br />put said heaters shall not be installed behind doors, under or near towel racks,
<br />or near shower curtains or windo'a curtains. Each heater must be on a separate
<br />circuit with a minimuai wire size of No. 12 At -,'G or larger.
<br />(s) One branch -circuit for signs shall be provided for each store
<br />frontage for each individual occupancy, said outlets to terminate outside, on
<br />or near the front of the building. Sign outlets and window lighting shall be
<br />controlled by wall switches, (It is suggested that these switches be installed
<br />near panel, so that time clock installation, if desired, will be conveniently
<br />located and less unsightly.)
<br />(t) SuFficient bathroom and toilet lighting must be installed and
<br />must be controlled by wall switches only.
<br />(u) For protection against rust or corrosion, all steel or iron out-
<br />let boxes, junction boxes, cabinets, gutters, and similar type equipment subject
<br />to rust or corrosion, shall be protected with a zinc or cadmium coating by
<br />either the galvanizing or sherardizing process.
<br />(v) Wiring of slim line or end to end fixtures shall be as follows:
<br />Asbestos 1,000 volt No. 14 wire or RH No. 12 wire will be accepted for circuit
<br />wiring o; fixtures that are installed end to end, to the extent of the supply
<br />of that circuit passing through fixture that it supplies. The only permitted
<br />use of the fixture as a raceway would be for those fixtures approved by the
<br />Underwriters for that purpose; with special raceways, and RH No. 12 wiring would
<br />be accepted for additional circuits when installed according to this approval.
<br />Gas and oil burning equipment: Each unit shall be on a separate
<br />circuit and be provided with a pilot light and switch located near the entrance_
<br />to the room where unit is installed: Minimum wire size No, 12 or larger,
<br />(w) Swimming pools: All conduits, junction boxes, reinforcing
<br />steel, filter pump equipment, lighting fixtures and similar metallic equipment
<br />must be bonded together and connected to a coT-.-rion ground, Metallic parts of
<br />ladders and diving boards must also be grounded, All underwater pool lights
<br />must be of approved low voltage type.
<br />Section 28. FEEDERS. The carrying capacity of each feeder or sub -
<br />feeder shall be based on the number of separate circuits which it supplies,
<br />conputed as follows:
<br />(1) Overhead lighting circuits--assas:ed as having 1,000 watts per
<br />circuit for each 15 -amp, circuit.
<br />(2) Convenience outlet circuits--assm.2d as having 1,000 watts per
<br />circuit.
<br />(3) Pion -itemized and heavy duty circuit --specified load for which
<br />designed.
<br />(4) Underground direct burial circuits shall be adequately sleeved
<br />under slabs, sid-:•)alks, roads, flo:)er beds, or :when entering
<br />or leaving a building,
<br />To the total of these three, such demand factors as permitted by
<br />PI E.0 should be applied.
<br />Section 29. VOLTAGE DROP. The maxi -um allowable voltage drop shall
<br />be as follo'as:
<br />(1) Light;nsand Feeders combined, 1% drop frog) point of at-
<br />- ,o Service drops to point of distribution (panel) for branch circuits.
<br />i;rr; •cw s, 2', fro„ distribution panel to receivers.
<br />(2) PO::er--.:'lr and feeders co.mbin=d, 3" fro,!I point of zlttachr;l,enl
<br />to s_riice drop, to distribution panel. brancil•es, 17; from distribution point
<br />(3) Li,,htir end no:r r co.abinod--Thnaximu,u allo;flble voltage drop
<br />an(' p0'r;-�r CU:`"llib_L Shc:ll b,-' 1i. IrJ.a point 01' sr, 'tiiGC e!ltl'AlIC2 t0
<br />pink. (;r�!nc!,''; ,hall ue in arcordi+r,cc uiLh th t!bovc
<br />( rOd .