Laserfiche WebLink
B. The Contractor shall employ a disinfection method approved by the Engineer and Owner, <br />and shall fully satisfy the Owner that adequate disinfection has been achieved prior to <br />placing a facility on-line. <br />C. The Contractor, in the presence of the Owner, will be responsible for the collection of all <br />water samples. The samples shall be collected in accordance with best management <br />processes in Chapter 17-550, 17-555 and 17-560, F.A.C. and submitted to a NELAC <br />approved analytical laboratory for analyses of the required constituents. <br />D. The cost of all disinfection work shall be included in the Lump Sum Bid and the <br />Contractor shall pay for all bacteriological clearance tests. <br />1.27 SERVICES OF MANUFACTURERS' FIELD SERVICE TECHNICIAN <br />A. Bid prices of equipment furnished under Divisions 11, 14, 1.5, and 16 shall include the <br />cost of a competent field service technician of the Manufacturers of all equipment to <br />supervise the installation, adjustment, and testing of the equipment and to instruct the <br />Owner's operating personnel on operation and maintenance. The approved Manufacturer's <br />operation and maintenance data as specified in Section 01730 shall be delivered to the <br />Engineer prior to instructing the Owner's personnel. This supervision may be divided into <br />two or more time periods as required by the installation program or as directed by the <br />Engineer. <br />