Laserfiche WebLink
do <br />4 <br />W <br />1. Manufacturer, trade name, catalog number and <br />supplier of each product and item of equipment <br />actually installed. <br />+ 2. Changes made by field order or by change <br />order. <br />1.05 SUBMITTAL <br />A. At Contract close-out, deliver Record Documents to <br />Engineer for the owner. <br />B. Accompany submittal with transmittal letter in <br />duplicate, containing: <br />1. Date <br />2. Project title and number <br />3. Contractor's name and address <br />4. Title and number of each Record Document <br />5. Signature of Contractor or his authorized <br />representative <br />1.06 AS -BUILT SURVEYS <br />A. CONTROL INFORMATION FOR AS -BUILT UTILITY SURVEY WORK <br />1. All as -built drawings shall state in 1" lettering <br />"AS -BUILT RECORD SURVEY" located in the bottom right <br />hand side of the drawing original and/or copies, <br />alone with the as -built date. <br />2. All as -built surveys shall meet the minimum <br />requirements of the Chapter 61G17, Florida <br />Administrative Code Pursuant to Section 472 of the <br />Florida Statures. All surveys shallbe based on a <br />minimum horizontal control Third Order, "Class 2". <br />3. All state plane coordinates shall be based on the <br />Florida State Plane horizontal Data (East Zone); <br />Florida High Precision Geodetic Network <br />(Superstation) and NAD 8311990 - final adjustment. <br />4. State plane coordiantes shall be physically tied to <br />a minimum of two known state plane coordiante <br />benchmarks that utilize number 3 above. State plane <br />coordinates shall be shown on survey at benchwa rks <br />used. <br />01720-3 <br />