Laserfiche WebLink
2. A nine -outlet (seven switched, two un -switched) rack mounted surge suppressor unit <br />shall be installed. The maximum surge current shall be 84kA with a load current of 15A <br />or 20A, at a working voltage of 120V 50/60Hz. <br />3. A 19" DIN Rail kit assembly shall be installed and have enough space for 32 modular <br />surge suppressor devices (11J11, RJ45, or BNC connector type) attached, meeting the <br />following criteria: ambient temperature of -402F to 1852F (-202C to 852C working) and <br />95% RH (non -condensing). Dimensions shall be 5.04"H x .99"W x 2.25"D. <br />h) Common Grounding System: A floor mounted, 12 -position ground bar, is to be provided <br />with the cabinet; <br />i) Cabinet Construction: <br />1. The cabinet shall contain R-4 insulation to control the effect of environmental <br />conditions. <br />2. Cabinet shall be of 1/8", 5052 Aluminum construction with white powder coat finish to <br />eliminate rusting. <br />3. Doors shall have NEMA 311 rated with neoprene gasketing for maximum equipment <br />protection and shall have heavy-duty 3 -point hardware on all doors. <br />4. All hinges shall be 1/8" aluminum with a stainless steel piano hinge, or continuous door <br />length stainless steel hinges. <br />7.9.4 Hub Cabinet Type IV (Model 336S Special) <br />Install cabinet that provides an environmentally secure enclosure to house ITS field device equipment, <br />subsystems and systems, lighting and surge protection. The cabinet shall be designed for the explicit use <br />of housing and protecting sensitive electronic equipment (Encoders, 10/100/1000 Ethernet switches, <br />media converters, port/terminal servers, fiber optics equipment, and other related components, etc.) <br />within a controlled environment necessary for the proper operation of installed electronic equipment. <br />The cabinet shall meet or exceed the following minimum requirements: <br />a) Size: Outside dimensions shall be approximately 48"H x 24"W x 24"D; <br />b) Cabinet Configuration: The cabinet is a single door cabinet with one (1) NEMA 4 rated <br />internal cabinet mounted to the interior of the outer cabinet; <br />c) Lighting: The cabinet shall include door activated 20W cool white fluorescent lights; <br />d) Electrical Outlets: One (1) duplex (GFI) receptacle shall be included with every cabinet; <br />e) Equipment Racks: One (1) 19" equipment rack, adjustable 4 -post design, with 5/8" - <br />5/8" —1/2" spacing with holes tapped for #12-24 screws, a rack -mounted drawer with <br />tabletop shall be included with the rack. Cable management guides shall be included <br />with the rack and shall be constructed of an 18-guage steel base plate with hook and <br />loop fasteners. Four (4), two (2) front, two (2) rear 19" horizontal cable management <br />guides and four (4), two (2) front, two (2) rear vertical cable management guides that <br />shall run the vertical length of the rack; <br />f) Air Handling / Filtration: The cabinet shall contain two (2) thermostatically controlled <br />fans, 100 cfm rated. The cabinet shall contain a filtered air intake vent featuring re- <br />usable, washable type filters; <br />g) Power Distribution: The cabinet shall contain one 480/120 Volt transformer (Dry Type, <br />10KVA). A 30A main breaker shall be provided in the cabinet and shall distribute power <br />to equipment, lighting, and outlets. The transformer and main breaker shall be mounted <br />inside the outer cabinet; <br />h) UPS: The cabinet shall contain one managed uninterruptible power supply. The UPS <br />shall be 19" rack mounted. The UPS shall be 120V input/120V output. Output power <br />capacity shall be 1400VA/1050Watts. The unit shall have a serial interface port for <br />management. The unit shall be no more than 3U high; <br />38 <br />