2. Stainless steel screens over all air openings. <br />3. Stainless steel nameplate. <br />4. Motor must be premium efficiency as determined by NEMA test mg 1-12.53d <br />(IEEE -112 test Method B). <br />5. The terminal housing for the motor is to be substantial fabricated steel or cast <br />ferrous construction, and be rotatable in 90 degree steps, or suitable to receive a <br />conduit from above, below or either side. The terminal housing is to be gasketed <br />between frame and box. Grounding provisions must be made inside the terminal <br />box by means of clamp type wire terminal. <br />6. The heater leads must be clearly identified with permanent tags. <br />7. Commercial test must be made on motor provided, including no-load current at <br />rated voltage, high potential, and locked rotor current. <br />2.11 COATINGS <br />A. The pump and motor shall be coated in accordance with Section 09900, and all paint in <br />contact with potable water must be NSF approved. <br />PART 3 - EXECUTION <br />3.01 GENERAL <br />A. The pump and its components shall be complete with a manufacturer's warranty for defects in <br />materials and workmanship for a period of one year from the time the pump is placed into <br />operation. <br />3.02 PRODUCT HANDLING <br />A. All parts shall be properly protected so that no damage or deterioration will occur during a <br />prolonged delay from the time of shipment until installation is completed and the units and <br />equipment are ready for operation. <br />3.03 PERFORMANCE <br />A. The manufacturer shall warrant that the performance of all pumps shall conform with <br />manufacturer's certified pump performance curves. The pumps must operate within the <br />tolerances of the Standards of the Hydraulic Institute. Curves published for similar pumps by <br />another manufacturer will not be acceptable for this purpose. <br />044572017 <br />11934-8 <br />