Laserfiche WebLink
2 . Stainless steel screens over all air openings . <br /> 3 . Stainless steel nameplate. <br /> 4 . Motor must be premium efficiency as determined by NEMA test mg 1 - 12 . 53d <br /> (IEEE- 112 test Method B) . <br /> 5 . The terminal housing for the motor is to be substantial fabricated steel or cast <br /> ferrous construction, and be rotatable in 90 degree steps , or suitable to receive a <br /> conduit from above, below or either side . The terminal housing is to be gasketed <br /> between frame and box. Grounding provisions must be made inside the terminal <br /> box by means of clamp type wire terminal . <br /> 6 . The heater leads must be clearly identified with permanent tags . <br /> 7 . Commercial test must be made on motor provided, including no-load current at <br /> rated voltage, high potential , and locked rotor current . <br /> 2 . 11 COATINGS <br /> A. The pump and motor shall be coated in accordance with Section 09900 , and all paint in <br /> contact with potable water must be NSF approved. <br /> PART 3 - EXECUTION <br /> 3 .01 GENERAL <br /> A. The pump and its components shall be complete with a manufacturer's warranty for defects in <br /> materials and workmanship for a period of one year from the time the pump is placed into <br /> operation . <br /> 3 .02 PRODUCT HANDLING <br /> A. All parts shall be properly protected so that no damage or deterioration will occur during a <br /> prolonged delay from the time of shipment until installation is completed and the units and <br /> equipment are ready for operation. <br /> 3 .03 PERFORMANCE <br /> A. The manufacturer shall warrant that the performance of all pumps shall conform with <br /> manufacturer' s certified pump performance curves. The pumps must operate within the <br /> tolerances of the Standards of the Hydraulic Institute. Curves published for similar pumps by !. <br /> another manufacturer will not be acceptable for this purpose. <br /> I <br /> I <br /> 044572017 <br /> 11934-8 <br />