directly on AC power (across the line) at full motor speed and load. Motor noise when <br /> operating on VFD shall not exceed full speed measured noise levels when operating at <br /> reduced motor load and speed conditions between 40 and 100 percent of output <br /> frequency . Noise shall be measured in accordance with IEEE Standard 85 . Output noise <br /> filters shall be provided where necessary to meet this requirement . <br /> 7 . Speed regulation ±3 percent without the use of a motor mounted tachometer . <br /> F . Features <br /> 1 . Provisions for the following control signals for automatic and remote manual operations : <br /> a . Start/stop signal from a single remote dry contact closure (maintained contact) . <br /> b . A linear 4-20 mA, 24 VDC input signal for remote speed (output frequency) control <br /> proportional to 20 - 100 percent output speed (frequency) . This range (20 - 100 <br /> percent) shall be field adjusted for proper control coordination . Input signal isolation <br /> shall be provided . <br /> c . Remote setpoint adjustment from a single 0- 10 VDC input signal . Once the setpoint <br /> has been provided to the VFD, the VFD shall operate to maintain this setpoint <br /> through feedback loop control from a linear 4-20 mA, 24 VDC input signal . This <br /> operation shall continue until a new remote setpoint is received even if the remote <br /> setpoint signal is lost. <br /> 2 . Controller keypad to program drive parameters as specified herein. <br /> 3 . Hand/off/automatic selector switch with auxiliary contacts as required by the Drawings. <br /> I <br /> 4 . Potentiometer or equivalent for manual speed (output frequency) control . <br /> 5 . Drive controller output digital type indicator and transmitter calibrated in percent of <br /> maximum output frequency. Transmitter shall provide a linear, isolated, 4-20 mA, 24 <br /> VDC output proportional to 0 - 100 percent (initial setting) of maximum output <br /> ifrequency. <br /> 6 . Incoming line molded-case switch or disconnect, mechanically interlocked with the <br /> variable frequency drive cabinet door handle, shall be provided. These shall be 250A, <br /> minimum with a minimum withstand rating of 25 ,000 amperes or as indicated on the <br /> drawings . These switches shall be padlockable in the "OFF" position. Incoming line <br /> i circuit breakers or fuses as required by the VFD manufacturer shall be provided. These <br /> shall be current-limiting if specified by the manufacturer. <br /> 7 . 120V a.c . control circuitry. <br /> 8 . Provision for automatic emergency shutdown without rampdown, in any mode, actuated <br /> by large, red, illuminated, local emergency pushbutton. <br /> I <br /> ' 9 . One set of DPST auxiliary contacts for each remote indication of status as required by the <br /> Drawings . <br /> 1 <br /> 044572017 <br /> 16483 -5 <br />