directly on AC power (across the line) at full motor speed and load. Motor noise when <br />operating on VFD shall not exceed full speed measured noise levels when operating at <br />reduced motor load and speed conditions between 40 and 100 percent of output <br />frequency. Noise shall be measured in accordance with IEEE Standard 85. Output noise <br />filters shall be provided where necessary to meet this requirement. <br />7. Speed regulation ±3 percent without the use of a motor mounted tachometer. <br />F. Features <br />1. Provisions for the following control signals for automatic and remote manual operations: <br />a. Start/stop signal from a single remote dry contact closure (maintained contact). <br />b. A linear 4-20 mA, 24 VDC input signal for remote speed (output frequency) control <br />proportional to 20 - 100 percent output speed (frequency). This range (20 - 100 <br />percent) shall be field adjusted for proper control coordination. Input signal isolation <br />shall be provided. <br />c. Remote setpoint adjustment from a single 0-10 VDC input signal. Once the setpoint <br />has been provided to the VFD, the VFD shall operate to maintain this setpoint <br />through feedback loop control from a linear 4-20 mA, 24 VDC input signal. This <br />operation shall continue until a new remote setpoint is received even if the remote <br />setpoint signal is lost. <br />2. Controller keypad to program drive parameters as specified herein. <br />3. Hand/off/automatic selector switch with auxiliary contacts as required by the Drawings. <br />4. Potentiometer or equivalent for manual speed (output frequency) control. <br />5. Drive controller output digital type indicator and transmitter calibrated in percent of <br />maximum output frequency. Transmitter shall provide a linear, isolated, 4-20 mA, 24 <br />VDC output proportional to 0 - 100 percent (initial setting) of maximum output <br />frequency. <br />6. Incoming line molded -case switch or disconnect, mechanically interlocked with the <br />variable frequency drive cabinet door handle, shall be provided. These shall be 250A, <br />minimum with a minimum withstand rating of 25,000 amperes or as indicated on the <br />drawings. These switches shall be padlockable in the "OFF" position. Incoming line <br />circuit breakers or fuses as required by the VFD manufacturer shall be provided. These <br />shall be current -limiting if specified by the manufacturer. <br />7. 120V a.c. control circuitry. <br />8. Provision for automatic emergency shutdown without rampdown, in any mode, actuated <br />by large, red, illuminated, local emergency pushbutton. <br />9. One set of DPST auxiliary contacts for each remote indication of status as required by the <br />Drawings. <br />044572017 <br />16483-5 <br />